CABLES CATALOGUE

PROVIDING
VERSION : 2011 R1

NATIONS WITH
CABLES

SAMA KEBEL SDN BHD


TERMS AND CONDITIONS

The contents of the pages of this catalogue are the copyrights of SAMA KEBEL SDN
BHD and all rights are reserved. All other intellectual property rights, including trade
marks, shall remain with SAMA KEBEL SDN BHD. The copying, publishing,
transmission to third parties or incorporation into any other work of part or all of the
material available in this catalogue in any form is prohibited SAVED FOR your
personal internal use. The terms and conditions apply to your use and your use of this
catalogue indicates your acceptance of the terms and conditions of this catalogue. If
you do not agree to the terms and conditions you must not use this catalogue. All
information provided in this catalogue (including but not limited to charts and
diagrams) is for illustration and reference purpose only and is believed to be correct at
the time of the last update to the relevant page. However, SAMA KEBEL SDN BHD
makes no warranties, express or implied, as to its accuracy, and accepts no liability
relating to its use. In the interests of continuous product improvement, SAMA
KEBEL SDN BHD reserves the right to alter specifications or materials as
appropriate. Purchasers are advised to refer to their consultants prior to making
purchases in order to determine the suitability of individual products for specific
applications.
Content Page

1 Company Profile 1-4

2 PVC-Insulated Power Cable A1 - A9

3 PVC-Insulated Cable B1 - B10

4 PVC-Insulated Instrumentation Cable C1 - C6

5 Flexible Cords F1 - F6

6 XLPE-Insulated Power Cable X1 - X10

7 Fire Resistant Cable Z1 - Z7


SAMA KEBEL SDN BHD (Company No. 221017-H)
Company Profile

O
OU RC
UR CO
OMMP
PAAN
NYY
SAMA KEBEL SDN BHD (Company No. 221017-H) is inaugurated on the 17 July
1991 under the Companies Act, 1965 as a private limited company. With the aim of
building for the future, SAMA KEBEL has built itself a sterling reputation specialising
in the manufacturing of wires and cables up to 1,000V ( low voltage range ). As a
Malaysian company, SAMA KEBEL has naturally aspired to use materials of
Malaysian origin and local personnel.

T
TH EL
HE LO
OCCA
ATTIIO
ONN
SAMA KEBEL is most strategically situated in the Rawang Perdana Industrial Estate,
state of Selangor Darul Ehsan, a mere 25 kilometers from the capital city of Malaysia,
Kuala Lumpur, making our factory premises link by modern expressways to market
centers and ports around the country.

O
OU RP
UR PR
ROOD
DUUC
CTTS
S
The core business of SAMA KEBEL is primarily focused on the manufacturing of low
voltage copper wires & cables ( up to 1,000V ) including:

 PVC or Low Smoke Halogen Free ( LSHF ) Wires


 PVC or LSHF or TP Flexible Cables
 PVC or XLPE or LSHF Armoured Cable
 PVC or XLPE or LSHF Non-Armoured Cable
 Multicore PVC or XLPE or LSHF Armoured Cable
Galvanised Steel Wire Armoured; Galvanised Steel Wire Braided;
Stainless Steel Wire Braided; Copper Wire Braided etc.
 Multicore PVC or XLPE or LSHF Non-Armoured Cable
 Multicore Screen Control Cable
Al-PET Overall Screened; Al-PET Individual and Overall Screened;
Copper Tape Screened; Copper Wire Screened;
Copper Wire Braided Screened;
Tinned Copper Wire Braided Screened etc.
 Armoured Fire Resistant Cable
 Non-Armoured Fire Resistant Cable
 Telephone Cables (Multipairs)
 Welding Cables
 Other products include:
 Auto cables
 Coaxial cable for household as well as industrial purposes.

1
SAMA KEBEL SDN BHD (Company No. 221017-H)
Company Profile

O
OU RS
UR SEER
RVVIIC
CEES
S
Our services include manufacturing tailor-made cables to suit clients’ specifications
upon request to suit variety of system and installation requirements, including but not
limited to adhering to clients’ specific cable construction such as multi-pair, multi-
core, armoured and stranded versions, using RoHS compliance materials and special
sheathing materials such as termite protection, rodent protection, ultra-violet
protection, flame retardant etc. The cable sheath colour can also be customised.

IIN
N--H
HOOU
US ER
SE REESSEEA
ARRC
CHHA
AN DD
ND DEEV
VEEL
LOOP
PMME
ENNT
T
Apart from the above, SAMA KEBEL has invested in fire testing equipment and has
the capabilities to conduct its research and development activities in-house for flame
retardant (such as IEC 60332-3 test methods) and fire resistant wires & cables (such
as BS 6387 Cat. C, W & Z test methods). The ongoing R & D activities of SAMA
KEBEL may include the development of higher flame retardant wires & cables and
fire resistant wires & cables with better flexibility.

With products and services ranging from power cables, control cables,
instrumentation cables, telephone cables and fire resistant cables, the overall strategy
of SAMA KEBEL is to build businesses around a focus technology core in order to
obtain maximum leverage of its core competencies. One of the strengths of SAMA
KEBEL is its investment in R & D activities which allows the company to produce
environmental friendly wires & cables ( such as using unleaded PVC compounds and
LSHF compounds ) and also enhanced fire performance wires & cables, which in turn
enable SAMA KEBEL to extend its market share in the region.

C
COOU
UNNT
TRRIIE
ESSE
EXXP
POOR
RTTE
EDD
Up to 31 May 2011, SAMA KEBEL had exported its wires & cables directly to the
following countries:

 Philippines  Singapore  Maldives


 Brunei  Indonesia  Myanmar
 New Zealand  Thailand  Hong Kong
 Korea  UAE  Qatar
 Vietnam  Germany  Lebanon
 Oman  Taiwan  Uganda
 Jordan  PNG

2
SAMA KEBEL SDN BHD (Company No. 221017-H)
Company Profile

P
PRRO
OJJE
ECCT
TSSS
SUUP
PPPL
LIIE
EDDR
REEFFEER
REEN
NCCE
E
Our wires & cables are supplied to the followings projects through our wholesaler: -

• Malaysia
Lynas Advanced Material Project Gebeng; Kemanman Substation in Kuantan;
Kukup Substation Johor; Tudan Substation Miri; Project KTM (OEM); HICOM;
Kuala Lumpur International Airport (KLIA); LRT; Stadium Batu Kawan Pulau
Pinang; Kuala Lumpur City Center (KLCC); Putrajaya; Bukit Jalil; Cyberjaya
Dengkil; Formula 1 Sepang; Kompleks Sukan Kuala Selangor; Jelantut Palm Oil
Mill Pahang; Kulai Indahpura Johor etc.

• Bandar Sri Begawan, Brunei


Dewan Majlis Building; Pusat Pemulihan Belia Lelaki Dan Perempuan;
Ammunition Bunker MT/GSE Complex; Street Lighting for Perpindahan Serasa;
Udang Fasa II, Tutong; Street Lighting Masjid Kampong; Kampong Meragang
Contract 8 & 5

• Hong Kong
Hong Kong Airport.

• Myanmar
Myanmar International Airport.

• Philippines
Rapu Rapu Mines Project; Subic Shipyard; Consolidated Industrial Gases Inc.
(CIGI); JGC Philippines

• Qatar
RAS Gas Limited; QATAR Petrochemical Company Ltd.

• Republic of Maldives
Maldives International Airport; Wataniya Resort; IGMH Hospital; Sonevagigili
Residential Villa Project; State Electricity Board

• Singapore
Shell Eastern Petroleum (Pte) Ltd Pulau Bukom

• Thailand
Petroluem Authority of Thailand; EGAT Plc Power Plant (Electricity Generating
Authority of Thailand)

• Vietnam
Dung Quat Oil Refinery

3
SAMA KEBEL SDN BHD (Company No. 221017-H)
Company Profile

Q
QUUA
ALLIIT
TYYA
ASSSSU
URRA
ANNC
CEE
SAMA KEBEL is an ISO 9002 accredited company with SIRIM (Standard Institute
and Research in Malaysia) and Suruhanjaya Tenaga approval.

The number one aim of SAMA KEBEL is to be a leader in providing quality and
reliability to our customers. Our policies include working towards total customers’
satisfaction with competitive price, prompt delivery and quality product. SAMA
KEBEL updates its employees on the latest developments in the industry as well as
increases their know-how by sending them to various courses throughout the year as
and when need arises in order to provide better products and services to its customers.

SAMA KEBEL has always committed to ensure that its high standards are adhered to
at every stage of the manufacturing process. An in-house team of skilled technicians
and engineers conducting constant stringent quality control checks are testament to
this pledge. In line with the company’s expansion plan, SAMA KEBEL will continue
to employ qualified staff to support the level of its business and operations.

T
TH EF
HE FU
UTTU
URRE
E
Aim for the excellent, SAMA KEBEL is not content to sit on its laurels. SAMA KEBEL
constantly upgrades its manufacturing equipment to the latest and most advance
technologies, increases its efficiencies, improves its research and development
capabilities for new products and materials, and establishes highest market reputation.
We are making plans to expand our product range to a wider array of power cables
and instrumentation cables. We are convinced that with our experience and dedicated
workforce, we will have the impetus to be at the forefront of the Malaysian cable
industry.

4
PVC-INSULATED
POWER CABLE
SAMA KEBEL SDN BHD

ARMOURED & NON


ARMOURED
PVC-INSULATED POWER CABLE
600/1000V, PVC Insulated, PVC Sheathed Unarmoured Cables

Application
Power cables for electricity supply are installed in open air, underground, in cable
ducts, outdoor and indoors, power stations, for industry and distribution boards as well
as in subscriber networks where mechanical damages are not to be expected. The
cables are suitable for continuous operation at a maximum conductor temperature of
70oC.

Construction : Technical Data :


Conductor : Circular stranded, circular compact stranded Voltage : 600/1000V
or sector shaped stranded plain annealed Temperature : Maximum 70oC
copper wire acc. to MS 69/BS 6360 class 2 Reference : MS 274 / BS 6346
Insulation : PVC (polyvinyl chloride) compound type TI1 Testing Voltage : 3500V
acc. to MS 138/BS 7655 Min. Bending Radius : 8 X Overall Diameter
Identification Single core – Red or Black
of cores: Two core – Red and Black
Three core – Red, Yellow, Blue
Four core – Red, Yellow, Blue, Black
Laying Up : Cores stranded together. Where necessary,

binder tapes and non-hygroscopic fillers may


be applied
Sheath : PVC (polyvinyl chloride) compound type TM1
acc. to MS 138/BS 7655
Colour: Black
(Termite protection sheathing upon request)
(Rodent protection sheathing upon request)
(UV protection sheathing upon request)
(Flame Retardant sheathing upon request)

A1
PVC-INSULATED POWER CABLE
600/1000V, PVC Insulated, PVC Sheathed Unarmoured Cables

Nominal Electrical Characteristics


Number
cross- Thickness Thickness Approx Approx Cond. Insulation
No. of and Short
sectional of of overall net Resistance Resistance
cores diameter Circuit Current
area of insulation oversheath diameter weight Max. at Min. at
of wires for 1 sec.
conductor 20oC 20oC
no mm2 no/mm mm mm mm kg/km /km M /km kA
50 19/1.78 1.4 1.4 15.1 610 0.387 5 5.8
70 19/2.14 1.4 1.4 16.9 830 0.268 5 8.1
95 19/2.52 1.6 1.5 19.4 1130 0.193 5 11.0
120 37/2.03 1.6 1.5 21.0 1385 0.153 5 13.9
150 37/2.25 1.8 1.6 23.2 1675 0.124 5 17.3
185 37/2.52 2.0 1.7 25.8 2120 0.0991 5 21.4
1 240 61/2.25 2.2 1.8 29.0 2730 0.0754 5 27.7
300 61/2.52 2.4 1.9 32.1 3420 0.0601 5 34.6
400 61/2.85 2.6 2.0 35.8 4335 0.047 5 46.2
500 61/3.20 2.8 2.1 39.6 5330 0.0366 5 57.7
630 127/2.52 2.8 2.2 43.8 6830 0.0283 5 72.7
800 127/2.85 2.8 2.3 48.3 8600 0.0221 5 92.3
1000 127/3.20 3.0 2.5 53.7 10700 0.0176 5 115
10 7/1.35 1.0 1.8 16.1 460 1.83 7 1.15
16 7/1.70 1.0 1.8 18.6 570 1.15 6 1.85
25 7/2.14 1.2 1.8 22.1 950 0.727 5 2.9
35 19/1.53 1.2 1.8 20.1 960 0.524 5 4.1
50 19/1.78 1.4 1.8 22.8 1260 0.387 5 5.8
70 19/2.14 1.4 1.9 25.5 1710 0.268 5 8.1
2 95 19/2.52 1.6 2.0 29.3 2300 0.193 5 11.0
120 37/2.03 1.6 2.1 31.8 2850 0.153 5 13.9
150 37/2.25 1.8 2.2 35.1 3480 0.124 5 17.3
185 37/2.52 2.0 2.4 39.1 4350 0.0991 5 21.4
240 61/2.25 2.2 2.5 43.9 5640 0.0754 5 27.7
300 61/2.52 2.4 2.7 48.7 7000 0.0601 5 34.6
400 61/2.85 2.6 2.9 54.2 8900 0.0470 5 46.2
Circular or compacted circular stranded conductors (Single core: All; 2 core: Up to and including 25mm2)
Sector shaped stranded conductors (2 core: 35mm2 and above)

A2
PVC-INSULATED POWER CABLE
600/1000V, PVC Insulated, PVC Sheathed Unarmoured Cables

Nominal Electrical Characteristics


Number
cross- Thickness Thickness Approx Approx Cond. Insulation
No. of and Short
sectional of of overall net Resistance Resistance
cores diameter Circuit Current
area of insulation oversheath diameter weight Max. at Min. at
of wires for 1 sec.
conductor 20oC 20oC
no mm2 no/mm mm mm mm kg/km /km M /km kA
10 7/1.35 1.0 1.8 17.0 590 1.83 7 1.15
16 7/1.70 1.0 1.8 19.7 820 1.15 6 1.85
25 7/2.14 1.2 1.8 23.5 1230 0.727 5 2.9
35 19/1.53 1.2 1.8 22.4 1380 0.524 5 4.1
50 19/1.78 1.4 1.8 25.5 1830 0.387 5 5.8
70 19/2.14 1.4 1.9 28.7 2490 0.268 5 8.1
3 95 19/2.52 1.6 2.1 33.3 3400 0.193 5 11.0
120 37/2.03 1.6 2.2 36.3 4190 0.153 5 13.9
150 37/2.25 1.8 2.3 40.0 5150 0.124 5 17.3
185 37/2.52 2.0 2.5 44.6 6430 0.0991 5 21.4
240 61/2.25 2.2 2.6 50.1 8350 0.0754 5 27.7
300 61/2.52 2.4 2.8 55.6 10350 0.0601 5 34.6
400 61/2.85 2.6 3.1 62.2 13230 0.0470 5 46.2
10 7/1.35 1.0 1.8 18.6 720 1.83 7 1.15
16 7/1.70 1.0 1.8 21.6 940 1.15 6 1.85
25 7/2.14 1.2 1.8 25.9 1540 0.727 5 2.9
35 19/1.53 1.2 1.8 25.4 1820 0.524 5 4.1
50 19/1.78 1.4 1.9 29.2 2450 0.387 5 5.8
70 19/2.14 1.4 2.0 33.0 3350 0.268 5 8.1
4 95 19/2.52 1.6 2.2 38.3 4560 0.193 5 11.0
120 37/2.03 1.6 2.3 41.8 5600 0.153 5 13.9
150 37/2.25 1.8 2.5 46.3 6920 0.124 5 17.3
185 37/2.52 2.0 2.6 51.3 8600 0.0991 5 21.4
240 61/2.25 2.2 2.8 58.0 11200 0.0754 5 27.7
300 61/2.52 2.4 3.1 64.6 13900 0.0601 5 34.6
400 61/2.85 2.6 3.3 72.0 17750 0.0470 5 46.2
2
Circular or compacted circular stranded conductors. (Up to and including 25mm )
2
Sector shaped conductors. (35mm and above)

A3
PVC-INSULATED POWER CABLE
600/1000V, PVC Insulated, PVC Sheathed Armoured Cables

Application
Power cables for electricity supply are installed in open air, underground, in cable
ducts, outdoor and indoors, power stations, for industry and distribution boards as well
as in subscriber networks where there is a risk of mechanical damage. The cables are
suitable for continuous operation at a maximum conductor temperature of 70 oC.

Construction : Technical Data :


Conductor : Circular stranded, circular compact stranded Voltage : 600/1000V
or sector shaped stranded plain annealed Temperature : Maximum 70oC
copper wire acc. to MS 69/BS 6360 class 2 Reference : MS 274 / BS 6346
Insulation : PVC (polyvinyl chloride) compound type TI1 Testing Voltage : 3500V
acc. to MS 138/BS 7655 Min. Bending Radius : 10 X Overall Diameter
Identification Single core – Red or Black
of cores: Two core – Red and Black
Three core – Red, Yellow, Blue
Four core – Red, Yellow, Blue, Black
Five core and above – (number) 1, 2, 3, 4,
5……, and the number shall be blue or black
printed on White cores
Laying Up : Cores stranded together. Where necessary,
binder tapes and non-hygroscopic fillers may
be applied
Bedding : Extruded PVC compound or lapped PVC tapes
Colour : Black
Armour : Single core - Consist of a single layer of non-
magnetic material, such as aluminium wire
Two core and above – Consist of a single layer
of galvanized steel wires
Sheath : PVC (polyvinyl chloride) compound type TM1
acc. to MS 138/BS 7655
Colour : Black
(Termite protection sheathing upon request)
(Rodent protection sheathing upon request)
(UV protection sheathing upon request)
(Flame Retardant sheathing upon request)

A4
PVC-INSULATED POWER CABLE
600/1000V, PVC Insulated, PVC Sheathed Armoured Cables

Electrical Characteristics
Nominal Number Nominal
No. Thickness Thickness Thickness Approx Approx Cond. Insulation Short
Cross- and Armour
of of of of Overall Net Resistance Resistance Circuit
Sectional Diameter of Wire
Cores Insulation Bedding Sheath Diameter Weight Max. at Min. at Current
Area Wires Diameter
20oC 20oC for 1 sec.
no mm2 no/mm mm mm mm mm mm kg/km /km M /km kA
70 19/2.14 1.4 0.8 1.25 1.6 21.1 1090 0.268 5 10.00
95 19/2.52 1.6 0.8 1.25 1.6 23.4 1410 0.193 5 13.50
120 37/2.03 1.6 1.0 1.6 1.7 26.3 1790 0.153 5 17.10
150 37/2.25 1.8 1.0 1.6 1.7 28.3 2110 0.124 5 21.40
185 37/2.52 2.0 1.0 1.6 1.8 30.8 2560 0.0991 5 26.40
1
240 61/2.25 2.2 1.0 1.6 1.9 34.1 3260 0.0754 5 34.30
300 61/2.52 2.4 1.0 1.6 1.9 37.0 3970 0.0601 5 42.70
400 61/2.85 2.6 1.2 2.0 2.1 42.0 5100 0.0470 5 57.20
500 61/3.20 2.8 1.2 2.0 2.1 45.6 6230 0.0366 5 71.50
630 127/2.52 2.8 1.2 2.0 2.2 49.7 7720 0.0283 5 70.00
1.5 7/0.53 0.6 0.8 0.9 1.4 12.3 290 12.1 10 0.17
2.5 7/0.67 0.7 0.8 0.9 1.4 13.6 350 7.41 9 0.29
4 7/0.85 0.8 0.8 0.9 1.4 15.1 435 4.61 8 0.46
6 7/1.04 0.8 0.8 0.9 1.5 16.5 520 3.08 7 0.69
10 7/1.35 1.0 0.8 1.25 1.6 20.1 850 1.83 7 1.15
16 7/1.70 1.0 0.8 1.25 1.6 21.9 1030 1.15 6 1.85
25 7/2.14 1.2 1.0 1.6 1.7 26.7 1640 0.727 5 2.9
35 19/1.53 1.2 1.0 1.6 1.8 24.9 1735 0.524 5 4.0
2 50 19/1.78 1.4 1.0 1.6 1.9 27.8 2080 0.384 5 5.8
70 19/2.14 1.4 1.0 1.6 1.9 30.4 2610 0.268 5 8.1
95 19/2.52 1.6 1.2 2.0 2.1 35.5 3650 0.193 5 11.0
120 37/2.03 1.6 1.2 2.0 2.2 38.0 4280 0.153 5 13.9
150 37/2.25 1.8 1.2 2.0 2.3 41.3 5050 0.124 5 17.3
185 37/2.52 2.0 1.4 2.5 2.4 46.4 6530 0.0991 5 21.4
240 61/2.25 2.2 1.4 2.5 2.5 51.2 8150 0.0754 5 27.7
300 61/2.52 2.4 1.6 2.5 2.7 56.4 9850 0.0601 5 34.6
400 61/2.85 2.6 1.6 2.5 2.9 61.9 11950 0.047 5 46.2
1.5 7/0.53 0.6 0.8 0.9 1.4 13.0 330 12.1 10 0.17
2.5 7/0.67 0.7 0.8 0.9 1.4 14.1 420 7.41 9 0.29
4 7/0.85 0.8 0.8 0.9 1.4 15..8 520 4.61 8 0.46
6 7/1.04 0.8 0.8 1.25 1.5 18.0 720 3.08 7 0.69
10 7/1.35 1.0 0.8 1.25 1.6 21.2 990 1.83 7 1.15
16 7/1.70 1.0 0.8 1.25 1.6 23.1 1240 1.15 6 1.85
25 7/2.14 1.2 1.0 1.6 1.7 28.2 1900 0.727 5 2.9
35 19/1.53 1.2 1.0 1.6 1.8 27.3 2220 0.524 5 4.0
3 50 19/1.78 1.4 1.0 1.6 1.9 30.5 2730 0.384 5 5.8
70 19/2.14 1.4 1.2 2.0 2.0 35.0 3820 0.268 5 8.1
95 19/2.52 1.6 1.2 2.0 2.1 39.3 4850 0.193 5 11.0
120 37/2.03 1.6 1.2 2.0 2.2 42.2 5780 0.153 5 13.9
150 37/2.25 1.8 1.4 2.5 2.4 47.5 7330 0.124 5 17.3
185 37/2.52 2.0 1.4 2.5 2.5 51.9 8830 0.0991 5 21.4
240 61/2.25 2.2 1.6 2.5 2.6 57.8 11140 0.0754 5 27.7
300 61/2.52 2.4 1.6 2.5 2.8 63.2 13500 0.0601 5 34.6
400 61/2.85 2.6 1.6 2.5 3.0 69.6 16750 0.047 5 46.2
Circular or compacted circular stranded conductors. (Single core: All; 2 Core: Up to and including 25mm2; 3 Core: Up to and including 25mm2).
Sector shaped stranded conductors. (2 Core: 35mm2 and above; 3 Core: 35mm2 and above)

A5
PVC-INSULATED POWER CABLE
600/1000V, PVC Insulated, PVC Sheathed Armoured Cables

Electrical Characteristics
Nominal Number Nominal
No. Thickness Thickness Thickness Approx Approx Cond. Insulation Short
Cross- and Armour
of of of of Overall Net Resistance Resistance Circuit
Sectional Diameter of Wire
Cores Insulation Bedding Sheath Diameter Weight Max. at Min. at Current
Area Wires Diameter
20oC 20oC for 1 sec.
no mm2 no/mm mm mm mm mm mm kg/km /km M /km kA
1.5 7/0.53 0.6 0.8 0.9 1.4 13.8 380 12.1 10 0.17
2.5 7/0.67 0.7 0.8 0.9 1.4 15.0 465 7.41 9 0.29
4 7/0.85 0.8 0.8 1.25 1.5 17.8 710 4.61 8 0.46
6 7/1.04 0.8 0.8 1.25 1.5 19.2 835 3.08 7 0.69
10 7/1.35 1.0 0.8 1.25 1.6 22.8 1175 1.83 7 1.15
16 7/1.70 1.0 1.0 1.6 1.7 26.3 1730 1.15 6 1.85
25 7/2.14 1.2 1.0 1.6 1.8 30.7 2350 0.727 5 2.9
35 19/1.53 1.2 1.0 1.6 1.9 30.5 2710 0.524 5 4.0
4
50 19/1.78 1.4 1.2 2.0 2.0 35.4 3850 0.384 5 5.8
70 19/2.14 1.4 1.2 2.0 2.1 39.2 4910 0.268 5 8.1
95 19/2.52 1.6 1.2 2.0 2.2 44.3 6370 0.193 5 11.0
120 37/2.03 1.6 1.4 2.5 2.4 49.3 8075 0.153 5 13.9
150 37/2.25 1.8 1.4 2.5 2.5 53.6 9540 0.124 5 17.3
185 37/2.52 2.0 1.6 2.5 2.6 59.0 11640 0.0991 5 21.4
240 61/2.25 2.2 1.6 2.5 2.8 65.7 14650 0.0754 5 27.7
300 61/2.52 2.4 1.6 2.5 3.0 72.0 17730 0.0601 5 34.6
5 0.8 0.9 1.4 14.3 420
7 0.8 0.9 1.4 15.2 495
10 0.8 1.25 1.5 19.0 770
12 0.8 1.25 1.5 19.4 830
1.5 7/0.53 0.6 12.1 10 0.17
19 0.8 1.25 1.6 22.2 1090
27 1.0 1.6 1.7 26.7 1600
37 1.0 1.6 1.8 29.2 1950
48 1.0 1.6 1.9 32.9 2360
5 0.8 0.9 1.5 16.3 550
7 0.8 1.25 1.5 18.0 750
10 0.8 1.25 1.6 21.9 1000
12 0.8 1.25 1.6 22.4 1090
2.5 7/0.67 0.7 7.41 9 0.29
19 1.0 1.6 1.7 26.6 1650
27 1.0 1.6 1.8 30.7 2100
37 1.0 1.6 1.9 34.0 2610
48 1.2 2.0 2.1 39.5 3550
5 0.8 1.25 1.5 19.0 810
7 0.8 1.25 1.6 20.5 960
10 1.0 1.6 1.7 26.1 1500
4 7/0.85 0.8 4.61 8 0.46
12 1.0 1.6 1.7 26.8 1620
19 1.0 1.6 1.8 30.5 2170
27 1.2 2.0 2.0 37.1 3200
Circular or compacted circular stranded conductors. (4 Core: Up to and including 25mm2; 5 Core and above: All).
Sector shaped stranded conductors. (4 Core: 35mm2 and above)

A6
PVC-INSULATED POWER CABLE
INSTALLED IN AIR
Current Ratings for PVC Insulated, PVC-Sheathed, Unarmoured Cables
600/1000V MS 274/BS 6346
Single core Two core Three and four core
Nominal
area of Three cables spaced # Three cables trefoil touching Approx. volt Approx. volt
Current Current
conductor Current Approx. volt drop Current Approx. volt drop drop per amp drop per amp
rating rating
rating per amp per metre rating per amp per metre per metre per metre
mm2 amp mV Amp mV Amp mV amp mV
1.5
2.5
4
6
10 66 4.30 56 3.80
16 86 2.80 73 2.40
25 116 1.70 97 1.50
35 145 1.30 120 1.10
50 185 0.83 170 0.82 170 0.94 150 0.82
70 235 0.60 220 0.58 220 0.66 185 0.57
95 300 0.47 270 0.43 265 0.49 230 0.42
120 345 0.40 310 0.35 305 0.40 265 0.35
150 395 0.35 360 0.30 350 0.34 305 0.29
185 460 0.33 420 0.25 410 0.29 350 0.25
240 585 0.32 495 0.22 485 0.24 415 0.21
300 680 0.31 575 0.19 550 0.21 475 0.18
400 780 0.28 660 0.18 630 0.19 550 0.17
500 890 0.27 760 0.16
630 1030 0.25 870 0.15
800 1170 0.23 990 0.15
1000 1290 0.22 1100 0.14
# Adjacent cable sufaces separated by one cable diameter.

Current Ratings for PVC Insulated, PVC-Sheathed, Armoured Cables


600/1000V MS 274/BS 6346
Single core
Two core Three and four core
Nominal Two cables spaced # Three cables trefoil touching
area of
Approx. volt Approx. volt
conductor Current Approx. volt drop Current Approx. volt drop Current Current
drop per amp drop per amp
rating per amp per metre rating per amp per metre rating rating
per metre per metre
mm2 amp mV amp mV amp mV amp mV
1.5 21 29 18 25
2.5 30 18 25 16
4 39 12 33 9.6
6 50 7.4 42 6.3
10 69 4.3 58 3.8
16 90 2.8 77 2.4
25 120 1.7 102 1.5
35 150 1.3 125 1.1
50 195 0.87 180 0.82 175 0.94 155 0.82
70 245 0.65 230 0.58 220 0.66 190 0.57
95 300 0.52 280 0.44 270 0.49 235 0.42
120 345 0.45 325 0.36 310 0.40 270 0.35
150 390 0.41 370 0.31 355 0.34 310 0.29
185 440 0.38 425 0.27 410 0.29 355 0.25
240 520 0.35 500 0.23 485 0.24 420 0.21
300 575 0.33 565 0.20 550 0.21 475 0.18
400 630 0.32 640 0.19 620 0.19 550 0.17
500 690 0.31 720 0.18
630 760 0.31 810 0.16
800 820 0.30 870 0.16
1000 880 0.29 940 0.15
#Adjacent cable surfaces separated by one cable diameter
Basic Assumptions
o o
Ground temperature : 25 C Ground thermal resistivity : 1.2 C m/W
o o
Ambient air temperature : 30 C Maximum conductor temperature : 70 C
Depth of laying : 0.5 metre ( to the centre of cable or trefoil group of cables)

Rating Factors for other Ambient Air Temperature


o
Ambient air temperature C 25 30 35 40 45
Rating factor 1.06 1.0 0.94 0.87 0.79

A7
PVC-INSULATED POWER CABLE
LAID DIRECT IN GROUND
Current Ratings for PVC Insulated, PVC-Sheathed, Unarmoured Cables
600/1000V MS 274/BS 6346
Single core
Two core Three and four core
Nominal Three cables spaced # Three cables trefoil touching
area of
Approx. Approx. Approx. Approx.
conductor Current Current Current Current
volt drop per volt drop per volt drop per volt drop per
rating rating rating rating
amp per metre amp per metre amp per metre amp per metre
mm2 amp mV amp mV amp mV amp mV
1.5
2.5
4
6
10 79 4.30 67 3.80
16 104 2.80 88 2.40
25 135 1.70 117 1.50
35 165 1.30 140 1.10
50 190 0.83 180 0.82 195 0.94 165 0.82
70 235 0.60 220 0.58 245 0.66 200 0.57
95 280 0.47 265 0.43 285 0.49 245 0.42
120 320 0.40 300 0.35 330 0.40 280 0.35
150 355 0.35 340 0.30 370 0.34 310 0.29
185 405 0.33 380 0.25 420 0.29 350 0.25
240 470 0.32 440 0.22 485 0.24 410 0.21
300 530 0.31 495 0.19 550 0.21 460 0.18
400 610 0.28 565 0.18 620 0.19 520 0.17
500 680 0.27 630 0.16
630 780 0.25 700 0.15
800 880 0.23 770 0.15
1000 980 0.22 850 0.14
# Adjacent cable surfaces separated by one cable diameter

Current Ratings for PVC Insulated, PVC-Sheathed, Armoured Cables


600/1000V MS 274/BS 6346
Single core
Two core Three and four core
Nominal Three cables spaced # Three cables: trefoil touching
area of
Approx. Approx. Approx. Approx.
conductor Current Current Current Current
volt drop per volt drop per volt drop per volt drop per
rating rating rating rating
amp per metre amp per metre amp per metre amp per metre
mm2 amp mV amp mV amp mV amp mV
1.5 27 29 23 25
2.5 36 18 31 16
4 47 12 41 9.60
6 59 7.40 51 6.30
10 79 4.30 67 3.80
16 104 2.80 88 2.40
25 135 1.70 117 1.50
35 165 1.30 140 1.10
50 190 0.87 180 0.82 195 0.94 165 0.82
70 230 0.65 230 0.58 245 0.66 200 0.57
95 270 0.52 265 0.44 285 0.49 245 0.42
120 300 0.45 300 0.36 330 0.40 280 0.35
150 335 0.41 335 0.31 370 0.34 310 0.29
185 370 0.38 375 0.27 420 0.29 350 0.25
240 415 0.35 430 0.23 485 0.24 410 0.21
300 450 0.33 475 0.20 540 0.21 460 0.18
400 480 0.32 530 0.19 600 0.19 515 0.17
500 515 0.31 575 0.18
630 550 0.31 640 0.16
800 565 0.30 670 0.16
1000 595 0.29 700 0.15
# Adjacent cable surfaces separated by one cable diameter
Basic Assumptions
o o
Ground temperature : 25 C Ground thermal resistivity : 1.2 C m/W
o o
Ambient air temperature : 30 C Maximum conductor temperature : 70 C
Depth of laying : 0.5 metre ( to the centre of cable or trefoil group of cables)

Rating Factors for other Ground Temperature


o
Ambient air temperature C 15 20 25 30 35
Rating factor 1.10 1.05 1.0 0.95 0.90

A8
PVC-INSULATED POWER CABLE
ALLOWABLE SHORT CIRCUIT CURRENTS FOR PVC INSULATED CABLE

16 25 35 50 70 95 120 150185 240 300 400 500 630 800 1000

100
90
80
70
60
50

40

30

20

0.5 SEC.

1 SEC. 10

9.0
8.0
2 SEC.
7.0
3 SEC. 6.0
4 SEC.
5.0
5 SEC.
SHORT CIRCUIT CURRENT (kA)

4.0

3.0

2.0

1.0

CONDUCTOR SIZE (mm 2)


CONDUCTOR : COPPER
INSULATION : POLYVINYL CHLORIDE
Curves based on formula -

0.1154A
l =
t

l = Short circuit current (kA)


A = Conductor area (mm2)
t = Time of short circuit (seconds)

A9
PVC-INSULATED
CABLE
SAMA KEBEL SDN BHD

SHEATHED & NON


SHEATHED &
LIGHTING CABLE
PVC-INSULATED CABLE
450/750V, PVC Insulated, Non-Sheathed General Purpose Cables

Application
Single core, non-sheathed general purpose cables are installed in surface mounted or
embedded conduits or similar closed systems. The cables are suitable for use in
channels with cover, fixed protected installation in or on lighting fittings and inside
appliances, up to 1000V ac or up to 750 V to earth, dc.

Construction : Technical Data :


Conductor : Single solid wire or circular stranded plain Voltage : 450/750V
annealed copper wire acc. to MS 69/BS 6360 Temperature : Maximum 70oC
Insulation : PVC (polyvinyl chloride) compound type TI1 Reference : MS 136 / BS 6004
acc. to MS 138/BS 7655 Testing Voltage : 2500V
2
Colour : Assorted colours : conductor area < 25mm ; Min. Bending Radius : 8 X Overall Diameter
2
Black : conductor area > 35mm

Nominal Number Electrical Characteristics


Thickness Approx Approx
cross-sectional and
of overall net Cond. Resistance Insulation Resistance
area of diameter
conductor of wires
insulation diameter weight Max. at 20oC Min. at 70oC
mm2 no/mm mm mm kg/km /km M /km
1.5 1/1.38 0.7 2.9 22 12.1 0.011
1.5 7/0.53 0.7 3.1 22 12.1 0.010
2.5 1/1.78 0.8 3.5 34 7.41 0.010
2.5 7/0.67 0.8 3.7 35 7.41 0.009
4 7/0.85 0.8 4.3 51 4.61 0.0077
6 7/1.04 0.8 4.9 72 3.08 0.0065
10 7/1.35 1.0 6.2 120 1.83 0.0065
16 7/1.70 1.0 7.2 180 1.15 0.0050
25 7/2.14 1.2 9.0 284 0.727 0.0050
35 19/1.53 1.2 10.2 380 0.524 0.0040
50 19/1.78 1.4 11.9 510 0.387 0.0045
70 19/2.14 1.4 13.7 720 0.268 0.0035
95 19/2.52 1.6 16.0 995 0.193 0.0035
120 37/2.03 1.6 17.7 1235 0.153 0.0032
150 37/2.25 1.8 19.6 1520 0.124 0.0032
185 37/2.52 2.0 22.0 1900 0.0991 0.0032
240 61/2.25 2.2 25.0 2500 0.0754 0.0032
300 61/2.52 2.4 27.8 3130 0.0601 0.0030
400 61/2.85 2.6 31.2 3980 0.0470 0.0028
500 61/3.20 2.8 34.8 5000 0.0366 0.0028
630 127/2.52 2.8 38.8 6350 0.0283 0.0028

B1
PVC-INSULATED CABLE
300/500V, PVC Insulated, Non-Sheathed Internal Wiring Cables

Application
Single core, non-sheathed internal wiring cables are for fixed protected installation,
inside appliances and in or on lighting fittings. The cables are suitable for installation
in surface mounted or embedded conduits. The cables are used only for signaling or
control circuits.

Construction : Technical Data :


Conductor : Single solid plain annealed copper wire acc. Voltage : 300/500V
to MS 69/BS 6360 Temperature : Maximum 70oC
Insulation : PVC (polyvinyl chloride) compound type TI1 Reference : MS 136 / BS 6004
acc. to MS 138/BS 7655 Testing Voltage : 2000V
Colour : Assorted colours Min. Bending Radius : 8 X Overall Diameter

Nominal Electrical Characteristics


Number
cross- Thickness Approx Approx
and Cond. Insulation
sectional of overall net
diameter Resistance Resistance Min.
area of insulation diameter weight
conductor
of wires Max. at 20oC at 70oC

mm2 no/mm mm mm kg/km /km M /km


0.5 1/0.80 0.6 2.1 9.4 36.0 0.015
0.75 1/0.98 0.6 2.3 12 24.5 0.012
1.0 1/1.13 0.6 2.5 15 18.1 0.011

B2
PVC-INSULATED CABLE
300/500V, PVC Insulated, PVC Sheathed Cables

Application
PVC insulated, PVC sheathed cables are for fixed installation in walls, on boards and in
channels, or embedded in plaster. The cables are not suitable for outdoor use or
embedding in concrete.

Construction : Technical Data :


Conductor : Single solid wire or circular stranded plain Voltage : 300/500V
annealed copper wire acc. to MS 69/BS 6360 Temperature : Maximum 70oC
Insulation : PVC (polyvinyl chloride) compound type TI1 Reference : MS 136 / BS 6004
acc. to MS 138/BS 7655 Testing Voltage : 2000V
Identification Single core - Red or Black Min. Bending Radius : 8 X Overall Diameter
of cores : Two core – Red and Black
Three core – Red, Yellow, Blue
Four core – Red, Yellow, Blue, Black
Five core and above – (number) 1, 2, 3, 4,
5……, and the number shall be blue or black
printed on White cores
Laying Up : Cores stranded together. Where necessary,
binder tapes and non-hygroscopic fillers may
be applied
Sheath : PVC (polyvinyl chloride) compound type
TM1/T6 (for two cores and above) or T6 (for
single core) acc. to MS 138/BS 7655
Colour : Black
(Termite protection sheathing upon request)
(Rodent protection sheathing upon request)
(UV protection sheathing upon request)
(Flame Retardant sheathing upon request)

B3
PVC-INSULATED CABLE
300/500V, PVC Insulated, PVC Sheathed Cables

Nominal Electrical Characteristics


Number Thickness Thickness Approx Approx
No. of cross-sectional Cond. Insulation
and diameter of of overall net
cores area of Resistance Resistance Min.
of wires insulation oversheath diameter weight
conductor Max. at 20oC at 70oC
no mm2 no/mm mm Mm mm kg/km /km M /km
1.0 1/1.13 0.6 0.8 4.2 27 18.1 0.011
1.5 1/1.38 0.7 0.8 4.6 36 12.1 0.011
1.5 7/0.53 0.7 0.8 4.9 40 12.1 0.010
2.5 1/1.78 0.8 0.8 5.4 55 7.41 0.010
2.5 7/0.67 0.8 0.8 5.5 55 7.41 0.009
1 4 7/0.85 0.8 0.9 6.3 77 4.61 0.008
6 7/1.04 0.8 0.9 6.8 100 3.08 0.0065
10 7/1.35 1.0 0.9 8.2 155 1.83 0.0065
16 7/1.70 1.0 1.0 9.4 225 1.15 0.0052
25 7/2.14 1.2 1.1 11.4 340 0.727 0.005
35 19/1.53 1.2 1.1 12.6 440 0.387 0.005
1.5 1/1.38 0.7 1.2 8.5 100 12.1 0.011
1.5 7/0.53 0.7 1.2 8.8 100 12.1 0.010
2.5 1/1.78 0.8 1.2 10.0 140 7.41 0.010
2.5 7/0.67 0.8 1.2 10.1 140 7.41 0.009
4 7/0.85 0.8 1.2 11.2 200 4.61 0.008
2
6 7/1.04 0.8 1.2 12.3 260 3.08 0.0065
10 7/1.35 1.0 1.4 15.3 410 1.83 0.0065
16 7/1.70 1.0 1.4 18.6 590 1.15 0.0052
25 7/2.14 1.2 1.4 22.5 880 0.727 0.005
35 19/1.53 1.2 1.6 26.0 1170 0.387 0.005
1.5 1/1.38 0.7 1.2 8.9 120 12.1 0.011
1.5 7/0.53 0.7 1.2 9.3 170 12.1 0.010
2.5 1/1.78 0.8 1.2 10.6 180 7.41 0.010
2.5 7/0.67 0.8 1.2 10.7 180 7.41 0.009
4 7/0.85 0.8 1.2 11.8 245 4.61 0.008
3
6 7/1.04 0.8 1.4 13.5 320 3.08 0.0065
10 7/1.35 1.0 1.4 16.3 520 1.83 0.0065
16 7/1.70 1.0 1.4 20.2 850 1.15 0.0052
25 7/2.14 1.2 1.6 24.3 1275 0.727 0.005
35 19/1.53 1.2 1.6 27.3 1670 0.387 0.005
1.5 1/1.38 0.7 1.2 9.7 150 12.1 0.011
1.5 7/0.53 0.7 1.2 10.1 160 12.1 0.010
2.5 1/1.78 0.8 1.2 11.6 220 7.41 0.010
2.5 7/0.67 0.8 1.2 11.7 220 7.41 0.009
4 7/0.85 0.8 1.4 13.3 320 4.61 0.008
4
6 7/1.04 0.8 1.4 14.7 430 3.08 0.0065
10 7/1.35 1.0 1.4 18.0 660 1.83 0.0065
16 7/1.70 1.0 1.4 22.0 1060 1.15 0.0052
25 7/2.14 1.2 1.6 27.0 1630 0.727 0.005
35 19/1.53 1.2 1.6 30.0 2140 0.387 0.005

B4
PVC-INSULATED CABLE
300/500V, PVC Insulated, PVC Sheathed Cables

Nominal Electrical Characteristics


Number Thickness Thickness Approx Approx
No. of cross-sectional Cond. Insulation
and diameter of of overall net
cores area of Resistance Resistance Min.
of wires insulation oversheath diameter weight
conductor Max. at 20oC at 70oC
no mm2 no/mm mm mm mm kg/km /km M /km
1.5 1/1.38 0.7 1.2 10.2 180 12.1 0.011
1.5 7/0.53 0.7 1.2 11.0 200 12.1 0.010
2.5 1/1.78 0.8 1.2 12.7 260 7.41 0.010
2.5 7/0.67 0.8 1.2 12.8 260 7.41 0.009
4 7/0.85 0.8 1.4 14.6 390 4.61 0.008
5
6 7/1.04 0.8 1.4 16.0 520 3.08 0.0065
10 7/1.35 1.0 1.4 19.7 810 1.83 0.0065
16 7/1.70 1.0 1.6 23.0 1220 1.15 0.0052
25 7/2.14 1.2 1.6 27.5 1810 0.727 0.005
35 19/1.53 1.2 1.6 31.0 2370 0.524 0.005
7 1.2 11.9 250
10 1.3 15.2 360
12 1.3 15.7 405
19 1.5 7/0.53 0.7 1.4 18.5 600 12.1 0.010
27 1.5 22.3 830
37 1.6 25.1 1095
48 1.6 28.5 1380
7 1.3 14.0 365
10 1.4 18.0 520
12 1.4 18.5 590
19 2.5 7/0.67 0.8 1.5 21.8 875 7.41 0.009
27 1.6 26.3 1215
37 1.7 29.6 1610
48 1.8 34.2 2070
7 1.4 15.8 510
10 1.5 20.2 725
12 4 7/0.85 0.8 1.5 21.0 830 4.61 0.008
19 1.6 24.7 1240
27 1.7 30.0 1725

B5
PVC-INSULATED CABLE
300/500V, PVC Insulated, PVC Sheathed Cables, Flat Twin & 3-Core without Earth Continuity Conductor

Application
Flat twin & 3-Core, PVC insulated, PVC sheathed cables without protective conductor
are suitable for fixed installation in walls, on boards and in channels, or embedded in
plaster.
Construction : Technical Data :
Conductor : Single solid wire or circular stranded plain Voltage : 300/500V
annealed copper wire acc. to MS 69/BS 6360 Temperature : Maximum 70oC
Insulation : PVC (polyvinyl chloride) compound type TI1 Reference : MS 136 / BS 6004
acc. to MS 138/BS 7655 Testing Voltage : 2000V
Identification Two core – Red and Black Min. Bending Radius : 8 X Overall Diameter
of cores : Three core – Red, Yellow, Blue
Laying Up : Cores laid parallel
Sheath : PVC (polyvinyl chloride) compound type T6
acc. to MS 138/BS 7655
Colour : Black, Grey or White
(Termite protection sheathing upon request)
(Rodent protection sheathing upon request)
(UV protection sheathing upon request)
(Flame Retardant sheathing upon request)

Overall Diameter Electrical Characteristics


Nominal Number
Thickness Thickness Approx Cond. Insulation
No. of Cross- and
of of Net Resistance Resistance
Cores Sectional Diameter of Lower limit Upper limit
Insulation Sheath Weight Max. at Min. at
Area Wires
20oC 70oC
no mm2 no/mm mm mm mm mm kg/100m /km M /km
1.0 1/1.13 0.6 0.9 4.0 x 6.2 4.7 x 7.4 5.3 18.1 0.011
1.5 1/1.38 0.7 0.9 4.4 x 7.0 5.4 x 8.4 6.5 12.1 0.011
1.5 7/0.53 0.7 0.9 4.5 x 7.2 5.5 x 8.6 6.6 12.1 0.011
2.5 1/1.78 0.8 1.0 5.2 x 8.4 6.2 x 9.8 9.7 7.41 0.010
2 2.5 7/0.67 0.8 1.0 5.4 x 8.9 6.4 x 10.3 10.4 7.41 0.010
4 7/0.85 0.8 1.0 5.6 x 9.6 7.2 x 11.5 14.8 4.61 0.008
6 7/1.04 0.8 1.1 6.4 x 10.3 8.0 x 13.0 20.1 3.08 0.0065
10 7/1.35 1.0 1.2 7.8 x 13.0 9.6 x 16.0 31.8 1.83 0.0065
16 7/1.70 1.0 1.3 9.0 x 15.5 11.0 x 18.5 46.1 1.15 0.0052
1.0 1/1.13 0.6 0.9 4.0 x 8.4 4.7 x 9.8 7.6 18.1 0.011
1.5 1/1.38 0.7 0.9 4.4 x 9.8 5.4 x 11.5 9.5 12.1 0.011
1.5 7/0.53 0.7 0.9 4.5 x 10.2 5.5 x 11.9 9.6 12.1 0.011
2.5 1/1.78 0.8 1.0 5.2 x 11.5 6.2 x 13.5 14.2 7.41 0.010
3 2.5 7/0.67 0.8 1.0 5.4 x 12.2 6.4 x 14.2 15.2 7.41 0.010
4 7/0.85 0.8 1.0 5.6 x 13.5 7.2 x 16.5 22.4 4.61 0.008
6 7/1.04 0.8 1.1 6.4 x 15.0 8.0 x 18.0 29.7 3.08 0.0065
10 7/1.35 1.0 1.2 7.8 x 19.0 9.6 x 22.5 48.6 1.83 0.0065
16 7/1.70 1.0 1.3 9.0 x 22.0 11.0 x 26.5 68.7 1.15 0.0052

B6
PVC-INSULATED CABLE
300/500V, PVC Insulated, PVC Sheathed Cables, Flat Twin & 3-Core with Earth Continuity Conductor

Application
Flat twin & 3-Core, PVC insulated, PVC sheathed cables with protective conductor are
suitable for fixed installation in walls, on boards and in channels, or embedded in
plaster.
Construction : Technical Data :
Conductor : Single solid wire or circular stranded plain Voltage : 300/500V
annealed copper wire acc. to MS 69/BS 6360 Temperature : Maximum 70oC
Insulation : PVC (polyvinyl chloride) compound TI1 acc. to Reference : MS 136 / BS 6004
MS 138/BS 7655 Testing Voltage : 2000V
Identification Two core – Red and Black Min. Bending Radius : 8 X Overall Diameter
Of cores : Three core – Red, Yellow, Blue
Laying Up : Cores laid parallel with earth continuity
conductor in between the two cores at the
same plane
Sheath : PVC (polyvinyl chloride) compound type T6
acc. to MS 138/BS 7655
Colour : Black, Grey or White
(Termite protection sheathing upon request)
(Rodent protection sheathing upon request)
(UV protection sheathing upon request)
(Flame Retardant sheathing upon request)

Number Overall Diameter Electrical Characteristics


Nominal
and EEC Thickness Thickness Approx Cond. Insulation
No. of Cross-
Diameter Sectional of of Net Resistance Resistance
Cores Sectional Lower limit Upper limit
of Area Insulation Sheath Weight Max. at Min. at
Area
Wires 20oC 70oC
no mm2 no/mm mm2 mm mm mm mm kg/100m /km M /km
1.0 1/1.13 1.0 0.6 0.9 4.0 x 7.2 4.7 x 8.6 6.7 18.1 0.011
1.5 1/1.38 1.0 0.7 0.9 4.4 x 8.2 5.4 x 9.6 8.1 12.1 0.011
1.5 7/0.53 1.0 0.7 0.9 4.6 x 8.6 5.6 x 10.0 9.2 12.1 0.011
2.5 1/1.78 1.0 0.8 1.0 5.2 x 9.8 6.2 x 11.5 11.4 7.41 0.010
2 2.5 7/0.67 1.0 0.8 1.0 5.4 x 10.5 6.4 x 12.0 12.6 7.41 0.010
4 7/0.85 1.5 0.8 1.0 5.6 x 10.5 7.2 x 13.0 17.2 4.61 0.008
6 7/1.04 2.5 0.8 1.1 6.4 x 12.5 8.0 x 15.0 23.8 3.08 0.0065
10 7/1.35 4.0 1.0 1.2 7.8 x 15.5 9.6 x 19.0 38.1 1.83 0.0065
16 7/1.70 6.0 1.0 1.3 9.0 x 18.0 11.0 x 22.0 55.2 1.15 0.0052
1.0 1/1.13 1.0 0.6 0.9 4.0 x 9.6 4.7 x 11.0 9.1 18.1 0.011
1.5 1/1.38 1.0 0.7 0.9 4.4 x 10.5 5.4 x 12.5 11.0 12.1 0.011
1.5 7/0.53 1.0 0.7 0.9 4.5 x 11.1 5.6 x 13.1 12.6 12.1 0.011
2.5 1/1.78 1.0 0.8 1.0 5.2 x 12.5 6.2 x 14.5 15.9 7.41 0.010
3 2.5 7/0.67 1.0 0.8 1.0 5.4 x 13.2 6.4 x 15.2 17.3 7.41 0.010
4 7/0.85 1.5 0.8 1.1 5.6 x 14.5 7.4 x 18.0 24.8 4.61 0.008
6 7/1.04 2.5 0.8 1.1 6.4 x 16.5 8.0 x 20.0 33.4 3.08 0.0065
10 7/1.35 4.0 1.0 1.2 7.8 x 21.0 9.6 x 25.5 53.6 1.83 0.0065
16 7/1.70 6.0 1.0 1.3 9.0 x 24.5 11.0 x 29.5 77.8 1.15 0.0052

B7
PVC-INSULATED CABLE
RATING FACTORS
Ratings Factors for Gouprs of More Than One Circuit of Single-Core Cables, or More Than One
Multicore Cable
Rating Factor
Method of Installation Number of Circuits or Multicore Cables
2 3 4 5 6 7 8 9 10 12 14 16 18 20
Enclosed or bunched and clipped
0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.48 0.45 0.43 0.41 0.39 0.38
direct to a non-metallic surface
Touching 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70
Single layer clipped to
a non-metallic surface
Space * 0.94 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90
Single layer multicore
Touching 0.86 0.81 0.77 0.75 0.74 0.73 0.72 0.71 0.70
on a perforated metal
cable tray, vertical or
Space * 0.91 0.89 0.88 0.87 0.87
horizontal
Single layer single- Horizontal 0.90 0.85
core on a perforated
metal cable tray, Vertical 0.85
touching
Single layer multicore touching on
0.86 0.82 0.80 0.79 0.78 0.78 0.78 0.77
ladder supports
* Spaced by a clearance between adjacent surfaces of at least one cable diameter (D e). Where the horizontal clearance between adjacent cables
exceeds 2De no correction factor need be applied.

Ratings Factors for other Ambient Temperature


Rating Factor
o
Type of Protection Ambient Temperature ( C)
25 30 35 40 45 50 55 60
The overcurrent protective device is intended
1.03 1.0 0.94 0.87 0.79 0.71 0.61 0.50
to provide short-circuit protection only *
The overcurrent protective device is a semi-
1.03 1.0 0.97 0.94 0.91 0.87 0.84 0.69
enclosed fuse to BS 3036
* Note : Except where the device is a semi-enclosed fuse to BS 3036, the factor also applies where the device is intended to provide overload protection

Ratings Factors for Cables Installed in Enclosed Trenches


Rating Factor
Trench size 450mm wide x 600mm
Trench size 450mm wide x 300mm deep Trench size 600mm wide x 760mm deep
deep
Conductor 2 single- 4 single- 6 single- 6 single- 8 single- 12 single- 12 single- 18 single- 24 single-
3 single-
Cross- core core core cables, core cables, core core cables, core cables, core cables, core cables,
core
Sectional cables, or cables, or 4 two-core 4 two-core cables, or 8 two-core 8 two-core 8 two-core 12 two-core
cables, or
Area 1 three- 2 three- cables, or 3 cables, or 3 4 three- cables, or 6 cables, or 6 cables, or 6 cables, or
2 two-
or four- or four- three- or three- or or four- three- or three- or three- or 12 three- or
core
core core four-core four-core core four-core four-core four-core four-core
cables
cables cables cables cables cables cables cables cables cables
mm2
4 0.93 0.90 0.87 0.82 0.86 0.83 0.76 0.81 0.74 0.69
6 0.92 0.89 0.86 0.81 0.86 0.82 0.75 0.80 0.73 0.68
10 0.91 0.88 0.85 0.80 0.85 0.80 0.74 0.78 0.72 0.66
16 0.91 0.87 0.84 0.78 0.83 0.78 0.71 0.76 0.70 0.64
25 0.90 0.86 0.82 0.76 0.81 0.76 0.69 0.74 0.67 0.62
35 0.89 0.85 0.81 0.75 0.80 0.74 0.68 0.72 0.66 0.60
50 0.88 0.84 0.79 0.74 0.78 0.73 0.66 0.71 0.64 0.59
70 0.87 0.82 0.78 0.72 0.77 0.72 0.64 0.70 0.62 0.57
95 0.86 0.81 0.76 0.70 0.75 0.70 0.63 0.68 0.60 0.55
120 0.85 0.80 0.75 0.69 0.73 0.68 0.61 0.66 0.58 0.53
150 0.84 0.78 0.74 0.67 0.72 0.67 0.59 0.64 0.57 0.51
185 0.83 0.77 0.73 0.65 0.70 0.65 0.58 0.63 0.55 0.49
240 0.82 0.76 0.71 0.63 0.69 0.63 0.56 0.61 0.53 0.48
300 0.81 0.74 0.69 0.62 0.68 0.62 0.54 0.59 0.52 0.46
400 0.80 0.73 0.67 0.59 0.66 0.60 0.52 0.57 0.50 0.44
500 0.78 0.72 0.66 0.58 0.64 0.58 0.51 0.56 0.48 0.43
630 0.77 0.71 0.65 0.56 0.63 0.57 0.49 0.54 0.47 0.41
*When cables having different conductor operating temperatures are grouped together the current rating shall be based on the lowest operating
temperature of any cable in the group.

B8
PVC-INSULATED CABLE
CURRENT CARRYING CAPACITY

Current-Carrying Capacity for Single-Core PVC-Insulated Cables, Non-Armoured, with or


without Sheath to MS 136/BS 6004
o
Ambient temperature : 30 C
o
Conductor operating temperature : 70 C
Method of Installation
Enclosed in In free Air
conduit in Enclosed in
On a perforated cable tray
thermally conduit on a wall Cliped direct Horizontal Vertical flat
horizontal or vertical Trefoil
insulating wall or in trunking etc. flat spaced spaced
Conductor
etc.
Cross-
2 cables, 3 or 4 3 or 4 2 cables, 2 cables,
Sectional 2 2 2 cables, 3
3 or 4 3 or 4 single- cables, cables, single- single-
Area cables, cables, single- cables,
cables, cables, phase three-phase three-phase phase a.c. phase a.c.
single- single- phase a.c. trefoil
three three a.c. or a.c. or d.c. a.c. or d.c. or d.c. or 3 or d.c. or 3
phase phase or d.c. flat three
phase phase d.c. flat flat and flat and cables cables
a.c. or a.c. or and phase
a.c. a.c. and touching or touching or three- three-phase
d.c. d.c. touching a.c.
touching trefoil trefoil phase a.c. a.c.
mm2 A A A A A A A A A A A
1 11 10.5 13.5 12 15.5 14
1.5 14.5 13.5 17.5 15.5 20 18
2.5 19.5 18 24 21 27 25
4 26 24 32 28 37 33
6 34 31 41 36 47 43
10 46 42 57 50 65 59
16 61 56 76 68 87 79
25 80 73 101 89 114 104 126 112 146 130 110
35 99 89 125 110 141 129 156 141 181 162 137
50 119 108 151 134 182 167 191 172 219 197 167
70 151 136 192 171 234 214 246 223 281 254 216
95 182 164 232 207 284 261 300 273 341 311 264
120 210 188 269 239 330 303 349 318 396 362 308
150 240 216 300 262 381 349 404 369 456 419 356
185 273 245 341 296 436 400 463 424 521 480 409
240 320 286 400 346 515 472 549 504 615 569 485
300 367 328 458 394 594 545 635 584 709 659 561
400 546 467 694 634 732 679 852 795 656
500 626 533 792 723 835 778 982 920 749
630 720 611 904 826 953 892 1138 1070 855

Current-Carrying Capacity for Multicore PVC-Insulated Cables to MS 136/BS 6004


o
Ambient temperature : 30 C
o
Conductor operating temperature : 70 C
Method of Installation
Enclosed in conduit on a
Enclosed in an On a perforated cable
wall or ceiling or in Clipped direct
insulating wall etc. tray or in free air
Conductor trunking
Cross- 1 three- 1 two-
1 two- 1 three- 1 three- 1 two- 1 three-
Sectional core cable core
core core cable 1 two-core core cable core core cable
or 1 four- cable
Area cable
core single-
or 1 four- cable single- or 1 four- cable or 1 four-
single- core phase a.c. core single- core
cable,three- phase a.c.
phase a.c. cable,three- or d.c. cable,three- phase a.c. cable,three-
phase a.c. or d.c.
or d.c. phase a.c. phase a.c. or d.c. phase a.c.

mm2 A A A A A A A A
1 11 10 13 11.5 15 13.5 17 14.5
1.5 14 13 16.5 15 19.5 17.5 22 18.5
2.5 18.5 17.5 23 20 27 24 30 25
4 25 23 30 27 36 32 40 34
6 32 29 38 34 46 41 51 43
10 43 39 52 46 63 57 70 60
16 57 52 69 62 85 76 94 80
25 75 68 90 80 112 96 119 101
35 92 83 111 99 138 119 148 126

B9
PVC-INSULATED CABLECAPACITY
CURRENT CARRYING
VOLTAGE DROP

Voltage Drop for Single-Core PVC-Insulated Cables, Non-Armoured, with or without Sheath
to MS 136/BS 6004
o
Conductor operating temperature : 70 C
Method of Installation
Conductor Cross-

2 cable, single-phase a.c. 3 or 4 cables, three-phase a.c.


Sectional Area

S cables d.c.

Enclosed in Enclosed in
Clipped direct or on
conduit etc. in or Spaced* conduit etc. in or In trefoil Flat spaced*
trays, touching
on a wall on a wall

mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m


1 44 44 44 44 38 38 38
1.5 29 29 29 29 25 25 25
2.5 18 18 18 18 15 15 15
4 11 11 11 11 9.5 9.5 9.5
6 7.3 7.3 7.3 7.3 6.4 6.4 6.4
10 4.4 4.4 4.4 4.4 3.8 3.8 3.8
16 2.8 2.8 2.8 2.8 2.4 2.4 2.4
r x z r x z r x z r x z r x z r x z
25 1.75 1.80 0.33 1.80 1.75 0.200 1.75 1.75 0.29 1.80 1.50 0.29 1.55 1.50 0.175 1.50 1.50 0.32 1.55
35 1.25 1.30 0.31 1.30 1.25 0.195 1.25 1.25 0.28 1.30 1.10 0.27 1.10 1.10 0.170 1.10 1.10 0.32 1.15
50 0.93 0.95 0.30 1.00 0.93 0.190 0.95 0.93 0.28 0.97 0.81 0.26 0.85 0.80 0.65 0.82 0.80 0.32 0.86
70 0.63 0.65 0.29 0.72 0.63 0.185 0.66 0.63 0.27 0.69 0.56 0.25 0.61 0.55 0.160 0.57 0.55 0.31 0.63
95 0.46 0.49 0.28 0.56 0.47 0.180 0.50 0.47 0.27 0.54 0.42 0.24 0.48 0.41 0.155 0.43 0.40 0.31 0.51
120 0.36 0.39 0.27 0.47 0.37 0.175 0.41 0.37 0.26 0.45 0.33 0.23 0.41 0.32 0.150 0.36 0.32 0.30 0.44
150 0.29 0.31 0.27 0.41 0.30 0.175 0.34 0.29 0.26 0.39 0.27 0.23 0.36 0.26 0.150 0.30 0.26 0.30 0.40
185 0.23 0.25 0.27 0.37 0.24 0.170 0.29 0.24 0.26 0.35 0.22 0.23 0.32 0.21 0.45 0.26 0.21 0.30 0.36
240 0.180 0.195 0.26 0.33 0.185 0.165 0.25 0.185 0.25 0.31 0.17 0.23 0.29 0.160 0.145 0.22 0.160 0.29 0.34
300 0.145 0.160 0.26 0.31 0.150 0.165 0.22 0.150 0.25 0.29 0.14 0.23 0.27 0.130 0.140 0.190 0.130 0.29 0.32
400 0.105 0.130 0.26 0.29 0.120 0.160 0.20 0.115 0.25 0.27 0.12 0.22 0.25 0.105 0.140 0.175 0.100 0.29 0.31
500 0.086 0.110 0.26 0.28 0.098 0.155 0.185 0.093 0.24 0.26 0.10 0.22 0.25 0.086 0.135 0.160 0.081 0.29 0.30
630 0.068 0.094 0.25 0.27 0.081 0.155 0.175 0.076 0.24 0.25 0.08 0.22 0.24 0.072 0.135 0.150 0.066 0.28 0.29
Note: *Spacing larger than one cable diameter will result in larger voltage drop.
For cables having conductors greater than 16mm2 the voltage drop is given in three values; the impedance values are given as (mV/A/m)z, together with the resistive component (m/V/A/m)r
and the reactive component (m/V/A/m)x. For more details, please refer to BS 7671 : 1992, Requirements for Electrical Installations, IEE Wiring Regulations, 16th Edition.

Voltage Drop for Multicore PVC-Insulated Cables to MS 136/BS 6004


o
Conductor operating temperature : 70 C

Conductor Cross- Two-core


Two-core cable, single-phase a.c. Three- or four-core cable, three-phase a.c.
Sectional Area cable, d.c.
2
mm mV/A/m mV/A/m mV/A/m
1 44 44 38
1.5 29 29 25
2.5 18 18 15
4 11 11 9.5
6 7.3 7.3 6.4
10 4.4 4.4 3.8
16 2.8 2.8 2.4
r x z r x z
25 1.75 1.75 0.170 1.75 1.50 0.145 1.50
35 1.25 1.25 0.165 1.25 1.10 0.145 1.10
Note: For information of r, x, z refer to footnote of voltage drop for single-core cables.

B 10
PVC-INSULATED
INSTRUMENTATION CABLE

SAMA KEBEL SDN BHD

MULTIPAIR &
MULTICORE
PVC-INSULATED INSTRUMENTATION CABLE
300/500V, Type 1, PVC-Insulated Multicore & Multipair Instrumentation Unarmoured Cables

Application
Instrumentation unarmoured cables are generally used in the petroleum and
petrochemical industries. These cables are generally for indoor control applications
and they are designed for use in intrinsically safe system. The cables are individually
and/or overall shielded for greater isolation and noise reduction. The cables are
suitable for continuous operation at a maximum conductor temperature of 70oC.

Construction : Technical Data :


Conductor : Circular stranded plain annealed copper Voltage : 300/500V
wire acc. to BS 6360 Reference : BS 5308 : Part 2
Insulation : PVC (polyvinyl chloride) compound type TI1 Temperature : Maximum 70oC
acc. to BS 7655 Ambient Temperature : Maximum -20oC
Identification of Two cores – Red and Black Testing Voltage : 1000V
cores: Three core - Red, Yellow, Blue Minimum Insulation Individual conductors-
Four core – Red, Yellow, Blue, Black Resistance : 25 M/km at 20oC
Five core and above – (number) 1, 2, 3, 4, Between individual
5……, and the number shall be blue or black screens -
printed on White cores 1 M/km at 20oC
Identification of Single pair – Black and White Maximum Mutual Adjacent cores –
pairs: Multi pairs – Black and (number) 1, 2, 3, 4, Capacitance : 250 pF/m at 1 kHz
5……, and the number shall be blue or black Maximum Capacitance to 400 pF/m at 1 kHz
printed on White cores Screen :
Pair Screen : Aluminium polyester tape with metallic side Min. Bending Radius : 8 X Overall Diameter
2
(optional) Downward in contact with a 0.5mm tinned
copper drain wire
Laying Up : Cores stranded together. Where necessary,
binder tapes and non hygroscopic fillers may
be applied
Overall Screen : Aluminium polyester tape with metallic side
(optional) Downward in contact with a 0.5mm2 tinned
copper drain wire
Sheath : PVC (polyvinyl chloride) compound type TM1
acc. to BS 7655
Colour : Black or Grey
* Anti-termite sheathing upon request
* FR-PVC (reduced propagation PVC)
to IEC 332-3 sheathing upon request
* LSHF (low smoke halogen free) sheathing
upon request

C1
PVC-INSULATED INSTRUMENTATION CABLE
300/500V, Type 1, PVC-Insulated Multicore & Multipair Instrumentation Unarmoured Cables

Type 1 Multicore, Overall Screened, Unarmoured


Nominal Number Thickness Thickness Approx Approx
No. of Cond. Resistance Maximum L/R
cross-sectional area and diameter of of overall net
cores D. C. at 20oC ratio
of conductor of wires insulation oversheath diameter weight
no mm2 no/mm mm mm mm kg/km /km MH/
2 0.8 7.0 60
3 0.8 7.3 75
4 0.8 7.9 80
6 0.9 9.3 110
0.5 16/0.2 39.0 25
10 1.0 11.9 180
20 1.2 14.9 310
40 1.3 20.1 570
80 1.5 26.3 1080
2 0.8 7.3 75
3 0.8 7.7 90
4 0.8 8.3 100
6 0.9 9.9 140
0.75 24/0.2 0.6 26.0 25
10 1.1 12.7 220
20 1.2 16.0 390
40 1.3 21.7 710
80 1.5 28.5 1350
2 0.8 8.3 105
3 0.9 8.9 135
4 0.9 9.7 150
6 1.1 11.7 205
1.5 7/0.53 12.1 40
10 1.2 14.7 330
20 1.3 18.7 580
40 1.5 24.6 1065
80 1.7 33.6 2025

C2
PVC-INSULATED INSTRUMENTATION CABLE
300/500V, Type 1, PVC-Insulated Multicore & Multipair Instrumentation Unarmoured Cables

Type 1 Multipair, Overall Screened, Unarmoured


Nominal Number Thickness Thickness Approx Approx
No. of Cond. Resistance D. Maximum L/R
cross-sectional area and diameter of of overall net
pairs C. at 20oC ratio
of conductor of wires insulation oversheath diameter weight
no mm2 no/mm mm mm mm kg/km /km /km
1 0.8 7.0 60
2 0.8 7.9 80
5 1.1 12.1 200
10 1.2 17.2 340
0.5 16/0.2 39.7 25
15 1.3 19.8 480
20 1.3 22.3 570
30 1.5 26.9 880
50 1.7 33.9 1310
1 0.8 7.3 75
2 0.8 8.3 100
5 1.2 14.3 250
10 1.3 18.7 450
0.75 24/0.2 0.6 26.5 25
15 1.3 21.4 600
20 1.5 24.5 800
30 1.7 29.5 1080
50 2.0 37.4 1860
1 0.8 8.3 100
2 0.9 9.7 150
5 1.2 16.4 360
10 1.3 21.6 670
1.5 7/0.53 12.3 40
15 1.5 25.2 970
20 1.5 28.5 1230
30 1.7 34.3 1730
50 2.0 43.6 2740
Type 1 Multipair, Individually Pair and Overall Screened, Unarmoured
2 1.1 12.0 170
5 1.2 15.2 270
10 1.3 21.1 520
15 0.5 16/0.2 1.5 24.5 650 39.7 25
20 1.5 27.3 860
30 1.7 32.3 1130
50 2.2 41.7 1880
2 1.1 12.8 200
5 1.2 16.3 355
10 1.3 22.7 560
15 0.75 24/0.2 0.6 1.5 26.4 770 26.5 25
20 1.7 29.8 990
30 2.0 35.5 1380
50 2.2 45.0 2225
2 1.2 14.7 265
5 1.3 18.8 490
10 1.5 26.5 820
15 1.5 7/0.53 1.7 30.8 1110 12.3 40
20 1.7 34.4 1470
30 2.0 41.0 2070
50 2.2 52.2 3340

C3
PVC-INSULATED INSTRUMENTATION CABLE
300/500V, Type 2, PVC-Insulated Multicore & Multipair Instrumentation Armoured Cables

Application
Instrumentation armoured cables are generally used in the petroleum and petrochemical industries. These
cables are suitable for burial underground and they are designed for use in intrinsically safe system. The
cables are individually and/or overall shielded for greater isolation and noise reduction. The cables are
suitable for continuous operation at a maximum conductor temperature of 70 oC.
Construction : Technical Data :
Conductor : Circular stranded plain annealed copper Voltage : 300/500V
wire acc. to BS 6360 Reference : BS 5308 : Part 2
Insulation : PVC (polyvinyl chloride) compound type TI1 Temperature : Maximum 70oC
acc. to BS 7655 Ambient Temperature : Maximum -20oC
Identification of Two core – Red and Black Testing Voltage : 1000V
cores: Three core - Red, Yellow, Blue Minimum Insulation Individual conductors-
Four core – Red, Yellow, Blue, Black Resistance : 25 M/km at 20oC
Five core and above – (number) 1, 2, 3, 4, Between individual
5……, and the number shall be blue or black screens -
printed on White cores 1 M/km at 20oC
Identification of Single pair – Black and White Maximum Mutual Adjacent cores –
pairs: Multi pairs – Black and (number) 1, 2, 3, 4, Capacitance : 250 pF/m at 1 kHz
5……, and the number shall be blue or black Maximum Capacitance to 400 pF/m at 1 kHz
printed on White cores Screen :
Pair Screen : Aluminium polyester tape with metallic side Min. Bending Radius : 8 X Overall Diameter
2
(optional) downward in contact with a 0.5mm tinned
copper drain wire
Laying Up : Cores stranded together. Where necessary,
binder tapes and non hygroscopic fillers may
be applied
Overall Screen : Aluminium polyester tape with metallic side
(optional) downward in contact with a 0.5mm2 tinned
copper drain wire
Bedding : Extruded PVC compound
Colour : Black
Armour : Consist of a single layer of galvanized steel
wires
Sheath : PVC (polyvinyl chloride) compound type TM1
acc. to BS 7655
Colour : Black or Grey
* Anti-termite sheathing upon request
* FR-PVC (reduced propagation PVC)
to IEC 332-3 sheathing upon request
* LSHF (low smoke halogen free) sheathing
upon request

C4
PVC-INSULATED INSTRUMENTATION CABLE
300/500V, Type 2, PVC-Insulated Multicore & Multipair Instrumentation Armoured Cables

Type 2 Multicore, Overall Screened, Armoured


Cond.
Nominal Number Nominal
Thickness Thickness Thickness Approx Approx Resistanc
No. of cross-sectional and armour Maximum
of of of overall net e
cores area of diameter wire L/R ratio
insulation bedding oversheath diameter weight D. C. at
conductor of wires diameter
20oC
no mm2 no/mm mm mm Mm mm mm kg/km /km MH/
2 0.8 0.9 1.3 11.4 255
3 0.8 0.9 1.3 11.7 280
4 0.8 0.9 1.3 12.3 305
6 0.9 0.9 1.4 13.9 360
0.5 16/0.2 39.0 25
10 1.0 0.9 1.5 16.7 510
20 1.2 1.25 1.6 20.6 860
40 1.3 1.6 1.7 26.7 1440
80 1.5 1.6 1.9 33.3 2200
2 0.8 0.9 1.3 11.7 280
3 0.8 0.9 1.3 12.1 305
4 0.8 0.9 1.4 12.9 335
6 0.9 0.9 1.4 14.5 400
0.75 24/0.2 0.6 26.0 25
10 1.1 0.9 1.5 17.5 565
20 1.2 1.25 1.6 21.7 950
40 1.3 1.6 1.8 28.5 1590
80 1.5 1.6 2.0 35.7 2450
2 0.8 0.9 1.4 12.9 330
3 0.9 0.9 1.4 13.5 380
4 0.9 0.9 1.4 14.3 420
6 1.1 0.9 1.4 16.3 540
1.5 7/0.53 12.1 40
10 1.2 1.25 1.6 20.4 750
20 1.3 1.6 1.7 25.3 1260
40 1.5 1.6 1.9 31.6 2140
80 1.7 2.0 2.1 41.8 3300

C5
PVC-INSULATED INSTRUMENTATION CABLE
300/500V, Type 2, PVC-Insulated Multicore & Multipair Instrumentation Armoured Cables

Type 2 Multipair, Overall Screened, Armoured


Nominal Number Nominal Cond.
Thickness Thickness Thickness Approx Approx
No. of cross-sectional and armour Resistanc Maximum
of of of overall net
pairs area of diameter wire e D. C. at L/R ratio
insulation Bedding oversheath diameter weight
conductor of wires diameter 20oC
no mm2 no/mm mm mm mm mm mm kg/km /km /km
1 0.8 0.9 1.3 11.4 255
2 0.8 0.9 1.3 12.3 305
5 1.1 0.9 1.5 17.9 610
10 1.2 1.25 1.6 22.9 1060
0.5 16/0.2 39.7 25
15 1.3 1.6 1.7 26.4 1330
20 1.3 1.6 1.8 29.1 1800
30 1.5 1.6 1.9 33.9 1980
50 1.7 2.0 2.1 42.1 3070
1 0.8 0.9 1.3 11.7 305
2 0.8 0.9 1.4 12.9 360
5 1.2 1.25 1.5 19.8 820
10 1.3 1.6 1.7 25.3 1250
0.75 24/0.2 0.6 26.5 25
15 1.3 1.6 1.8 28.2 1600
20 1.5 1.6 1.8 31.3 1800
30 1.7 2.0 2.0 37.5 2570
50 2.0 2.5 2.3 45.8 3800
1 0.8 0.9 1.4 12.9 360
2 0.9 0.9 1.4 14.3 460
5 1.2 1.25 1.6 22.1 1040
10 1.3 1.6 1.8 28.4 1610
1.5 7/0.53 12.3 40
15 1.5 1.6 1.9 32.2 2060
20 1.5 1.6 2.0 35.7 2630
30 1.7 2.0 2.1 42.5 3460
50 2.0 2.5 2.4 53.4 5520
Type 2 Multipair, Individually Pair and Overall Screened, Armoured
2 1.1 0.9 1.5 16.8 505
5 1.2 1.25 1.6 20.9 830
10 1.3 1.6 1.8 27.9 1420
15 0.5 16/0.2 1.5 1.6 1.8 31.3 1570 39.7 25
20 1.5 1.6 1.9 34.3 2040
30 1.7 2.0 2.1 40.5 2610
50 2.2 2.5 2.4 51.5 4270
2 1.1 0.9 1.5 17.6 545
5 1.2 1.25 1.6 22.0 1005
10 1.3 1.6 1.8 29.5 1400
15 0.75 24/0.2 0.6 1.5 1.6 1.9 33.4 1750 26.5 25
20 1.7 2.0 2.0 37.8 2300
30 2.0 2.0 2.2 43.9 2460
50 2.2 2.5 2.5 55.0 4800
2 1.2 1.25 1.6 20.4 800
5 1.3 1.6 1.7 25.4 1290
10 1.5 1.6 1.9 33.5 1990
15 1.5 7/0.53 1.7 2.0 2.0 38.8 2590 12.3 40
20 1.7 2.0 2.1 42.6 3310
30 2.0 2.5 2.4 50.8 4380
50 2.2 2.5 2.7 62.6 6260

C6
FLEXIBLE CORDS

SAMA KEBEL SDN BHD


PVC-INSULATED FLEXIBLE CORDS
300/300V PVC-Insulated, Non Sheathed Cord

Application
PVC insulated, non sheathed flexible cords are for installation in domestic areas,
kitchens and offices. The cables are also for usage in household equipments, eg.
washing machines, hair dryers, refrigerators, cookers and heaters. The cables are able
to withstand medium mechanical stress and frequent twisting and bending. The cables
are not suitable for permanent external installation nor for use directly or indirectly
underground.

Construction : Technical Data :


Conductor : Circular stranded plain annealed copper Voltage : 300/300V
wire acc. to MS 69/BS 6360 Class 5 Temperature : Maximum 70oC
Insulation : PVC (polyvinyl chloride) compound type TI1 Reference : MS 140 / BS 6500
acc. to MS 138/BS 7655 Testing Voltage : 2000V
Colour : Assorted colours Min. Bending Radius : 6 X Overall Diameter
Laying Up : Cores twisted together

Nominal Electrical Characteristics


Number Thickness Approx Approx
No. of cross-sectional
and diameter of overall net Cond. Resistance Insulation Resistance
cores area of
conductor
of wires insulation diameter weight Max. at 20oC Min at 70oC
no mm2 no/mm mm mm kg/km /km M/km

0.5 16/0.20 0.60 2.3 10 39.0 0.013

1 0.75 24/0.20 0.60 2.5 13 26.0 0.011

1.00 32/0.20 0.60 3.0 16 19.5 0.010

0.5 16/0.20 0.60 2.3 x 4.6 20 39.0 0.013

2 0.75 24/0.20 0.60 2.5 x 5.0 26 26.0 0.011

1.00 32/0.20 0.60 3.0 x 6.0 32 19.5 0.010

F1
PVC-INSULATED FLEXIBLE CORDS
PVC-Insulated, PVC Sheathed Flexible Cord

Application
PVC insulated, PVC sheathed flexible cords are suitable for indoor small electrical
appliances and instruments. The cables are capable of withstanding medium
mechanical stress and frequent twisting and bending. The cables are not suitable for
permanent external installation nor for use directly or indirectly underground.

Construction : Technical Data :


Conductor : Circular stranded plain annealed copper wire acc. Temperature : Maximum 70oC
to MS 69/BS 6360 Class 5 Reference : MS 140 / BS 6500
Insulation : PVC (polyvinyl chloride) compound type TI2 acc. to Testing Voltage : 2000V
MS 138/BS 7655; Colour – Twin: Blue and Brown; Min. Bending Radius : 6 X Overall Diameter
Identification Twin-Core: Blue and Brown
of cores : 3-Core: Green/Yellow, Blue and Brown
4-Core:Green/Yellow, Black, Blue and Brown
Laying Up : Twin-Core: Cores laid parallel
3-Core and above: stranded together. Where
necessary, fillers may be applied.
Sheath : PVC compound type TM2 acc. to MS 138/BS 7655;
Colour : Black or Grey

Electrical Characteristics
Nominal Number
Thickness Thickness Approx Approx Cond. Insulation
Rated cross-sectional and
Type of of overall net Resistance Resistance
voltage area of diameter
insulation oversheath diameter weight Max. at Min. at
conductor of wires
20oC 70oC
V mm2 no/mm mm mm mm kg/km /km M /km
Parallel Twin 0.50 16/0.20 0.5 0.6 3.3 x 5.2 33 39 0.012
Sheathed 0.75 24/0.20 0.5 0.6 3.6 x 5.6 40 26 0.010
2-Core Circular 0.50 16/0.20 0.5 0.6 5.2 40 39 0.012
Sheathed 0.75 24/0.20 0.5 0.6 5.6 50 26 0.010
300/300
3-Core Circular 0.50 16/0.20 0.5 0.6 5.5 50 39 0.012
Sheathed 0.75 24/0.20 0.5 0.6 6.0 60 26 0.010
4-Core Circular 0.50 16/0.20 0.5 0.6 6.0 60 39 0.012
Sheathed 0.75 24/0.20 0.5 0.6 6.5 75 26 0.010
Parallel Twin
0.75 24/0.20 0.6 0.8 4.0 x 6.4 45 26 0.011
Sheathed
0.50 16/0.20 0.6 0.8 6.1 55 39 0.013
0.75 24/0.20 0.6 0.8 6.5 65 26 0.011
2-Core Circular 1.00 32/0.20 0.6 0.8 6.9 75 19.5 0.010
Sheathed 1.25 40/0.20 0.7 0.8 7.4 85 15.6 0.010
1.50 30/0.25 0.7 0.8 7.5 90 13.3 0.010
2.50 50/0.25 0.8 1.0 9.4 140 7.98 0.009
300/500 0.75 24/0.20 0.6 0.8 6.9 75 26 0.011
1.00 32/0.20 0.6 0.8 7.3 85 19.5 0.010
3-Core Circular
1.25 40/0.20 0.7 0.9 8.0 110 15.6 0.010
Sheathed
1.50 30/0.25 0.7 0.9 8.5 115 13.3 0.010
2.50 50/0.25 0.8 1.1 10.2 180 7.98 0.009
0.75 24/0.20 0.6 0.8 7.5 90 26 0.011
4-Core Circular 1.00 32/0.20 0.6 0.9 8.2 110 19.5 0.010
Sheathed 1.50 30/0.25 0.7 1.0 9.3 150 15.6 0.010
2.50 50/0.25 0.8 1.1 11.0 216 7.98 0.009

F2
PVC-INSULATED FLEXIBLE CORDS
450/750V, Single Core PVC-Insulated Flexible Cord

Application
Single core PVC insulated flexible cords are suitable for installation in trays, trunking,
lighting units or inside switching and control equipments. The cables are suitably used
for voltages up to 1000V A.C.

Construction : Technical Data :


Conductor : Circular stranded plain annealed copper Voltage : 450/750V
wire acc. to MS 69/BS 6360 Class 5 Temperature : Maximum 70oC
Insulation : PVC (polyvinyl chloride) compound type TI1 Reference : MS 136 / BS 6004
acc. to MS 138/BS 7655 Testing Voltage : 2500V
Colour : Assorted colours Min. Bending Radius : 6 X Overall Diameter

Nominal Electrical Characteristics


Number Thickness Approx Approx
cross-sectional
and diameter of overall net Cond. Resistance Insulation Resistance
area of
conductor
of wires insulation diameter weight Max. at 20oC Min. at 70oC
mm2 no/mm mm mm kg/km /km M /km
1.5 30/0.25 0.7 3.5 23 13.3 0.010
2.5 50/0.25 0.8 4.2 35 7.98 0.009
4 56/0.30 0.8 4.8 50 4.95 0.007
6 84/0.30 0.8 6.3 70 3.30 0.006
10 80/0.40 1.0 7.6 125 1.91 0.0056
16 126/0.40 1.0 8.8 195 1.21 0.0046
25 196/0.40 1.2 11.0 300 0.780 0.0044
35 276/0.40 1.2 12.5 410 0.554 0.0038
50 396/0.40 1.4 14.5 585 0.386 0.0037
70 360/0.50 1.4 17.0 810 0.272 0.0032
95 475/0.50 1.6 19.0 1065 0.206 0.0032
120 608/0.50 1.6 21.0 1335 0.161 0.0029
150 756/0.50 1.8 23.5 1600 0.129 0.0029
185 925/0.50 2.0 26.0 2000 0.106 0.0029
240 1221/0.50 2.2 29.5 2500 0.081 0.0028

F3
SWITCHGEAR AND CONTROL PANEL WIRES
600/1000V, Single Core, PVC Flexible Cables

Application
Single core, PVC flexible wires are suitable for the wiring of switch, control, metering,
relay and instrument panels of power switchgear, and for such purposes as internal
connections in rectifier equipment and in motor starters and controllers

Construction : Technical Data :


Conductor : Flexible stranded plain annealed copper Voltage : 600/1000V
wire acc. to BS 6360 Class 5 Temperature : Maximum 90oC
Insulation : PVC (polyvinyl chloride) heat resistant acc. Reference : BS 6231
to BS 7655 Testing Voltage : 3500V
2
Colour : Assorted colours: conductor area < 6mm Min. Bending Radius : 6 X Overall Diameter
Black: conductor area > 10mm2

Nominal Electrical Characteristics


Number Thickness Approx Approx
cross-sectional
and diameter of overall net Cond. Resistance Insulation Resistance
area of
conductor
of wires insulation diameter weight Max. at 20oC Min. at 90oC
mm2 no/mm mm mm kg/km /km M /km
1.0 30/0.20 0.8 3.4 16 19.5 0.013
1.5 30/0.25 0.8 3.7 23 13.3 0.010
2.5 50/0.25 0.8 4.2 35 7.98 0.009
4 56/0.30 0.8 4.8 51 4.95 0.007
6 84/0.30 0.8 6.3 71 3.30 0.006
10 80/0.40 1.0 7.8 131 1.91 0.0056
16 126/0.40 1.0 9.0 199 1.21 0.0046
25 196/0.40 1.2 11.5 305 0.780 0.0044
35 276/0.40 1.2 13.0 404 0.554 0.0038
50 396/0.40 1.4 15.0 576 0.386 0.0037
70 360/0.50 1.4 17.5 765 0.272 0.0032
95 475/0.50 1.6 19.5 1052 0.206 0.0032
120 608/0.50 1.6 21.5 1261 0.161 0.0029
150 756/0.50 1.8 24.0 1567 0.129 0.0029
185 925/0.50 2.0 26.5 1892 0.106 0.0029
240 1221/0.50 2.2 30.0 2538 0.081 0.0028

F4
LOW SMOKE HALOGEN FREE FLEXIBLE WIRE
600/1000V, Single Core, LSHF Flexible Wire

Application
Single core, LSHF flexible wire is suitable for installation in switch cabinets, appliances
and devices for communication technologies, household appliances, construction of
power generation and transformers, machine construction, railway technologies and
particularly suitable for internal wiring of railway vehicles.

Construction : Technical Data :


Conductor : Circular stranded plain annealed copper Voltage : 600/1000V for 1.5sq.mm and above;
wire acc. to IEC 60228 Class5 450/750V for 0.5sq.mm to 1.0sq.mm
Insulation : LSHF (low smoke halogen free) compound Temperature : Maximum 90oC
Colour : Assorted colours Reference : IEC 60502, IEC 60332-1
Testing Voltage : 3500V for 1.5sq.mm and above;
2500V for 0.5sq.mm to 1.0sq.mm
Min. Bending Radius : 6 X Overall Diameter

Nominal Electrical Characteristics


Number Thickness Approx Approx
cross-sectional
and diameter of overall net Cond. Resistance Insulation Resistance
area of
conductor
of wires insulation diameter weight Max. at 20oC Min. at 90oC
mm2 no/mm mm mm kg/km /km M /km
0.5 16/0.20 0.8 2.6 11 39.0 0.013
0.75 24/0.20 0.8 2.8 14 26.0 0.013
1.0 30/0.20 0.8 2.9 16 19.5 0.013
1.5 30/0.25 0.8 3.2 23 13.3 0.010
2.5 50/0.25 0.8 3.6 35 7.98 0.009
4 56/0.30 0.8 4.2 51 4.95 0.007
6 84/0.30 0.8 4.8 71 3.30 0.006
10 80/0.40 1.0 6.1 131 1.91 0.0056
16 126/0.40 1.0 7.2 199 1.21 0.0046
25 196/0.40 1.2 9.7 305 0.780 0.0044
35 276/0.40 1.2 11.1 404 0.554 0.0038
50 396/0.40 1.4 13.6 576 0.386 0.0037
70 360/0.50 1.4 15.4 765 0.272 0.0032
95 475/0.50 1.6 17.6 1052 0.206 0.0032
120 608/0.50 1.6 19.5 1261 0.161 0.0029
150 756/0.50 1.8 21.9 1567 0.129 0.0029
185 925/0.50 2.0 23.5 1892 0.106 0.0029
240 1221/0.50 2.2 27.2 2538 0.081 0.0028

F5
TP SDI FLEXIBLE CABLES
600/1000V, Single Core, TP Insulated, TP Sheathed Flexible Cables

Application
TP insulated, TP sheathed flexible cables are suitable for wiring of switch, control,
metering, relay and instrument panels of power switchgear, transformers, battery leads,
battery chargers, electric forklifts, earth and electrode leads for welding. These cables
have lighter weight than conventional thermoset rubber. Hence, they are easy to move
and carry, and less expensive to ship or truck.

Construction : Technical Data :


Conductor : Circular stranded plain annealed copper Voltage : 600/1000V
wire acc. to BS 6360 Temperature : Maximum 90oC
Insulation : Thermoplastic elastomer alloy Reference : AS/NZS 1995, AS/NZS 5000.1,
Colour : White BS 638
Sheath : Thermoplastic elastomer alloy Testing Voltage : 3500V
Colour : Orange or Black Fire Performance : Flame retardant and self
extinguishing acc. to
AS/NZS 1660.5, IEC 60332-1,
BS 4066 Part 1
Min. Bending Radius : 5 X Overall Diameter (Static)

Nominal Number Approx Approx Cond.


Thickness of Thickness of
cross-sectional area of and diameter overall net Resistance Max.
insulation oversheath
conductor of wires diameter weight at 20oC

mm2 no/mm mm mm mm kg/km /km


6 190/0.2 1.0 1.0 7.8 107.3 3.3
10 318/0.2 1.0 1.0 8.8 153.4 1.91
16 513/0.2 1.0 1.0 10.2 222.4 1.21
25 783/0.2 1.0 1.0 11.7 314.0 0.78
35 1107/0.2 1.0 1.0 13.1 420.0 0.554
50 1566/0.2 1.1 1.1 15.1 580.0 0.386
70 2214/0.2 1.2 1.2 17.5 801.8 0.272
95 2997/0.2 1.3 1.3 19.9 1066.4 0.206
120 950/0.4 1.4 1.4 22.1 1338.0 0.161
150 1184/0.4 1.5 1.5 24.5 1654.2 0.129
185 1445/0.4 1.6 1.6 26.9 2005.2 0.106
240 1908/0.4 1.7 1.7 30.3 2608.0 0.0801
300 2383/0.4 2.4 1.9 34.9 3332.3 0.0641
400 3146/0.4 2.6 2.0 39.4 4336.4 0.0486
500 3980/0.4 2.8 2.1 43.6 5428.5 0.0384
630 4982/0.4 2.8 2.1 47.2 5860.0 0.0287

F6
XLPE-INSULATED
POWER CABLE
SAMA KEBEL SDN BHD

ARMOURED & NON


ARMOURED
XLPE-INSULATED POWER CABLE
600/1000V, Single Core, XLPE Insulated, PVC Sheathed Unarmoured Cables

Application
Power cables for electricity supply are installed in open air, underground, in cable
ducts, outdoor and indoors, power stations, for industry and distribution boards as well
as in subscriber networks where mechanical damages are not to be expected. The
cables are suitable for continuous operation at a maximum conductor temperature of
90oC.

Construction : Technical Data :


Conductor : Circular stranded, circular compact stranded Voltage : 600/1000V
or sector shaped stranded plain annealed Temperature : Maximum 90oC
wire acc. to IEC 60228 class 2 Reference : IEC 60502-1
Insulation : XLPE (cross-linked polyethylene) acc. to Testing Voltage : 3500V
IEC 60502-1 Min. Bending Radius : 8 X Overall Diameter
Identification Single core – Black or Natural
of cores: Two core – Red and Black
Three core – Red, Yellow, Blue
Four core – Red, Yellow, Blue, Black
Laying Up : Cores stranded together. Where necessary,
binder tapes and non-hygroscopic fillers may
be applied
Sheath : PVC (polyvinyl chloride) compound type ST2
acc. to IEC 60502-1
Colour: Black
(Termite protection sheathing upon request)
(Rodent protection sheathing upon request)
(UV protection sheathing upon request)
(Flame Retardant sheathing upon request)

X1
XLPE-INSULATED POWER CABLE
600/1000V, XLPE Insulated, PVC Sheathed Unarmoured Cables

Electrical Characteristics
Nominal
Number Cond. Resistance
cross- Thickness Thickness Approx Approx Short
No. of and
sectional of of overall net Reactance Circuit
cores diameter D. C. at 50 Hz at
area of insulation oversheath diameter weight at 50 Hz Current
of wires 20oC 90oC
conductor for 1 sec.
no mm2 no/mm mm mm mm kg/km /km /km /km kA
16 7/1.70 0.7 1.4 9.7 210 1.15 1.47 2.28
25 7/2.14 0.9 1.4 11.3 310 0.727 0.927 0.0979 3.57
35 19/1.53 0.9 1.4 12.5 415 0.524 0.669 0.0934 5.00
50 19/1.78 1.0 1.4 13.8 540 0.387 0.494 0.0905 7.15
70 19/2.14 1.1 1.4 15.7 750 0.268 0.342 0.087 10.0
95 19/2.52 1.1 1.5 18.0 1025 0.193 0.247 0.0851 13.5
120 37/2.03 1.2 1.5 19.6 1265 0.153 0.196 0.0837 17.1
150 37/2.25 1.4 1.6 22.0 1575 0.124 0.160 0.0837 21.4
1
185 37/2.52 1.6 1.6 24.0 1885 0.0991 0.128 0.0826 26.4
240 61/2.25 1.7 1.7 27.0 2560 0.0754 0.0988 0.0812 34.3
300 61/2.52 1.8 1.8 30.0 3175 0.0601 0.0801 0.0801 42.9
400 61/2.85 2.0 1.9 33.5 4050 0.047 0.0643 0.0792 57.2
500 61/3.20 2.2 2.0 37.5 5090 0.0366 0.0521 0.0785 71.5
630 127/2.52 2.4 2.2 42.2 6550 0.0283 0.0428 0.0776 90.0
800 127/2.85 2.6 2.3 47.0 8290 0.0221 0.0363 0.0759 114.0
1000 127/3.20 2.8 2.4 52.0 10455 0.0176 0.0317 0.0749 143.0
16 7/1.70 0.7 1.8 17.2 515 1.15 1.47 0.0761 2.28
25 7/2.14 0.9 1.8 20.8 680 0.727 0.927 0.0683 3.57
35 19/1.53 0.9 1.8 19.3 850 0.524 0.669 0.0656 5.00
50 19/1.78 1.0 1.8 21.5 1125 0.387 0.494 0.0651 7.15
70 19/2.14 1.1 1.8 24.5 1580 0.268 0.342 0.0637 10.0
95 19/2.52 1.1 1.9 27.4 2125 0.193 0.247 0.0616 13.50
2
120 37/2.03 1.2 2.0 30.4 2665 0.153 0.196 0.0613 17.10
150 37/2.25 1.4 2.2 34.0 3250 0.124 0.160 0.0618 21.40
185 37/2.52 1.6 2.3 37.6 4080 0.0991 0.129 0.0623 26.40
240 61/2.25 1.7 2.5 42.3 5130 0.0754 0.0993 0.0612 34.30
300 61/2.52 1.8 2.6 46.8 6310 0.0601 0.0807 0.0605 42.90
400 61/2.85 2.0 2.9 52.6 8130 0.0470 0.0650 0.0603 57.20
2
Circular or compacted circular stranded conductors (Single core: All; 2 core: Up to and including 25mm )
2
Sector shaped stranded conductors (2 core: 35mm and above)

X2
XLPE-INSULATED POWER CABLE
600/1000V, XLPE Insulated, PVC Sheathed Unarmoured Cables

Nominal Electrical Characteristics


Number
cross- Thickness Thickness Approx Approx
No. of and Short
sectional of of overall net Cond. Resistance
cores diameter Reactance Circuit
area of insulation oversheath diameter weight
of wires D. C. at 50 Hz at at 50 Hz Current
conductor
20oC 90oC for 1 sec.
No
mm2 no/mm mm mm mm kg/km /km /km /km kA

16 7/1.70 0.7 1.8 18.3 640 1.15 1.47 0.0761 2.28

25 7/2.14 0.9 1.8 22.1 920 0.727 0.927 0.0683 3.57

35 19/1.53 0.9 1.8 21.5 1220 0.524 0.669 0.0656 5.00

50 19/1.78 1.0 1.8 24.6 1585 0.387 0.494 0.0651 7.15

70 19/2.14 1.1 1.9 27.9 2250 0.268 0.342 0.0637 10.00

95 19/2.52 1.1 2.0 31.8 3075 0.193 0.247 0.0616 13.50


3
120 37/2.03 1.2 2.1 35.2 3885 0.153 0.196 0.0613 17.10

150 37/2.25 1.4 2.3 38.9 4750 0.124 0.160 0.0618 21.40

185 37/2.52 1.6 2.4 43.5 5925 0.0991 0.129 0.0623 26.40

240 61/2.25 1.7 2.6 48.8 7840 0.0754 0.0996 0.0612 34.30

300 61/2.52 1.8 2.8 54.0 9760 0.0601 0.0809 0.0605 42.90

400 61/2.85 2.0 3.0 61.0 11985 0.0470 0.0653 0.0603 57.20

16 7/1.70 0.7 1.8 19.5 855 1.15 1.47 0.0761 2.28

25 7/2.14 0.9 1.8 22.0 1300 0.727 0.927 0.0683 3.57

35 19/1.53 0.9 1.8 24.3 1635 0.524 0.669 0.0656 5.00

50 19/1.78 1.0 1.9 27.5 2175 0.387 0.494 0.0651 7.15

70 19/2.14 1.1 2.0 32.0 3070 0.268 0.342 0.0637 10.00

95 19/2.52 1.1 2.1 35.8 4150 0.193 0.247 0.0616 13.50


4
120 37/2.03 1.2 2.3 39.9 5210 0.153 0.196 0.0613 17.10

150 37/2.25 1.4 2.4 44.0 6405 0.124 0.160 0.0618 21.40

185 37/2.52 1.6 2.6 49.5 8010 0.0991 0.129 0.0623 26.40

240 61/2.25 1.7 2.8 55.8 10500 0.0754 0.0996 0.0612 34.30

300 61/2.52 1.8 3.0 61.3 13070 0.0601 0.0809 0.0605 42.90

400 61/2.85 2.0 3.3 68.5 16120 0.0470 0.0653 0.0603 57.20
2
Circular or compacted circular stranded conductors. (Up to and including 25mm )
2
Sector shaped stranded conductors. (35mm and above)

X3
XLPE-INSULATED POWER CABLE
600/1000V, XLPE Insulated, PVC Sheathed Armoured Cables

Application
Power cables for electricity supply are installed in open air, underground, in cable
ducts, outdoor and indoors, power stations, for industry and distribution boards as well
as in subscriber networks where there is a risk of mechanical damage. The cables are
suitable for continuous operation at a maximum conductor temperature of 90 oC.
Construction : Technical Data :
Conductor : Circular stranded, circular compact stranded Voltage : 600/1000V
or sector shaped stranded plain annealed Temperature : Maximum 90oC
copper wire acc. to IEC 60228 class 2 Reference : IEC 60502-1
Insulation : XLPE (cross-linked polyethylene) acc. to Testing Voltage : 3500V
IEC 60502-1 Min. Bending Radius : 10 X Overall Diameter
Identification Single core – Black or Natural
of cores: Two core – Red and Black
Three core – Red, Yellow, Blue
Four core – Red, Yellow, Blue, Black
Laying Up : Cores stranded together. Where necessary,
Binder tapes and non-hygroscopic fillers may
be applied
Bedding : Extruded black PVC (polyvinyl chloride)
compound or lapped PVC tapes
Colour: Black
Armour : Single core - Consist of a single layer of non-
magnetic material, such as aluminium wire
Two core and above – Consist of a single layer
of galvanized steel wires
Sheath : PVC (polyvinyl chloride) compound type ST2
acc. to IEC 60502-1
Colour: Black
(Termite protection sheathing upon request)
(Rodent protection sheathing upon request)
(UV protection sheathing upon request)
(Flame Retardant sheathing upon request)

X4
XLPE-INSULATED POWER CABLE
600/1000V, XLPE Insulated, PVC Sheathed Armoured Cables

Number Electrical Characteristics


Nominal
and Thickness Thickness Approx Approx
No. of Cross- Short
Diameter of of Overall Net Cond. Resistance
Cores Sectional Reactance Circuit
of Insulation Sheath Diameter Weight
Area D. C. at 50 Hz at at 50 Hz Current
Wires
20oC 90oC for 1 sec.
no mm2 no/mm mm mm mm kg/km /km /km /km kA

70 19/2.14 1.1 1.8 20.5 975 0.268 0.342 0.107 10.00

95 19/2.52 1.1 1.8 22.5 1270 0.193 0.247 0.102 13.50

120 37/2.03 1.2 1.8 24.5 1600 0.153 0.196 0.101 17.10

150 37/2.25 1.4 1.8 27.5 1910 0.124 0.159 0.0999 21.40

185 37/2.52 1.6 1.8 30.5 2330 0.0991 0.128 0.0975 26.40
1
240 61/2.25 1.7 1.9 33.0 2985 0.0754 0.0982 0.0946 34.30

300 61/2.52 1.8 1.9 36.0 3700 0.0601 0.0793 0.0920 42.90

400 61/2.85 2.0 2.1 40.5 4790 0.0470 0.0632 0.0923 57.20

500 61/3.20 2.2 2.2 44.5 5885 0.0366 0.0509 0.0903 71.50

630 127/2.52 2.4 2.3 49.0 7480 0.0283 0.0415 0.0878 90.00

16 7/1.70 0.7 1.8 20.5 865 1.15 1.47 0.0761 2.28

25 7/2.14 0.9 1.8 24.0 1280 0.727 0.927 0.0679 3.57

35 19/1.53 0.9 1.7 24.9 1525 0.524 0.699 0.0652 5.00

50 19/1.78 1.0 1.8 27.0 1800 0.387 0.494 0.0648 7.15

70 19/2.14 1.1 2.0 30.5 2455 0.268 0.342 0.0633 10.00

2 95 19/2.52 1.1 2.1 34.2 3310 0.193 0.247 0.0612 13.50

120 37/2.03 1.2 2.2 37.5 4010 0.153 0.196 0.0609 17.10

150 37/2.25 1.4 2.3 40.8 4735 0.124 0.160 0.0618 21.40

185 37/2.52 1.6 2.5 45.8 6120 0.0991 0.129 0.0623 26.40

240 61/2.25 1.7 2.7 50.8 7650 0.0754 0.0993 0.0612 34.30

300 61/2.52 1.8 2.8 54.8 9120 0.0601 0.0807 0.0605 42.90
2
Circular or compacted circular stranded. (Single core: All; 2 Core: Up to and including 25mm )
2
Sector shaped stranded conductors (2 Core: 35mm and above)

X5
XLPE-INSULATED POWER CABLE
600/1000V, XLPE Insulated, PVC Sheathed Armoured Cables

Number Electrical Characteristics


Nominal
and Thickness Thickness Approx Approx
No. of Cross- Short
Diameter of of Overall Net Cond. Resistance
Cores Sectional Reactance Circuit
of Insulation Sheath Diameter Weight
Area D. C. at 50 Hz at at 50 Hz Current
Wires
20oC 90oC for 1 sec.
no mm2 no/mm mm mm mm kg/km /km /km /km kA

16 7/1.70 0.7 1.8 21.5 1030 1.15 1.47 0.0761 2.28

25 7/2.14 0.9 1.8 25.5 1650 0.727 0.927 0.0679 3.57

35 19/1.53 0.9 1.8 27.5 2015 0.524 0.669 0.0652 5.00

50 19/1.78 1.0 1.8 30.5 2500 0.387 0.494 0.0648 7.15

70 19/2.14 1.1 2.0 35.1 3535 0.268 0.342 0.0633 10.00

3 95 19/2.52 1.1 2.2 39.3 4550 0.193 0.247 0.0612 13.50

120 37/2.03 1.2 2.3 42.5 5510 0.153 0.196 0.0609 17.10

150 37/2.25 1.4 2.5 48.0 6990 0.124 0.160 0.0618 21.40

185 37/2.52 1.6 2.6 52.5 8460 0.0991 0.129 0.0623 26.40

240 61/2.25 1.7 2.8 58.0 10610 0.0754 0.0996 0.0612 34.30

300 61/2.52 1.8 3.0 63.5 12900 0.0601 0.0809 0.0605 42.90

16 7/1.70 0.7 1.8 25.0 1520 1.15 1.47 0.0761 2.28

25 7/2.14 0.9 1.8 28.0 2035 0.727 0.927 0.0679 3.57

35 19/1.53 0.9 1.9 30.5 2525 0.524 0.669 0.0652 5.00

50 19/1.78 1.0 2.0 33.5 3170 0.387 0.494 0.0648 7.15

70 19/2.14 1.1 2.2 39.5 4550 0.268 0.342 0.0633 10.00

4 95 19/2.52 1.1 2.3 43.5 5800 0.193 0.247 0.0612 13.50

120 37/2.03 1.2 2.5 49.0 7480 0.153 0.196 0.0609 17.10

150 37/2.25 1.4 2.6 53.5 8925 0.124 0.160 0.0618 21.40

185 37/2.52 1.6 2.8 58.5 10800 0.0991 0.129 0.0623 26.40

240 61/2.25 1.7 3.0 65.5 13800 0.0754 0.0996 0.0612 34.30

300 61/2.52 1.8 3.2 70.0 16800 0.0601 0.0809 0.0605 42.90
2
Circular or compacted circular stranded conductors. (Up to and including 25mm )
2
Sector shaped stranded conductors. (35mm and above)

X6
XLPE-INSULATED POWER CABLE
INSTALLED IN AIR
Current Ratings for XLPE Insulated, PVC-Sheathed, Unarmoured Cables
600/1000V IEC 60502-1
Single core Two core Three and four core
Two cables spaced # Three cables
Nominal Trefoil touching Laid flat spaced # Approx. Approx.
area of Approx. Current volt drop Current volt drop
conductor Current volt drop Approx. volt Approx.
rating per amp rating per amp
rating per amp Current drop Current volt drop
per metre per metre
per metre rating per amp rating per amp
per metre per metre
mm2 amp mV amp mV Amp mV amp mV amp mV
16 115 2.90 96 2.50
25 150 1.80 130 1.60
35 180 1.30 160 1.10
50 255 1.00 215 0.85 250 0.88 225 0.98 190 0.85
70 330 0.72 270 0.61 325 0.64 280 0.69 245 0.60
95 410 0.56 340 0.45 395 0.49 350 0.51 300 0.44
120 480 0.46 400 0.36 470 0.41 405 0.41 350 0.36
150 550 0.40 460 0.31 540 0.36 465 0.35 400 0.30
185 640 0.35 530 0.26 620 0.32 540 0.29 465 0.25
240 760 0.31 630 0.22 740 0.29 630 0.24 560 0.21
300 900 0.29 740 0.19 880 0.27 740 0.21 630 0.19
400 1060 0.27 870 0.17 1040 0.26 840 0.19 720 0.18
500 1250 0.26 1020 0.16 1210 0.25
630 1480 0.25 1140 0.15 1420 0.24
800 1620 0.24 1260 0.14 1560 0.23
1000 1770 0.23 1400 0.13 1700 0.22
#Adjacent cable surfaces separated by one cable diameter

Current Ratings for XLPE Insulated, PVC-Sheathed, Armoured Cables


600/1000V IEC 60502-1
Single core*
Three cables trefoil Two core Three and four core
Nominal Two cables spaced #
touching
area of Approx. Approx. Approx. Approx.
conductor Current volt drop Current volt drop Current volt drop Current volt drop
rating per amp rating per amp rating per amp rating per amp
per metre per metre per metre per metre
mm2 amp mV amp mV amp mV amp mV
16 115 2.90 100 2.60
25 155 1.90 135 1.60
35 190 1.30 165 1.20
50 275 1.00 225 0.86 230 1.00 195 0.87
70 345 0.74 290 0.62 290 0.70 250 0.61
95 420 0.56 350 0.46 360 0.52 305 0.45
120 490 0.47 410 0.37 415 0.42 355 0.36
150 550 0.42 465 0.32 470 0.35 415 0.30
185 620 0.37 540 0.27 550 0.29 470 0.25
240 730 0.33 630 0.23 640 0.24 560 0.21
300 830 0.30 720 0.21 740 0.22 630 0.19
400 900 0.29 830 0.19 820 0.20 720 0.18
500 1000 0.28 920 0.18
630 1100 0.27 1040 0.17
800 1210 0.26 1140 0.16
1000 1320 0.25 1370 0.15
*Single core cables are aluminium wire armoured
#Adjacent cable surfaces separated by one cable diameter
Rating Factors for other Ambient Air Temperature
o
Ambient air temperature C 25 30 35 40 45 50 55 60
Rating factor 1.04 1.00 0.95 0.90 0.85 0.79 0.73 0.67

X7
XLPE-INSULATED POWER CABLE
LAID DIRECT IN GROUND
Current Ratings for XLPE Insulated, PVC-Sheathed, Unarmoured Cables
600/1000V IEC 60502-1
Single core Two core Three and four core
Two cables spaced # Three cables
Nominal Approx. Approx.
Trefoil touching Laid flat spaced # volt drop volt drop
area of Approx. Current Current
conductor Current volt drop Approx. volt drop Approx. per amp per amp
rating rating
rating per amp Current per amp per metre Current volt drop per per
per metre rating rating per amp metre metre
Trefoil Flat per metre
2
mm amp mV amp mV mV amp mV amp mV amp mV
16 130 2.80 110 2.50
25 165 1.80 135 1.60
35 200 1.30 165 1.10
50 265 1.00 215 0.85 0.87 230 0.88 235 0.97 200 0.84
70 325 0.72 265 0.61 0.62 285 0.64 295 0.68 245 0.59
95 380 0.56 310 0.44 0.45 330 0.49 360 0.50 295 0.44
120 440 0.46 360 0.36 0.37 375 0.41 400 0.41 340 0.35
150 495 0.40 405 0.31 0.32 425 0.36 465 0.34 375 0.29
185 570 0.35 455 0.26 0.27 485 0.32 510 0.29 430 0.25
240 660 0.31 530 0.22 0.23 570 0.29 610 0.24 500 0.21
300 740 0.29 610 0.19 0.21 640 0.27 670 0.21 560 0.18
400 850 0.27 690 0.17 0.19 740 0.26 770 0.19 660 0.16
500 950 0.26 780 0.16 0.18 840 0.25
630 1100 0.25 890 0.15 0.17 940 0.24
800 1210 0.24 980 0.14 0.16 1030 0.23
1000 1320 0.23 1070 0.13 0.15 1130 0.22
#Adjacent cable surfaces separated by one cable diameter
Current Ratings for XLPE Insulated, PVC-Sheathed, Armoured Cables
600/1000V IEC 60502-1
Single core*
Two core Three and four core
Nominal Two cables spaced Three cables trefoil touching
area of
Approx. Approx. Approx. Approx.
conductor Current Current Current Current
volt drop per volt drop per volt drop per volt drop per
rating rating rating rating
amp per metre amp per metre amp per metre amp per metre
mm2 amp mV amp mV amp mV amp mV
16 130 2.90 105 2.60
25 165 1.90 140 1.60
35 200 1.30 165 1.20
50 255 0.99 220 0.86 235 1.00 200 0.87
70 315 0.70 270 0.61 295 0.70 245 0.61
95 375 0.53 320 0.46 355 0.52 295 0.45
120 430 0.43 365 0.37 400 0.42 335 0.36
150 475 0.37 405 0.32 445 0.35 375 0.30
185 540 0.31 455 0.27 500 0.29 430 0.25
240 620 0.26 520 0.23 585 0.24 495 0.21
300 700 0.24 585 0.21 650 0.22 550 0.19
400 770 0.21 650 0.19 730 0.19 620 0.18
500 850 0.20 720 0.18
630 930 0.19 780 0.17
800 1020 0.18 880 0.16
1000 1110 0.17 930 0.15
*Single core cables are aluminium wire armoured
Basic Assumptions
o o
Ground temperature : 25 C Ground thermal resistivity : 1.2 C m/W
Depth of laying : 0.5 metre ( to the centre of cable or trefoil group of cables)
o
Maximum conductor temperature : 90 C
Rating Factors for other Ground Temperature
o
Ambient air temperature C 15 20 25 30 35 40 45
Rating factor 1.07 1.04 1.0 0.96 0.92 0.88 0.83

X8
XLPE-INSULATED POWER CABLE
RUN IN SINGLE WAY DUCTS
Current Ratings for XLPE Insulated, PVC-Sheathed, Unarmoured Cables
600/1000V IEC 60502-1
Single core Two core Three and four core
Two cables: ducts Three cables: ducts touching,
Nominal touching trefoil or flat
Approx. Approx.
area of Approx. Trefoil touching Current volt drop Current volt drop
conductor Current volt drop Approx. volt drop rating per amp rating per amp
rating per amp Current per amp per metre per metre per metre
per metre rating
Trefoil Flat
mm2 Amp mV amp mV mV amp mV amp mV
16 110 2.9 87 2.5
25 130 1.8 120 1.6
35 160 1.3 135 1.1
50 245 1.1 225 0.93 0.94 190 0.98 165 0.85
70 300 0.80 275 0.70 0.72 240 0.69 200 0.60
95 350 0.65 320 0.56 0.57 285 0.51 240 0.44
120 405 0.55 370 0.48 0.50 330 0.41 280 0.36
150 455 0.50 415 0.43 0.45 370 0.35 310 0.30
185 520 0.45 465 0.39 0.41 425 0.29 355 0.25
240 610 0.40 540 0.35 0.37 485 0.24 410 0.21
300 690 0.37 610 0.32 0.35 560 0.21 465 0.19
400 790 0.35 700 0.30 0.32 630 0.19 530 0.18
500 900 0.32 790 0.28 0.31
630 1030 0.30 900 0.26 0.29
800 1130 0.28 990 0.25 0.28
1000 1230 0.26 1080 0.24 0.27

Current Ratings for XLPE Insulated, PVC-Sheathed, Armoured Cables


600/1000V IEC 60502-1
Single core*
Three cables: ducts trefoil Two core Three and four core
Nominal Two cables: ducts touching
area of touching
conductor Approx. Approx. Approx. Approx.
Current Current Current Current
volt drop per volt drop per volt drop per volt drop per
rating rating rating rating
amp per metre amp per metre amp per metre amp per metre
mm2 amp mV amp mV amp mV amp mV
16 105 2.90 87 2.60
25 135 1.90 115 1.60
35 165 1.30 140 1.20
50 240 1.10 220 0.93 195 1.00 165 0.87
70 290 0.80 260 0.70 240 0.70 200 0.61
95 340 0.65 310 0.56 290 0.52 245 0.45
120 385 0.55 345 0.48 330 0.42 280 0.36
150 415 0.50 380 0.43 375 0.35 315 0.30
185 450 0.45 410 0.39 425 0.29 355 0.25
240 515 0.40 465 0.35 485 0.24 410 0.21
300 565 0.37 510 0.32 550 0.22 460 0.19
400 600 0.35 540 0.30 620 0.20 520 0.18
500 640 0.33 580 0.28
630 700 0.30 620 0.26
800 770 0.28 680 0.24
1000 840 0.26 740 0.21
*Single core cables are aluminium wire armoured
Basic Assumptions
o o
Ground temperature : 25 C Ground thermal resistivity : 1.2 C m/W
Depth of laying : 0.5 metre ( to the centre of cable or trefoil group of cables)
o
Maximum conductor temperature : 90 C
Rating Factors for other Ground Temperature
o
Ambient air temperature C 15 20 25 30 35 40 45
Rating factor 1.07 1.04 1.0 0.96 0.92 0.88 0.83

X9
XLPE-INSULATED POWER CABLE
ALLOWABLE SHORT CIRCUIT CURRENTS FOR XLPE INSULATED CABLE

16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000

100
90
80
70
60
50

40

30

20
0.5 SEC.

1 SEC.

2 SEC. 10
9.0
3 SEC.
4 SEC. 8.0
7.0
6.0
5 SEC.
5.0

4.0
SHORT CIRCUIT CURRENT (kA)

3.0

2.0

1.0

CONDUCTOR SIZE (mm2)


CONDUCTOR : COPPER
INSULATION : CROSS LINKED POLYETHYLENE
Curves based on formula -

l = 0.143A
t

l = Short circuit current (kA)


A = Conductor area (mm2)
t = Time of short circuit (seconds)

X 10
FIRE RESISTANT
CABLE
SAMA KEBEL SDN BHD

ARMOURED & NON


ARMOURED
FIRE-RESISTANT CABLE
600/1000V, LSHF Insulated, LSHF Sheathed Non-Armoured Fire Resistant Cables

Application
Non-armoured fire-resistant cables are for general application in power and signal
wirings where mechanical damages are not to be expected, not only for emergency
circuits but for areas where maintaining circuit integrity and/or control of fire spread
are deemed desirable. With a high level of fire resistance, the cables are durable and
flexible enough to be pulled into conduit and trunking, and are the cost effective
alternative to standard cable wiring systems. Due to its low smoke halogen free
compound which ensures flame retardant, low toxicity and acidic gases and smoke
emission, the cables increase chances of survival during fire breakout and are ideal for
installation in existing metal conduit or trunking to update existing alarm and lighting
systems previously wired in PVC cables in the public, commercial and industrial
environments. The cables are RoHS compliance and are suitable for continuous
operation at a maximum conductor temperature of 70 oC.

Construction : Technical Data :


Conductor : Circular stranded plain annealed copper Voltage : 600/1000V
wire acc. to IEC 60228/BS 6360 Temperature : Maximum 90oC
Flame Barrier Layer : Mica based fire-resistant tapes Reference : IEC 60502-1,
Insulation : LSHF (low smoke halogen free) compound; IEC 60331,
Identification of Single core – Natural SS 299 / BS 6387 CWZ
cores: Two core - Red and Black Testing Voltage : 3500V
Three core - Red, Yellow, Blue Min. Bending Radius : 8 X Overall Diameter
Four core – Red, Yellow, Blue, Black
Laying Up : Cores stranded together. Where necessary,
binder tapes and non hygroscopic fillers may
be applied
Sheath : LSHF (low smoke halogen free) compound;
Colour : Orange
(Termite protection sheathing upon request)
(Rodent protection sheathing upon request)

Z1
FIRE-RESISTANT CABLE
600/1000V, LSHF Insulated, LSHF Sheathed Non-Armoured Fire Resistant Cables

Nominal Electrical Characteristics


Number
cross- Thickness Thickness Approx Approx
No. of and Short
sectional of of overall net Cond. Insulation
cores diameter Circuit
area of insulation oversheath diameter weight Resistance Resistance
of wires Current
conductor Max at 20oC Min at 70oC
for 1 sec.
no mm2 no/mm mm mm mm kg/km /km /km kA
1.5 7/0.53 0.7 1.4 7.0 65 12.1 0.010 0.215
2.5 7/0.67 0.7 1.4 7.5 80 7.41 0.0084 0.358
4 7/0.85 0.7 1.4 8.0 100 4.61 0.0070 0.572
6 7/1.04 0.7 1.4 8.5 125 3.08 0.0059 0.858
10 7/1.35 0.7 1.4 9.5 170 1.83 0.0047 1.43
16 7/1.70 0.7 1.4 10.5 235 1.15 0.0039 2.28
25 7/2.14 0.9 1.4 12.5 350 0.727 0.0039 3.57
35 19/1.53 0.9 1.4 13.5 445 0.524 0.0034 5.00
50 19/1.78 1.0 1.4 15.0 585 0.387 0.0032 7.15
1 70 19/2.14 1.1 1.5 17.0 815 0.268 0.0030 10.0
95 19/2.52 1.1 1.5 19.0 1080 0.193 0.0026 13.5
120 37/2.03 1.2 1.5 21.0 1340 0.153 0.0026 17.1
150 37/2.25 1.4 1.6 23.0 1635 0.124 0.0026 21.4
185 37/2.52 1.6 1.7 25.5 2030 0.0991 0.0026 26.4
240 61/2.25 1.7 1.8 28.5 2645 0.0754 0.0025 34.3
300 61/2.52 1.8 1.8 31.0 3260 0.0601 0.0023 42.9
400 61/2.85 2.0 1.9 34.8 4130 0.0470 0.0023 57.2
500 61/3.20 2.2 2.2 39.2 5200 0.0366 0.0023 71.5
630 127/2.52 2.4 2.3 43.2 6690 0.0283 0.0022 90.0
1.5 7/0.53 0.7 1.8 12.0 200 12.1 0.010 0.215
2.5 7/0.67 0.7 1.8 12.5 235 7.41 0.0084 0.358
4 7/0.85 0.7 1.8 14.0 305 4.61 0.0070 0.572
6 7/1.04 0.7 1.8 15.0 375 3.08 0.0059 0.858
10 7/1.35 0.7 1.8 17.0 510 1.83 0.0047 1.430
16 7/1.70 0.7 1.8 19.0 685 1.15 0.0039 2.288
25 7/2.14 0.9 1.8 22.0 965 0.727 0.0039 3.515
35 19/1.53 0.9 1.8 24.0 1220 0.524 0.0034 5.005
2
50 19/1.78 1.0 1.8 27.0 1590 0.387 0.0032 7.150
70 19/2.14 1.1 1.8 30.5 2145 0.268 0.0030 10.010
95 19/2.52 1.1 1.9 34.5 2845 0.193 0.0026 13.585
120 37/2.03 1.2 2.0 38.0 3520 0.153 0.0026 17.160
150 37/2.25 1.4 2.2 42.5 4360 0.124 0.0026 21.450
185 37/2.52 1.6 2.3 46.5 5375 0.0991 0.0026 26.455
240 61/2.25 1.7 2.5 52.5 6940 0.0754 0.0025 34.320
300 61/2.52 1.8 2.6 59.3 8520 0.0601 0.0023 42.900

Z2
FIRE-RESISTANT CABLE
600/1000V, LSHF Insulated, LSHF Sheathed Non-Armoured Fire Resistant Cables

Nominal Electrical Characteristics


Number
cross- Thickness Thickness Approx Approx Short
No. of and Cond. Insulation
sectional of of overall net Circuit
cores diameter Resistance Resistance
area of insulation oversheath diameter weight Current
conductor
of wires Max at 20oC Min at 70oC
for 1 sec.
No mm2 no/mm mm mm mm kg/km /km /km kA
1.5 7/0.53 0.7 1.8 12.5 230 12.1 0.010 0.215
2.5 7/0.67 0.7 1.8 13.5 280 7.41 0.0084 0.358
4 7/0.85 0.7 1.8 15.0 365 4.61 0.0070 0.572
6 7/1.04 0.7 1.8 16.0 455 3.08 0.0059 0.858
10 7/1.35 0.7 1.8 18.0 630 1.83 0.0047 1.430
16 7/1.70 0.7 1.8 20.5 865 1.15 0.0039 2.288
25 7/2.14 0.9 1.8 23.5 1230 0.727 0.0039 3.515
35 19/1.53 0.9 1.8 25.5 1575 0.524 0.0034 5.005
3
50 19/1.78 1.0 1.8 29.0 2065 0.387 0.0032 7.150
70 19/2.14 1.1 1.9 33.0 2830 0.268 0.0030 10.010
95 19/2.52 1.1 2.0 37.0 3760 0.193 0.0026 13.585
120 37/2.03 1.2 2.1 42.0 4675 0.153 0.0026 17.160
150 37/2.25 1.4 2.4 47.0 5780 0.124 0.0026 21.450
185 37/2.52 1.6 2.4 52.0 7135 0.0991 0.0026 26.455
240 61/2.25 1.7 2.6 58.0 9230 0.0754 0.0025 34.320
300 61/2.52 1.8 2.7 64.0 11375 0.0601 0.0023 42.900
1.5 7/0.53 0.7 1.8 13.5 280 12.1 0.010 0.215
2.5 7/0.67 0.7 1.8 14.5 340 7.41 0.0084 0.358
4 7/0.85 0.7 1.8 16.5 450 4.61 0.0070 0.572
6 7/1.04 0.7 1.8 17.5 560 3.08 0.0059 0.858
10 7/1.35 0.7 1.8 20.0 785 1.83 0.0047 1.430
16 7/1.70 0.7 1.8 22.5 1080 1.15 0.0039 2.288
25 7/2.14 0.9 1.8 26.0 1555 0.727 0.0039 3.515
35 19/1.53 0.9 1.8 28.6 2000 0.524 0.0034 5.005
4
50 19/1.78 1.0 1.8 32.1 2625 0.387 0.0032 7.150
70 19/2.14 1.1 2.0 37.0 3625 0.268 0.0030 10.010
95 19/2.52 1.1 2.1 42.0 4840 0.193 0.0026 13.585
120 37/2.03 1.2 2.3 47.0 6040 0.153 0.0026 17.160
150 37/2.25 1.4 2.4 51.7 7435 0.124 0.0026 21.450
185 37/2.52 1.6 2.6 57.7 9215 0.0991 0.0026 26.455
240 61/2.25 1.7 2.8 65.0 11930 0.0754 0.0025 34.320
300 61/2.52 1.8 3.0 71.6 14720 0.0601 0.0023 42.900

Z3
FIRE-RESISTANT CABLE
600/1000V, LSHF Insulated, LSHF Sheathed Armoured Fire Resistant Cables

Application
Armoured fire-resistant cables offer the advantages of an armoured 600/1000V rated,
low smoke halogen free cable and are for general application in power and signal
wirings, not only for emergency circuits but for areas where maintaining circuit
integrity and/or control of fire spread are deemed desirable. Due to its low smoke
halogen free compound which ensures flame retardant, low toxicity and acidic gases
and smoke emission, the cables increase chances of survival during fire breakout. The
cables are suitable for use in public, commercial and industrial environments where
maintaining life, equipment and structures are critical. The cables are RoHS
compliance and are suitable for continuous operation at a maximum conductor
temperature of 70oC.
Construction : Technical Data :
Conductor : Circular stranded plain annealed copper Voltage : 600/1000V
wire acc. to IEC 60228/BS6360 Temperature : Maximum 90oC
Flame Barrier Layer : Mica based fire-resistant tapes Reference : IEC 60502-1
Insulation : LSHF (low smoke halogen free) compound IEC 60331,
Identification of Single core - Natural SS 299 / BS 6387 CWZ
cores : Two core – Red and Black Testing Voltage : 3500V
Three core – Red, Yellow, Blue Min. Bending Radius : 10 X Overall Diameter
Four core – Red, Yellow, Blue, Black
Laying Up : Cores stranded together. Where necessary,
binder tapes and non hygroscopic fillers may
be applied
Bedding : Extruded LSHF (low smoke halogen free)
compound
Colour : Natural
Armour : Single core - Consist of a single layer of non-
magnetic material, such as aluminium wire
Two core and above – Consist of a single layer
of galvanized steel wires
Sheath : LSHF (low smoke halogen free) compound;
Colour : Orange
(Termite protection sheathing upon request)
(Rodent protection sheathing upon request)

Z4
FIRE-RESISTANT CABLE
600/1000V, LSHF Insulated, LSHF Sheathed Armoured Fire Resistant Cables

Number Electrical Characteristics


Nominal
and Thickness Thickness Approx Approx Short
No. of Cross- Cond. Insulation
Diameter of of Overall Net Circuit
Cores Sectional Resistance Resistance
of Insulation Sheath Diameter Weight Current
Area Max at 20oC Min at 70oC
Wires for 1 sec.
no mm2 no/mm mm mm mm kg/km /km /km kA
70 19/2.14 1.1 1.8 22.5 1015 0.268 0.0030 10.010
95 19/2.52 1.1 1.8 24.0 1400 0.193 0.0026 13.585
120 37/2.03 1.2 1.8 27.0 1700 0.153 0.0026 17.160
150 37/2.25 1.4 1.8 29.0 2000 0.124 0.0026 21.450
185 37/2.52 1.6 1.9 31.3 2400 0.0991 0.0026 26.455
1
240 61/2.25 1.7 2.0 35.0 3300 0.0754 0.0025 34.320
300 61/2.52 1.8 2.1 37.0 3800 0.0601 0.0023 42.900
400 61/2.85 2.0 2.3 42.0 4800 0.0470 0.0023 57.200
500 61/3.20 2.2 2.4 46.0 5975 0.0366 0.0023 71.500
630 127/2.52 2.4 2.5 51.0 7540 0.0283 0.0022 90.090
1.5 7/0.53 0.7 1.8 15.0 415 12.1 0.010 0.215
2.5 7/0.67 0.7 1.8 16.0 470 7.41 0.0084 0.358
4 7/0.85 0.7 1.8 17.0 560 4.61 0.0070 0.572
6 7/1.04 0.7 1.8 18.0 645 3.08 0.0059 0.858
10 7/1.35 0.7 1.8 20.0 900 1.83 0.0047 1.430
16 7/1.70 0.7 1.8 22.5 1180 1.15 0.0039 2.288
25 7/2.14 0.9 1.8 26.5 1600 0.727 0.0039 3.515
2 35 19/1.53 0.9 1.9 29.0 2080 0.524 0.0034 5.005
50 19/1.78 1.0 1.9 32.2 2560 0.387 0.0032 7.150
70 19/2.14 1.1 2.0 37.6 3380 0.268 0.0030 10.010
95 19/2.52 1.1 2.1 41.6 4455 0.193 0.0026 13.585
120 37/2.03 1.2 2.2 45.4 5255 0.153 0.0026 17.160
150 37/2.25 1.4 2.4 50.7 6300 0.124 0.0026 21.450
185 37/2.52 1.6 2.5 55.9 8050 0.0991 0.0026 26.455
240 61/2.25 1.7 2.7 61.9 9885 0.0754 0.0025 34.320

Z5
FIRE-RESISTANT CABLE
600/1000V, LSHF Insulated, LSHF Sheathed Armoured Fire Resistant Cables

Electrical Characteristics
Nominal Number
Thickness Thickness Approx Approx Short
No. of cross- and Cond. Insulation
of of overall net Circuit
cores sectional diameter Resistance Resistance
insulation oversheath diameter weight Current
area of wires Max at 20oC Min at 70oC
for 1 sec.
no mm2 no/mm mm mm mm kg/km /km /km kA
1.5 7/0.53 0.7 1.8 15.9 455 12.1 0.010 0.215
2.5 7/0.67 0.7 1.8 16.8 520 7.41 0.0084 0.358
4 7/0.85 0.7 1.8 18.0 635 4.61 0.0070 0.572
6 7/1.04 0.7 1.8 20.0 740 3.08 0.0059 0.858
10 7/1.35 0.7 1.8 21.6 1135 1.83 0.0047 1.430
16 7/1.70 0.7 1.8 24.0 1395 1.15 0.0039 2.288
25 7/2.14 0.9 1.8 28.5 2070 0.727 0.0039 3.515
3 35 19/1.53 0.9 1.8 31.0 2485 0.524 0.0034 5.005
50 19/1.78 1.0 1.9 34.5 3090 0.387 0.0032 7.150
70 19/2.14 1.1 2.1 40.5 4010 0.268 0.0030 10.010
95 19/2.52 1.1 2.2 45.0 5460 0.193 0.0026 13.585
120 37/2.03 1.2 2.3 49.0 6520 0.153 0.0026 17.160
150 37/2.25 1.4 2.5 55.0 8310 0.124 0.0026 21.450
185 37/2.52 1.6 2.7 60.0 9920 0.0991 0.0026 26.455
240 61/2.25 1.7 2.9 67.0 12350 0.0754 0.0025 34.320
1.5 7/0.53 0.7 1.8 16.6 520 12.1 0.010 0.215
2.5 7/0.67 0.7 1.8 17.7 605 7.41 0.0084 0.358
4 7/0.85 0.7 1.8 19.5 800 4.61 0.0070 0.572
6 7/1.04 0.7 1.8 21.0 1000 3.08 0.0059 0.858
10 7/1.35 0.7 1.8 23.5 1350 1.83 0.0047 1.430
16 7/1.70 0.7 1.8 26.4 1700 1.15 0.0039 2.288
25 7/2.14 0.9 1.8 31.0 2465 0.727 0.0039 3.515
4 35 19/1.53 0.9 1.9 34.2 3000 0.524 0.0034 5.005
50 19/1.78 1.0 2.0 39.0 3900 0.387 0.0032 7.150
70 19/2.14 1.1 2.2 44.0 5290 0.268 0.0030 10.010
95 19/2.52 1.1 2.3 49.0 6720 0.193 0.0026 13.585
120 37/2.03 1.2 2.5 55.0 8570 0.153 0.0026 17.160
150 37/2.25 1.4 2.7 60.0 10250 0.124 0.0026 21.450
185 37/2.52 1.6 2.8 66.0 12275 0.0991 0.0026 26.455
240 61/2.25 1.7 3.1 75.0 16000 0.0754 0.0025 34.320

Z6
LSHF-INSULATED POWER CABLE
ALLOWABLE SHORT CIRCUIT CURRENTS FOR LSHF INSULATED CABLE

16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000

100
90
80
70
60
50

40

30

20
0.5 SEC.

1 SEC.

2 SEC. 10
9.0
3 SEC.
4 SEC. 8.0
7.0
6.0
5 SEC.
5.0

4.0
SHORT CIRCUIT CURRENT (kA)

3.0

2.0

1.0

CONDUCTOR SIZE (mm2)


CONDUCTOR : COPPER
INSULATION : LOW SMOKE HALOGEN FREE
Curves based on formula -

l = 0.143A
t

l = Short circuit current (kA)


A = Conductor area (mm2)
t = Time of short circuit (seconds)

Z7
Lot 16, Jalan RP3, Rawang Perdana Industrial Estate,
48000 Rawang, Selangor Darul Ehsan, Malaysia.
Tel: +603-6092 1353 Fax: +603-6092 9871 / 6092 1352