High-Voltage DC Relay
FTR-J2/FTR-K2W Series
FUJITSU COMPONENT has introduced relays as the key device for DC distribution
systems, which are currently under the spotlight as they contribute significantly to
advancing society while reducing CO2 and preventing global warming. “FTR-J2 Series”
are relays for high-voltage DCs that are optimal for server feeding in data centers and
so forth.“ FTR-K2W Series”are relays for medium-voltage and high-current DCs that
are ideal for battery protection in communication base stations and so forth.
which may cause abnormal heating in the Figure 1 Concept of Reduced Conversion Loss by DC Feeding (Example of a Data Center)
contact and its surroundings and lead to
failure or secondary disaster if it continues for Examples of current systems (3 conversions ⇒ large conversion loss)
a certain period. The conventional switching UPS Server
elements used in high-voltage DC circuits Conversion-1 Conversion-2 Conversion-3
CPU
had large gaps between contacts and were Commercial
power
AC Distribution
board AC DC DC AC AC DC
supplied in the large form of magnetic (power company)
HDD
switches or magnetic contactor that could not Storage battery
be reduced to a size suitable for built-in parts
on printed boards.
Example of DC feeding (1 conversion ⇒ reduced conversion loss)
High-voltage Conversion-1
UPS Server
FTR-J2 Series
In addition to having two built-in relays
with 1mm contact gap in one cover so that
Since there is no zero-cross point,
the arc can be completely extinguished it is easy to continue the arc when
even under high voltage and two contacts Arc is extinguished
the contact is open if the voltage
is high, making it easier to induce
at the zero-cross
connected in series to ensure 2mm total point.
abnormal heating or failure with
this energy.
contact gap, a permanent magnet is attached
atop the cover to extinguish the arc from
the contact opening and thereby achieve the
450VDC-10A rating in a small size. Figure 3 Positioning of the New High-voltage DC Relays
Coil 1 coil×2
Figure 4 FTR-J2 External Dimensions Figure 5 FTR-J2 Pin Assignments and Printing Diagram
24 +0.3
Printed board processing diagram
23.5+0.3
4-φ0.9±0.1 16.5±0.1 3.5±0.1
4-φ1.3±0.1
7.5±0.1
Pin assignments
+0.3
5±0.1
27
(23.5)
7.5±0.1
3.3
0.35 (1.75) 1
pre-soldering
0.4 7.5±0.1
φ0.5
7.5±0.1
(1.8) 3.5±0.1
(1.75)
5±0.1
(1.8) 16.5 3.5 7.5 5 7.5 16.5±0.1
Unit : mm (24)
Unit : mm
■ Load connection diagram for 450VDC, 10A ■ Load connection diagram for 200 VDC, 10A
(view from the back of the relay) (view from the back of the relay)
When a contact is open, the load and load power supply are completely The load and load power supply are connected even when the
isolated. The two opening contacts switch with independent contact is open with the normal connection method for using the relay.
mechanisms and are effective in preventing locking caused by arc
extinguish, preventing locking caused by contact surface wearing and
opening failure by contact weld.
Coil for driving Coil power supply Coil for driving Load
Load power supply
200VDC
Coil power supply
Load
Coil for driving Coil power supply Coil for driving Load
Load power supply
200VDC
Figure 7 FTR-K2W External Dimensions Figure 8 FTR-K2W Pin Assignments and Printing Diagram
(4.95)
4-φ1.6±0.1
34.9 36.5 (36.5)
4-φ0.9±0.1
Pin assignments
30.15
(34.9)
7.5±0.1
10±0.1
0.5 0.3 0.8
(3.45) 30±0.1
7.5±0.1
(4.95) 30
(3.45)
Unit : mm
Note: Two coils shall be connected in series to be used as one coil for driving.