Sprinkler Design Information (1 building)

Project : Engineer in Charge :

1. Building Classification :
Small Residence Other residential Shop
Institutional Office Warehouse
Assembly Factory Others(state) :_____________

Hazard Class :_____

2. Building Parameters
Height :_____m Height of Concealed Ceiling :_____m
Floor Area(sq.m) :_____sq.m Height between highest and lowest sprinklers :_____m
Volume(cu.m) :_____cu.m

3. Design Standards
NFPA13 MS1910 Other (Please State) : __________

4. Type Of Calculation
Pre-Calculated Fully Software Calculation

5. Storage Classification
Storage category : Ceiling height :_____m
Storage height :_____m

6. Sprinkler Parameters
Type of Sprinklers : Sprinkler Temperature :
Design Density :_____mm/min K- Factor :
Design Area :_____sq.m Coverage per sprinkler :_____m
No of in-rack sprinkler activation :
No of Roof sprinkler activation :

7. Tank Parameter
Tank Type :__________________ Discharge type :_________
Priming tank : Yes / No Water Duration :______ min

8. Pump and Tank Size (Table 1)

System
Fully Hydraulic Calculation
Parameters Pre-Calculated
Most Favourable Most Unfavourable
Flow rate (l/m)

Pressure (bar)

Required Pump Size

Net water capacity

Tank Size (cu.m)

TABLE 1
Sprinkler Design Information (multiple building)

Project : Engineer in Charge :

1. Building Classification :
Small Residence Other residential Shop
Institutional Office / Warehouse /
Assembly Factory / Others (State) : ________

2. Building Sprinkler Details (refer to table 1)

3. Storage Classification
Storage category : Ceiling height :_____m
Storage height :_____m
No of in-rack sprinkler activation :
No of Roof sprinkler activation :

4. Tank Parameter
Tank Type :__________________ Discharge type :_________
Priming tank : Yes / No Water Duration :______ min

4. Pump and Tank Size (Table 2)

System
Fully Hydraulic Calculation
Parameters Pre-Calculated
Most Favourable Most Unfavourable
Flow rate (l/m)

Pressure (bar)

Required Pump Size

Net water capacity

Tank Size (cu.m)

TABLE 2
250 mm Diameter Pipe 200 mm Diameter Pipe

K - 360, P - 3.4 K - 320, P - 2.8 K - 360, P - 3.4 K - 320, P - 2.8


Parameters Parameters
Data Data
Flow rate (l/m) 8011.1 6460.7 Flow rate (l/m) 8011.1 6460.7

Pressure (bar) 7.4 5.935 Pressure (bar) 9.55 7.4

Required Pump Size 8500 l/min @ 8 bar 7000 l/min @ 6.6 bar Required Pump Size 8500 l/min @ 10 bar 7000 l/min @ 8 bar

Net water capacity 721 cu.m 630 cu.m Net water capacity 721 cu.m 630 cu.m

Tank Size 10 x 12 x 4h 10 x 10 x 4h Tank Size 10 x 12 x 4h 10 x 10 x 4h


Building Parameters Standards Sprinkler Detail
Design Density
Classfication Hazard Class Height (m) Area (sq.m) Volume (cu.m) Hc(m) Hs(m) NFPA MS1910 Others Type Ac (sq.m) T (K) K-Factor
(mm/min)
BLOCK 1

OFFICE - 14.3 558.15 7981.545 - - - - - - - - Based on UBBL tenth schedule, no protection is required
BLOCK 2

WAREHOUSE & 2634.81 51826.71 - - - -


OH3 19.67 LPC ESFR 12 pts 9 347.15 200
LOADING BAY AREA 510.38 10039.25 - - - -

PRODUCTION OFFICE OH3 19.67 1188.98 23387.24 ? ? - / - MS 5 9 330.15 80

FACTORY OH3 18.32 5758.03 105487.11 ? ? - / - MS 5 9 366.15 80

COMPOUNDING &
OH3 14.63 1626.78 23799.79 ? ? - / - MS 5 9 366.15 80
SCRUBBER & CHLORIN ROOM

TABLE 1

Hc = Height of concealed ceiling (if available)


Hs = Height difference between the highest and lowest sprinkler
Ac = Coverage area of one sprinkler head
T = Sprinkler Temperature
Height = Height between ground and highest occupied floor