Вы находитесь на странице: 1из 1

9 8 7 6 5 4 3 2 1

NOTES

SCHEDULE FOR AIR TERMINAL


Supply air diffuser Supply Return air diffuser Return Return/Extract
Supply Return (4 way blow type Air quantity (4 way blow type Air quantity Supply grille Supply grille Supply Return grille grille Return
FCU Reference Air quantity Air quantity Supply Air louvre faced) from each Return Air louvre faced) from each Supply Air Size (Eggcrate type) Air quantity from Return Air Size (Eggcrate type) Air quantity from
Number Room Served Diffuser TAG (Size-600x600) Supply Diffuser TAG (Size-600x600) Supply Grille TAG each Supply grille Grille TAG each Supply grille
(L/S) (L/S) (in mm) Diffuser (in mm) Diffuser (in mm ) Qty (L/S) (in mm ) (L/S)
H Qty (L/S) Qty (L/S) Qty H

Ground Floor
GF-FCU-01 Manager Office 145 145 SAD-01 1 145 RAD-01 1 145
GF-FCU-02 Corridor 145 145 SAD-02 1 145 RAD-02 1 145
Security Room 100 100 SAD-03 1 100 RAD-03 1 100
GF-FCU-03
Fire Alarm Room 50 50 SAD-04 1 50 RAD-04 1 50
GF-FCU-04 Airlock Foyer 145 145 SAD-05 1 145 RAD-05 1 145
Quartermaster Store 50 50 SAD-06 1 50 RAD-06 1 50
GF-FCU-05
Office 100 100 SAD-07 1 100 RAD-07 1 100
Warehouse Store Area 02 80 80 SAD-08-09 2 40 RAD-08-09 2 40
GF-FCU-06
Storekeeper 65 65 SAD-10 1 65 RAD-10 1 65
GF-FCU-07 Female Prayer Room 120 120 SAD-11 1 120 RAD-11 1 120
ERU 2
Ablution 25 28 SAD-12 1 25 RAD-12 1 28
GF-FCU-08 Corridor 145 145 SAD-13 1 145 RAD-13 1 145
G Warehouse Store Area 45 45 SAD-14-15 2 23 RAD-14-15 2 23 G
GF-FCU-09
File room 100 100 SAD-16 1 100 RAD-16 1 100
GF-FCU-10 Workshop 150 150 SAD-17-18 2 75 RAD-17-18 2 75 SAG-41-42 150 X 150
GF-FCU-11 Male Prayer Room 140 140 SAD-19-20 2 70 RAD-19-20 2 70
ERU 2
Ablution 25 28 SAD-21 1 25 RAD-21 1 28
Generator Room 79 79 SAD-22 1 79 RAD-22 1 79
GF-FCU-12
Electrical Room 79 79 SAD-23 1 79 RAD-23 1 79
GF-FCU-13 BMS ELV Room 145 145 SAD-24 1 145 RAD-24 1 145
GF-FCU-14 Water Tank Room 150 150 SAD-25-26 2 75 RAD-25-26 2 75
GF-FCU-15 Corridor 145 145 SAD-27 1 145 RAD-27 1 145
ERU Janitor 10 15 SAG-01 150 X 150 1 10 RAG-01 150 X 150 1 15
ERU Airlock 30 25 SAG-02 150 X 150 1 30 RAG-02 150 X 150 1 25
Foyer 2
ERU 10 SAG-39 150 X 150 1 10
ERU Male Toilet 90 100 SAG-03-04 150 X 150 2 45 RAG-03-06 150 X 150 4 25
F ERU Airlock 30 25 SAG-05 150 X 150 1 30 RAG-07 150 X 150 1 25 F
Foyer 2
ERU 10 SAG-40 150 X 150 1 10
RAG-08-10,
ERU Female Toilet 90 100 SAG-06-07 150 X 150 2 45 28 150 X 150 4 25
ERU Staitcase 01 30 26 SAG-08 150 X 100 1 30 RAG-11 150 X 100 1 26
ERU Staitcase 02 130 110 SAG-09 300 X 200 1 130 RAG-12 300 X 200 1 110
CRAC 01-02 Temperature controlled 2092 110 SAG-19-38 300 X 150 20 104
warehouse
First Floor
FF-FCU-01 Corridor 145 145 SAD-28 1 145 RAD-28 1 145
FF-FCU-02 Office 01 533 533 SAD-29-33 5 107 RAD-29-35 7 76
FF-FCU-03 Corridor 145 145 SAD-34 1 145 RAD-36 1 145
FF-FCU-04 Office 02 383 383 SAD-35-38 4 96 RAD-37-42 6 64
FF-FCU-05 Break Room 533 533 SAD-39-43 5 107 RAD-43-49 7 76
FF-FCU-06 Corridor 145 145 SAD-44 1 145 RAD-50 1 145
FF-FCU-07 Pantry 158 158 SAD-45-46 2 79 RAD-51-52 2 79
FF-FCU-08 & Multipurpose Room 1200 1200 6
F FF-FCU-09 SAD-47-52 6 200 RAD-53-58 200 F
FF-FCU-10 & Meeting Room 766 766 6
FF-FCU-11 SAD-53-58 6 128 RAD-59-64 128
FF-FCU-12 Electrical Room 145 145 SAD-59 1 145 RAD-65 1 145
ERU Foyer 5 4 SAG-11 150 X 150 1 5 RAG-14 150 X 150 1 4
2
ERU Female Toilet 90 100 SAG-12-13 150 X 150 2 45 RAG-15-18 150 X 150 4 25
ERU Foyer 5 4 SAG-14 150 X 150 1 5 RAG-20 150 X 150 1 4 REFERENCE
2
ERU Male Toilet 90 100 SAG-15-16 150 X 150 2 45 RAG-21-24 150 X 150 4 25 DRAWING NUMBER REVISION
ERU Staitcase 01 50 43 SAG-17 300 X 200 1 50 RAG-25 300 X 200 1 43
ERU Staitcase 02 120 102 SAG-18 300 X 200 1 120 RAG-19 300 X 200 1 102

SCHEDULE OF FIRE DAMPER SCHEDULE OF FIRE DAMPER SCHEDULE OF VOLUME CONTROL DAMPER SCHEDULE OF VOLUME CONTROL DAMPER
Size Quantity Size Quantity Size Quantity Size Quantity
E S.No FD Tag S.No FD Tag S.No VCD Tag S.No VCD Tag E
(MM X MM) No. (MM X MM) No. (MM X MM) No. (MM X MM) No.
1 FD-1 300 X 200 1 41 FD-41 700 X 300 1 1 VCD-1 100 X 100 1 41 VCD-41 400 X 150 1
2 FD-2 300 X 200 1 42 FD-42 550 X 300 1 2 VCD-2 100 X 100 1 42 VCD-42 400 X 150 1 CONSTRUCTION NOTE (REV. 0)
3 FD-3 100 X 100 1 43 FD-43 700 X 300 1 3 VCD-3 100 X 100 1 43 VCD-43 400 X 300 NA
4 FD-4 100 X 100 1 44 FD-44 700 X 300 1 4 VCD-4 100 X 100 1 44 VCD-44 400 X 300 NA 2
5 FD-5 100 X 100 1 45 FD-45* 400 X 150 1 5 VCD-5 100 X 100 1 45 VCD-45 400 X 300 NA
6 FD-6 100 X 100 1 46 FD-46 400 X 150 1 6 VCD-6 100 X 100 1 46 VCD-46 400 X 300 1
7 FD-7 100 X 100 1 47 FD-47 350 X 150 1 7 VCD-7 100 X 100 1 47 VCD-47 350 X 150 1
8 FD-8 100 X 100 1 48 FD-48 350 X 150 1 8 VCD-8 100 X 100 1 48 VCD-48 350 X 150 1
9 FD-9 150 X 150 1 2 49 FD-49 250 X 250 1 9 VCD-9 100 X 100 1 49 VCD-49 150 X 100 1
10 FD-10 100 X 100 1 50 FD-50 300 X 200 1 10 VCD-10 100 X 100 1 50 VCD-50 150 X 100 1
11 FD-11 150 X 150 1 2 51 FD-51 250 X 200 1 11 VCD-11 100 X 100 1 51 VCD-51 250 X 250 1 SUB CONTRACTOR/INSTALLER SHALL TAKE ALL APPROPRIATE PRECAUTIONS
12 FD-12 100 X 100 1 52 FD-52 200 X 200 1 2 12 VCD-12 100 X 100 1 52 VCD-52 250 X 200 1 2 TO ENSURE THE SAFETY OF ALL PEOPLE LOCATED ON THE WORK
SITE, INCLUDING CONTRACTOR'S/INSTALLER'S PERSONNEL (OR THAT
C 13 FD-13 200 X 100 1 53 FD-53 200 X 200 1 13 VCD-13 100 X 100 1 53 VCD-53 200 X 200 1 OF ITS SUB-CONTRACTOR(S)) PERFORMING THE WORK. C
14 FD-14 150 X 150 1 54 FD-54 500 X 300 1 14 VCD-14 100 X 100 1 54 VCD-54 500 X 300 1
SPECIFICATIONS:
15 FD-15 100 X 100 1 55 FD-55 200 X 150 1 15 VCD-15 100 X 100 1 55 VCD-55 250 X 200 1 2
16 FD-16 56 FD-56 16 VCD-16 56 VCD-56 PROJECT NO.: 13235-001
100 X 100 1 250 X 200 1 100 X 100 1 150 X 150 1
17 FD-17 100 X 100 1 57 FD-57 250 X 200 1 17 VCD-17 100 X 100 1 57 VCD-57 200 X 150 1
18 FD-18 100 X 100 1 58 FD-58 500 X 200 1 18 VCD-18 100 X 100 1 58 VCD-58 200 X 150 NA 2
19 FD-19 150 X 100 1 2 59 FD-59 200 X 150 1 19 VCD-19 100 X 100 1 59 VCD-59 150 X 150 1
20 FD-20* 150 X 100 1 60 FD-60 200 X 100 1 20 VCD-20 100 X 100 1 60 VCD-60 150 X 100 1
3 15.06.17 Amended to ENEC DTR KK DSR ANAS ANAS
21 FD-21* 500 X 200 1 61 FD-61 150 X 100 1 21 VCD-21 100 X 100 1 61 VCD-61 150 X 150 1 comments
22 FD-22* 300 X 250 1 62 FD-62 200 X 150 NA 22 VCD-22 150 X 100 1 62 VCD-62 150 X 100 1 2 09.04.17 Detail Design KK DSR ANAS ANAS

23 FD-23* 500 X 150 1 63 FD-63 200 X 150 NA 23 VCD-23 150 X 100 1 63 VCD-63 150 X 100 1 1 03.02.17 Detail Design KK DSR ANAS ANAS

24 FD-24* 200 X 250 1 64 FD-64 200 X 100 NA 24 VCD-24 100 X 100 1 64 VCD-64 150 X 100 1 REV. DATE DESCRIPTION PREPARED CHECKED REVIEWED APPROVED

25 FD-25 400 X 150 1 65 FD-65 150 X 100 NA 25 VCD-25 150 X 100 1 65 VCD-65 200 X 150 1 CLIENT

26 FD-26 200 X 100 1 66 FD-66 200 X 150 1 26 VCD-26 100 X 100 1 66 VCD-66 200 X 200 1
B 27 FD-27 200 X 100 1 2 67 FD-67 150 X 100 1 27 VCD-27 100 X 100 1 B
28 FD-28 500 X 200 1 68 FD-68 500 X 300 1 28 VCD-28 500 X 200 1
29 FD-29 100 X 100 1 69 FD-69 150 X 100 1 29 VCD-29 200 X 100 1
30 FD-30 300 X 200 1 70 FD-70 200 X 150 1 30 VCD-30 450 X 250 1 2
MAIN CONTRACTOR SUB - CONTRACTOR
31 FD-31 500 X 250 1 71 FD-71 150 X 100 1 31 VCD-31 250 X 300 1
32 FD-32 400 X 150 1 2 72 FD-72 150 X 100 1 32 VCD-32 100 X 100 1
33 FD-33 250 X 250 1 73 FD-73 300 X 200 1 33 VCD-33 250 X 150 1
34 FD-34 400 X 250 1 74 FD-74 300 X 300 1 34 VCD-34 400 X 250 1
35 FD-35 500 X 250 1 75 FD-75* 500 X 200 1 35 VCD-35 250 X 250 1
36 FD-36 600 X 250 1 76 FD-76* 400 X 250 1 36 VCD-36 500 X 250 1
37 FD-37 300 X 250 1 77 FD-77 200 X 200 1 37 VCD-37 150 X 200 1
38 FD-38 350 X 300 1 78 FD-78 200 X 150 1 38 VCD-38 300 X 250 1
PROJECT TITLE
39 FD-39 450 X 300 1 79 FD-79 150 X 150 1 39 VCD-39 150 X 150 1 PHYSICAL PROTECTION SYSTEM (PPS)
40 FD-40 200 X 100 1 2 80 FD-80 300 X 150 1 40 VCD-40 300 X 250 1 PHASE 1
A A
81 FD-81 200 X 150 1 2 PACKAGE TITLE
PPS Warehouse
82 FD-82 400 X 250 1 Equipments Schedule
3
NOTE - 83 FD-83 200 X 200 1 PROJECT SHEET
Fire damper marked with "*" shall be motorized fire damper DRAWING
NUMBER
0-983-F-M105-004 2 02 of 02

Mott MacDonald PACKAGE SAFETY PACKAGE


SCALE UNIT NO. REV.
NUMBER CATEGORY NUMBER
This document is issued for the party which commissioned it and for specific purposes connected with the captioned project only. It should not be relied upon by any other party or used for any other purpose. 1 2 3 4 1&2 3&4 1-4
983 NTS 3
We accept no responsibility for the consequences of this document being relied upon by any other party, or being used for any other purpose, or containing any error or omission which is due to an error or omission in data supplied to us by other parties.

9 8 7 6 5 4 3 2 1