SE-105 MANUAL

GROUND-FAULT GROUND-CHECK MONITOR


REVISION 13-D-050315

F1

CT1 CT2 A B L1 L2

GROUND RESET GROUND


FAULT CHECK

1.0

0.1 2.0 GF MODE POWER


GF TRIP 4.0 A SH
TIME (s) 2.0 A
0.5 A UV ENHANCED
FILTERING

SE-105
GF-GC MONITOR
SW CI GI GC G

F2

Copyright  2015 by Littelfuse Startco

All rights reserved.

Document Number: PM-1300-EN


Printed in Canada.
Page i
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

This page intentionally left blank.


Page ii
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

TABLE OF CONTENTS LIST OF TABLES


SECTION PAGE TABLE PAGE

1 General ................................................................. 1 1 Terminal Designations .......................................... 6


2 Operation ............................................................. 1 2 Ground-Fault-Test Record .................................. 15
2.1 Settings.................................................................. 1
2.1.1 GF Trip Time ............................................. 1
2.1.2 GF .............................................................. 1 DISCLAIMER
2.1.3 Mode .......................................................... 1
2.2 Indication and Reset .............................................. 1
2.3 Fusing.................................................................... 1 Specifications are subject to change without notice.
3 Installation ........................................................... 2 Littelfuse Startco is not liable for contingent or
3.1 SE-105 .................................................................. 2 consequential damages, or for expenses sustained as a
3.2 Ground-Fault CT................................................... 4 result of incorrect application, incorrect adjustment, or a
3.3 Ground-Check Termination .................................. 5 malfunction.
3.4 Remote Operation ................................................. 6
3.5 Parallel-Path Isolation ........................................... 6
3.6 Ground-Fault Testing ............................................ 6
4 Compatibility ....................................................... 6
5 Technical Specifications ................................... 12
5.1 SE-105 ................................................................ 12
5.2 Current Sensors ................................................... 13
5.3 Termination Assemblies ..................................... 13
6 Ordering Information ....................................... 13
7 Warranty ........................................................... 14
8 Ground-Fault Performance Test ..................... 15
Appendix A SE-105 Revision History......................... 16

LIST OF FIGURES
FIGURE PAGE

1 Typical Application .............................................. 3


2 SE-105 Outline and Mounting Details .................. 4
3 CT200 and CT200L Current Transformers .......... 5
4 Zener-Diode Termination Devices........................ 6
5 SE-TA6 Termination Assembly ............................ 7
6 SE-TA6ASF-WL Small-Format Termination
Assembly with Wire Leads ................................... 7
7 RK-102 Remote Indication and Reset Kit ............ 8
8 RK-105 Remote Indication-and-Reset Assembly . 8
9 RK-105I Remote Indication Assembly ................. 9
10 RK-13 Relay Interface Module ............................. 9
11 PPI-600V Parallel-Path Isolator .......................... 10
12 PPI-600V Typical Installation ............................ 11
13 Ground-Fault-Test Circuits ................................. 15
Page iii
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

This page intentionally left blank.


Page 1
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

1. GENERAL invalid or if a ground-fault trip occurs. The shunt-trip


mode is not fail-safe and is not recommended because:
The SE-105 is a combination ground-fault and ground-  Shunt-trip devices do not operate if supply voltage
check monitor for resistance-grounded systems in non- fails.
hazardous applications. The ground-fault circuit is  Shunt-trip ground-check circuits allow open cable
latching and the ground-check circuit is typically non- couplers to be energized for a short interval after
latching. One output contact is provided for contactor supply voltage is applied.
control, or for shunt or undervoltage operation in a In the undervoltage mode (UV), the output relay is
breaker trip circuit. energized and its contact is closed when the ground-check
Ground-fault current is sensed by a CT200-series loop is valid and the ground-fault circuit is not tripped.
current transformer. A trip level of 0.5, 2.0, or 4.0 A is The undervoltage mode is referred to as fail-safe and is
switch selectable for use with a 5-, 15-, or 25-A recommended because:
grounding resistor. Enhanced filtering eliminates false  Undervoltage devices release if supply voltage fails.
ground-fault trips from adjustable-speed-drive harmonic  Undervoltage ground-check circuits do not allow
distortion. Trip time is adjustable from 0.1 to 2.0 cable couplers to be energized until the ground-check
seconds. loop is verified.
The fail-safe ground-check circuit is validated by an For fail-safe-only applications, use an SE-107 Ground-
end-of-line termination with a 5.6-volt Zener Fault Ground-Check Monitor.
characteristic. The Zener-characteristic clamps induced
voltage and allows induced current to flow in the ground- 2.2 INDICATION AND RESET
check loop. Consequently, induced-ac-withstand The blue POWER LED indicates that the internal
capability, noise immunity, and open/short detection are power supply is on. The red GROUND FAULT LED
independent of current in the phase conductors. indicates a ground-fault trip and the green GROUND
Enhanced filtering prevents false ground-check validation CHECK LED indicates a valid ground-check loop. When
due to an active chopper condition. See a ground-fault trip occurs, the SE-105 remains latched
www.littelfuse.com/relayscontrols for Technical Note until the reset button is pressed or the supply voltage is
GC-1. cycled. The ground-check circuit is non-latching and
does not require a reset. Terminals are provided for
NOTE: The SE-105 is not a lock-out device. Follow remote indication and reset as shown in Fig. 1.
lock-out procedures for maintenance. For latching ground-check (Option L), the
GROUND CHECK LED is red and it indicates a latched
ground-check trip.
2. OPERATION
2.1 SETTINGS 2.3 FUSING
2.1.1 GF TRIP TIME The output contact is protected by fuse F1 (4.0 A, time
Ground-fault trip time is adjustable from 0.1 to delay). The ground-check circuit is protected by fuse F2
2.0 seconds. Time-coordinated ground-fault protection (0.5 A, time delay).
requires this setting to be longer than the trip time of
downstream ground-fault devices.

2.1.2 GF
The ground-fault-circuit trip level is 0.5, 2.0, or 4.0 A
when current is sensed with a CT200-series current
transformer. Since the ground-fault-circuit trip level
should not be greater than 20% of the grounding resistor
let-through current, these levels are appropriate for use
with 5-, 15-, or 25-A grounding resistors. For other
applications, the trip level of the ground-fault circuit is
0.25, 1.0, or 2.0% of the primary rating of the 5-A-
secondary current transformer.

2.1.3 MODE
In the shunt-trip mode (SH), the output relay energizes
and its contact closes if the ground-check loop becomes
Page 2
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

3. INSTALLATION
3.1 SE-105
SE-105 outline and mounting details are shown in
Fig. 2. Typical connections are shown in Fig. 1. Connect
supply voltage to L1 and L2. For a 120-Vac supply,
connect supply neutral to L2. For direct-current supply
(Option D), connect supply negative to L2. Connect
chassis-bonding terminal to ground.
Connect contact terminals A and B as required.
Faceplate LED's are driven in series with remote-
indication LED's. When a remote kit is not used,
terminals CI, +, and GI must be connected for the face-
plate LED’s to operate. These jumpers are installed at the
factory.
Connect terminal GC to the outgoing ground-check
conductor and connect terminal G to ground. To meet
electrical code requirements, do not jumper chassis-
bonding terminal to terminal G.
Install the upper terminal-block cover to prevent
inadvertent contact with line terminals.
Page 3
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

CT200
LOAD

GROUND
UV START
STOP
120 VAC GROUND CHECK
GC
L N GC NOTE 1
USE LOW- HOLD-IN
NOTE 1 CONTACT
G
F1 LEVEL
G CONTACTS
GROUND-CHECK ALTERNATE TERMINATION CIRCUIT
CT1 CT2 A B L1 L2 TERMINATION FOR REMOTE CONTACTOR CONTROL

SE-105
GROUND RESET GROUND GF-GC MONITOR
FAULT CHECK
SW CI GI GC G
1.0

0.1 2.0 GF MODE POWER F2


GF TRIP 4.0 A SH
TIME (s) 2.0 A
0.5 A UV ENHANCED
FILTERING

SE-105
GF-GC MONITOR GI GROUND-FAULT
SW CI GI GC G INDICATOR
RED
+

F2 CI GROUND-CHECK
GREEN INDICATOR
SW
RESET SWITCH

REMOTE INDICATION AND RESET

SE-105
GF-GC MONITOR
SW CI GI GC G
SE-105
GF-GC MONITOR
SW CI GI GC G
F2
SW CI/GI + GI/RI

F2
SW CI/GI + GI/RI

TB1 S
W
R
S
R
S K1
C
G +
G
R K2
NOTE 2
1 2 I I

K1 K2 GI GROUND-FAULT
TB1 S
W
R
S
1
R
S
2
K1
C
G
I
+
G
R
I
K2
RED INDICATOR
K1 K2 NOTE 2 +

RK-13 CONNECTION WITHOUT REMOTE INDICATION OR RESET CI GROUND-CHECK


GREEN INDICATOR
NOTES:
SW
RESET SWITCH
1. SEE ORDERING INFORMATION FOR 24-120 Vac/Vdc
TERMINATION DEVICES. 5-W AXIAL
ALTERNATE
LEAD DEVICE INCLUDED. RESET CIRCUIT

2. K1 CLOSES ON GROUND-CHECK VALID. RK-13 CONNECTION WITH REMOTE INDICATION AND RESET
FOR OPTION L, K1 CLOSES ON
GROUND-CHECK TRIP.
K2 CLOSES ON GROUND-FAULT TRIP.

FIGURE 1. Typical Application.


Page 4
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

3.2 GROUND-FAULT CT Connect the secondary of the ground-fault CT to


Outline and mounting details for CT200 and CT200L SE-105 terminals CT1 and CT2. The CT connection to
current transformers are shown in Fig. 3. Pass the phase the SE-105 is not polarity sensitive. Ground one side of
conductors through the CT window as shown in Fig. 1. the CT secondary.
Do not pass the ground or ground-check conductors
through the CT. In applications that require shields or NOTE: The CT200 and CT200L are 600-V-rated current
drain wires to pass through the CT, return them through transformers. When system voltage is above 600 V,
the CT before connecting them to ground. ensure conductors passed through the sensor window are
insulated to system voltage.

NOTE 5

109.0 100.0

(1.71)
43.5
(4.29) (3.93)
88.9 77.8
(3.50) (3.06)

F1

CT1 CT2 A B L1 L2
NOTE 4

GROUND RESET GROUND


FAULT CHECK
(5.50)

(5.90)
150.0
139.7

1.0

0.1 2.0 GF MODE POWER


GF TRIP 4.0 A SH
TIME (s) 2.0 A
0.5 A UV ENHANCED
FILTERING

SE-105
GF-GC MONITOR
SW CI GI GC G

F2

4.8 (0.19) DIA


(1.71)
43.5

NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
NOTE 5
2. TERMINAL-BLOCK SCREWS: 6-32 x 0.25.

3. MOUNTING SCREWS: M4 OR 8-32.


4. SHOWN WITH TERMINAL-BLOCK COVER REMOVED.
5. MINIMUM CLEARANCE FOR FUSE REMOVAL.

FIGURE 2. SE-105 Outline and Mounting Details.


Page 5
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

D 44.5 MAX
(1.75)

NOTES:

1. DIMENSIONS IN MILLIMETRES
(INCHES).

2. MOUNTING SCREWS: M4 OR
8-32.
A X1 X2
E

BLACK

WHITE

FRONT SIDE
B
9.4
(0.37) C

(0.87)
22.2
F

(1.75)
44.5
TAP M4 OR 8-32

BOTTOM MOUNTING DETAIL

PART DIMENSIONS
NUMBER A B C D E F

CT200 55.9 (2.20) 120.7 (4.75) 101.6 (4.00) 98.3 (3.87) 108.0 (4.25) 5.6 (0.22)

CT200L 88.9 (3.50) 154.0 (6.06) 133.4 (5.25) 139.7 (5.50) 144.5 (5.69) 7.1 (0.28)

FIGURE 3. CT200 and CT200L Current Transformers.

3.3 GROUND-CHECK TERMINATION ground-check loop. Connect terminal GC of the


Install the ground-check termination at the load to termination to the incoming ground-check conductor.
complete the ground-check loop as shown in Fig. 1. If ground-check interlocks are used, low-level
Termination outlines and mounting details are shown in (bifurcated, precious-metal, or sealed-reed) contacts are
Figs. 4, 5, and 6. Use only a Littelfuse Startco recommended.
termination device; others may not meet performance If used as a ground-fault monitor only, install the
requirements. Connect terminal G of the termination to termination at the SE-105.
the equipment frame so that the ground-conductor-to-
equipment-frame connection is included in the monitored
Page 6
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

3.4 REMOTE OPERATION 3.6 GROUND-FAULT TESTING


Terminals SW, CI, , and GI are provided for remote Use CT-primary current injection to test the ground-
LED indication and remote reset as shown in Fig. 1. fault circuit. Fig. 13 shows test circuits using the SE-400
Remote LED's are driven in series with the front-panel Ground-Fault-Relay Test Unit and the SE-100T Ground-
LED's. Fault-Relay Tester. The SE-400 has a programmable
Remove factory-installed jumpers from terminals CI, output of 0.5 to 9.9 A for a duration of 0.1 to 9.9
+, and GI, and connect a remote kit as shown in Fig. 1. seconds. The SE-100T has LO and HI outputs for 5- and
Optional remote kits are shown in Figs. 7, 8, and 9. 15-A resistance-grounded systems.
Standard LED indicator lamps are not compatible with A test-record form is provided in Section 8 of this
the SE-105. manual. Record the test results and test dates on this
For general-purpose applications, use the RK-105 form to meet the requirements of the National Electrical
Remote Indication-and-Reset Assembly or the RK-105I Code (NEC). Retain the form so that the test data can be
Remote Indication Assembly. Connect terminals SW, made available to the authority having jurisdiction.
CI, +, and GI to remote-kit terminals SW, CI/RI, +, and
GI.
For 22-mm-component applications, use the RK-102 4. COMPATIBILITY
Remote Indication and Reset Kit. Connect terminal X2 The SE-105 is a direct replacement for the SEL-100,
of the green ground-check indicator to CI, terminal X2 SEL-100TD, SE-101, SE-101S, SE-102, SE-102S, SE-
of the red ground-fault indicator to GI, and connect 102M, SE-103, and SE-103S. Terminal designations
indicator X1 terminals to +. For remote reset, connect have been changed as shown in Table 1.
the normally open push-button switch across terminals + Terminals CT1 and CT2 are transformer isolated so
and SW. that the CT secondary can be grounded. Units with old
If indication is required from a separate voltage designations do not allow the secondary of the ground-
source, or if separate ground-fault and ground-check fault CT to be grounded when the ground-check circuit
contacts are required, use an RK-13 Relay Interface is used.
Module. The RK-13 mounts on the SE-105 lower
terminal block and is compatible with the RK-102, TABLE 1. TERMINAL DESIGNATIONS
RK-105 and RK-105I. See Figs. 1 and 10. Contact K1
OLD SE-105
closes when the GC LED is on and contact K2 closes
DESIGNATION DESIGNATION
when the GF LED is on.
CT CT1
CT CT2
3.5 PARALLEL-PATH ISOLATION (RELAY) A
A PPI-600V can be used for parallel-path rejection. A (RELAY) B
PPI-600V will also eliminate intermachine arcing and L L1
prevent stray ac and dc currents from flowing in the N L2
monitored ground wire. See Figs. 11 and 12. See SW SW
Technical Note GC-10 “Parallel Path Isolator” at PL CI
www.littelfuse.com/relayscontrols, or contact Littelfuse + +
Startco for application details. GL GI
P GC
G G

69.9
(2.75)
G GC
250 (9.84) LENGTH OF # 14 AWG
GC
G

YELLOW STRANDED WIRE


(1.38)
35.0
LOAD.
BE INSTALLED AT
TERMINATION MUST

NOTES:
(0.40)
10.0

0.25” - 28 UNF
1. DIMENSIONS IN MILLIMETRES (INCHES).

1N5339B SE-TA6-SM 2. CAN BE IMMERSED IN GLYCOL.

FIGURE 4. Zener-Diode Termination Devices.


Page 7
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

41.5 40.0
(1.63) (1.57)

(0.31)
8.0
40.0 22.2 10.5 19.0
(1.57) (0.87) (0.41) (0.75)

SE-TA6
TERMINATION
ASSEMBLY
TAP M4
GC OR 8-32

(2.64)
(2.01)

67.0
51.0
(2.64)

G
67.0

4.5 (0.18) Ø, C’BORE 10.0 (0.39) Ø


3.2 (0.13) DEEP
FRONT SIDE MOUNTING DETAIL

NOTES:

1. DIMENSIONS IN MILLIMETRES (INCHES).

2. TERMINAL-BLOCK SCREWS: 6-32 x 0.25.

3. MOUNTING SCREWS: M4 OR 8-32.

4. ENCLOSURE IS ELECTRICALLY CONNECTED


TO TERMINAL G.

5. CAN BE IMMERSED IN GLYCOL.

FIGURE 5. SE-TA6 Termination Assembly.

NOTE 2
(0.50)
12.7

4.0 50.8
(0.13)
3.2

(0.16) (2.00)
MOUNTING DETAIL
SE-TA6ASF-WL TERMINATION ASSY
(0.50)

R
12.7

Rev: 01 Serial No: DE130600619


Rating: 5.6 Vdc @ 105 mA 12 W Max C US
Use with: SE-134, SE-134C, SB6100LR 53428
SIDE
NOTES:
58.8
(2.32)
GC 1. DIMENSIONS IN MILLIMETRES (INCHES).
300 (12) OF
YELLOW WIRE 2. MOUNTING SCREWS M3.5 OR 6-32.
(0.75)
19.0

3. CAN BE IMMERSED IN GLYCOL.


G
300 (12) OF
GREEN/YELLOW WIRE
TOP

FIGURE 6. SE-TA6ASF-WL Small-Format Termination Assembly with Wire Leads.


Page 8
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

30.0
(1.18)
RESET GROUND CHECK GROUND FAULT

(0.98)
25.0
LEGEND
PLATE

(1.71)
NOTE 2

43.5

(0.59)
15.0
(0.89)
22.5
22.2 (0.87) DIA

17.3 36.6 29.9


(0.68) (1.44) (1.17)
LEGEND PLATES NOTES:
LED PILOT LIGHTS
1. DIMENSIONS IN MILLIMETRES
(INCHES).

40.0 MINIMUM
(1.71) 2. ----- INDICATES CLEARANCE
43.5

30.0 MINIMUM

(1.57)
REQUIRED.
(1.18)
3. PANEL THICKNESS 1.0 TO 6.0
(0.04 TO 0.24).
14.9 36.6 29.9
4. NEMA 4X.
(0.59) (1.44) (1.17)
5. CERTIFICATIONS NOT SHOWN.
PUSH BUTTON MOUNTING DETAIL

FIGURE 7. RK-102 Remote Indication and Reset Kit.

30.0
(1.18) 60.0
(2.36)
25.0 7.7 44.5
(0.98) (0.30) (1.75)
(0.40)

OUTLINE
10.0

GROUND CHECK

(1.125)
28.58

CI/RI GROUND FAULT


1.25”
+ CONDUIT
GI KNOCKOUT
1.70” DIA
SW RESET
(3.78)

(3.00)
96.0

76.0

RK-105

3.8 (0.15)
22.25 DIA
(0.875)
SIDE VIEW FRONT VIEW MOUNTING DETAIL
NOTES:

1. DIMENSIONS IN MILLIMETRES (INCHES).

2. NEMA 1.

FIGURE 8. RK-105 Remote Indication-and-Reset Assembly.


Page 9
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

30.0
60.0
(1.18) (2.36)
7.7 44.5
25.0
(0.30) (1.75)
(0.98)

(0.40)
OUTLINE

10.0
GROUND CHECK

(1.125)
28.58
CI/RI GROUND FAULT 1.25”
CONDUIT
+
KNOCKOUT
GI 1.70” DIA
SW

(3.78)

(3.00)
96.0

76.0
RK-105I

3.8 (0.15)
22.25 DIA
(0.875)

SIDE VIEW FRONT VIEW MOUNTING DETAIL


NOTES:

1. DIMENSIONS IN MILLIMETRES (INCHES).

2. NEMA 1.

FIGURE 9. RK-105I Remote Indication Assembly.

SW CI/GI + GI/RI
(1.87)
47.5
(1.22)
31.0

TB1 S R R C G
S S G + R
W 1 2 K1 I I K2

SIDE VIEW
60.2 RK-13 SHOWN MOUNTED ON SE-105/SE-107/SE-325
(2.37)

INSTALLATION INSTRUCTIONS:
S R R C G
S S G + R
W 1 2 K1 I I K2
1. REMOVE FOUR LEFTMOST LOWER TERMINAL BLOCK SCREWS.
(0.83)
21.0

2. PLACE RK-13 ON TERMINAL BLOCK AND REPLACE SCREWS.


3. MAKE REQUIRED CONNECTIONS TO TERMINAL BLOCK TB1.

NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. CERTIFICATIONS NOT SHOWN.

FIGURE 10. RK-13 Relay Interface Module.


Page 10
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

9.5 DIA.
(0.38 DIA.)

(0.75) (0.50)
12.7
19.1

(2.50)
63.5
(0.75)
19.1
8-32 TAP

260.4
(10.25)
34.9 190.5 34.9
(1.38) (7.50) (1.38)
152.4
(6.00)

(1.50)
38.1

(4.03)
(1.03)
102.4
26.2
(1.50)
38.1

235.0
(9.25)

NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).

FIGURE 11. PPI-600V Parallel-Path Isolator.


Page 11
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

GROUND CHECK MONITOR


SE-105, SE-107, SE-134C, OR SE-135

CABLE GROUND
GROUND CHECK
G GC

GC OUTGOING
GROUND CHECK

G OUTGOING
GROUND

INCOMING
GROUND

CHASSIS GROUND BUS PPI-600V

NOTES:

1. THE PARALLEL-PATH ISOLATOR IS NOT POLARIZED. EITHER FLANGE CAN BE


CONNECTED TO CHASSIS.

2. THE OUTGOING GROUND MUST BE ISOLATED FROM THE CHASSIS GROUND BUS.
IF A FLANGE-MOUNTED RECEPTACLE IS USED, VERIFY THAT THE FLANGE IS ISOLATED
FROM THE GROUND PIN, AND

- USE A MATING PLUG WITH A NON-METALLIC HOUSING, OR

- ISOLATE THE FLANGE FROM THE CHASSIS IF THE MATING PLUG HAS A
METALLIC HOUSING.

3. CABLE PLUGS AND RECEPTACLES WITH GROUNDED METAL HOUSING MUST BE


ISOLATED FROM GROUND TO PREVENT PARALLEL GROUND PATHS.

4. FOR SYSTEMS ABOVE 600 VAC, CONNECT A V131DA40 MOV ACROSS THE PPI-600V.

FIGURE 12. PPI-600V Typical Installation.


Page 12
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

5. TECHNICAL SPECIFICATIONS Trip Time............................ 0.2 s (GC open),


0.5 s (GC to G short)
5.1 SE-105 Trip-Time Accuracy ........... +10, -30%
GC-Loop
Supply:
Trip Resistance(3) ................ 40 ± 10 
ac ............................................10 VA, 120 or 240 Vac Trip Mode........................... Non-Latching,
(+10, -45%), 50/60 Hz Latching with Option L
ac/dc .......................................5 W, 120 Vdc (+40, -8%);
10 VA, 120 Vac Output Relay:
(+10, -45%), 50/60 Hz CSA/UL Contact Ratings ... 1 mA to 4 A Resistive,
240 Vac or 28 Vdc
NOTE: Voltage between supply terminals (L1, L2) and
ground terminal (G) must not exceed 300 Vac continuous Supplemental Contact Ratings:
or 1,250 Vac under transient conditions. Make/carry 0.2 s .............. 10 A
Carry continuous ............. 4 A
Dimensions: Break:
Height ................................. 150 mm (5.9”) dc .................................. 20 W Resistive,
Width .................................. 109 mm (4.3”) 10 W Inductive
Depth .................................. 100 mm (4.0”) (L/R=0.04 s)
ac................................... 960 VA Resistive,
Shipping Weight....................... 1 kg (2.2 lb) 700 VA Inductive
(PF=0.4)
Environment: Subject to maximums of 4 A and 240 V (ac or dc)
Operating Temperature ....... -40 to 60°C (-40 to 140°F) Contact Configuration ........ N.O. (Form A)
Storage Temperature........... -55 to 80°C (-67 to 176°F) Fuse Rating (F1) ................. 4.0 A, 250 Vac,
Humidity ............................. 85% Non-Condensing Time Delay
Fuse Part Number ............... Littelfuse 313004. or
Ground-Fault Circuit:
CT Ratio ............................. 200:5 Bussman MSL-4
CT Input Burden ................. 0.02  Operating Mode.................. UV (Undervoltage/Fail-
Trip Level (1) ....................... 0.5, 2.0, or 4.0 A Safe) or SH (Shunt
Frequency Response ........... 25 to 110 Hz Trip/Non-Fail-Safe)
Trip Time ............................ 0.1 to 2.0 s
Thermal Withstand (1) ......... 200 A Continuous, Remote Indication:
2,500 A for 2 s .......................................... 12 Vdc
Trip-Level Accuracy........... +10, -20% GI/CI .................................. Current Sink,
CT Lead Resistance Limit (2) 560  Internal
0.5 A Trip Level......... 2 
2 A Trip Level............ 5  Optional RK-13 Module:
4 A Trip Level............ 5  Contact Ratings .................. 0.08 A, 120 V (ac or dc)
Trip-Time Accuracy ........... 10% 0.50 A, 24 Vdc
Trip Mode ........................... Latching Contact Configuration ........ N.O. (Form A)
Reset Input ......................... 24 to 120 V (ac or dc),
Ground-Check Circuit: Isolated
Open-Circuit Voltage ......... 12 Vdc
Output Impedance............... 240  PWB Conformal Coating............ MIL-1-46058 qualified,
Nominal Loop Current........ 25 mA
UL QMJU2 recognized
Induced-ac Withstand ......... 25 Vac Continuous,
120 Vac for 3 s
Fuse Rating (F2) ................. 0.5 A, 250 Vac,
Time Delay
Fuse Part Number ............... Littelfuse 313.500 or
Bussman MDA-1/2,
MDL-1/2
Pull-in Filter........................ Chopper Rejection
Pull-in Time ........................ 1.5 s
Page 13
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

Certification.............................. CSA, Canada and USA Dimensions ............................ 67 x 40 x 41.5 mm


(2.6 x 1.6 x 1.6”)
R LR 53428
C US
Shipping Weight ................... 200 g (0.45 lb)
UL Listed SE-TA6ASF-WL:
Characteristic ...................... 6-V Zener, Temperature
Compensated
Australia(4) Circuit Type........................ High-Current Shunt
Regulator
Reverse Voltage ................. 5.6 ±0.03 Vdc @ 100 mA
N11659 Forward Voltage................. 0.5 ±0.1 Vdc @ 100 mA
FCC Operating Temperature....... -40 to 60°C (-40 to 140°F)
Current Range .................... 2 mA to 15 A
Maximum Clamping
Voltage ............................... 55 V @ 250 A,
NOTES: 5x20 µs Pulse
(1)
Currents referred to primary of CT200 for prospective Power Rating ...................... 12 W
ground-fault currents less than 4,000 A. Wire Leads ......................... 18 AWG (0.82 mm2),
(2)
Typical maximum CT lead resistance to meet 300 mm (11.8”)
specified trip-level accuracy. Dimensions ......................... 58.8 x 19 x 12.7 mm
(3)
The GROUND CHECK LED may flash when the (2.32 x 0.75 x 0.5”)
GC-loop trip resistance is near the trip level. Shipping Weight................. 45 g (0.1 lb)
(4)
Applicable only on 240 Vac Supply (Option E in the
ordering information). SE-TA6-SM:
Characteristic ...................... Zener Diode,
5.2 CURRENT SENSORS Unidirectional
Circuit Type........................... High Current Shunt
Environment:
Regulator
Operating Temperature ....... -40 to 60°C (-40 to 140°F)
Reverse Voltage .................... 5.6 ± 0.3 Vdc @ 25 mA
Storage Temperature........... -55 to 80°C (-67 to 176°F)
Forward Voltage ................... 0.65 ± 0.1 Vdc @ 25 mA
Humidity ............................. 85% Non-Condensing
Operating Temperature ......... -40 to 60°C (-40 to 140°F)
Power Rating ......................... 50 W
CT200: Screw Terminal ..................... 0.25” – 28 UNF
Current Ratio ...................... 200:5 A Dimensions:
Insulation ...............................600-V Class Body ................................ 45 mm
Window Diameter .................56 mm (2.2”) Wire Lead ........................ 250 mm (9.84”)
Shipping Weight ....................1 kg (2.2 lb) 14 AWG (2.08 mm2)
Shipping Weight ................... 45 g (0.1 lb)
CT200L:
Current Ratio ...................... 200:5 A
Insulation ...............................600-V Class 6. ORDERING INFORMATION
Window Diameter .................89 mm (3.5”)
Shipping Weight ....................1 kg (2.2 lb) Option List (1)
SE-105
5.3 TERMINATION ASSEMBLIES
120-Vac Supply (2) L Latching Ground-Check Trip
SE-TA6: E 240-Vac Supply (3)
Characteristic ...................... Zener Diode, D 120-Vac/dc Supply
Unidirectional Each SE-105 is supplied with a 1N5339B termination device.
Circuit Type ...........................High Current Shunt (1)
List options required in order shown above.
Regulator (2)
Standard, leave blank.
Reverse Voltage.....................5.6 ± 0.3 Vdc @ 25 mA (3)
Only Supply option available with C-Tick
Forward Voltage ....................0.65 ± 0.1 Vdc @ 25 mA certification.

Operating Temperature .........-40 to 60°C (-40 to 140°F) Ground-Fault CT’s:


Power Rating .........................50 W CT200 ............................... 56 mm (2.2”) window
Screw Terminal .....................6-32 x 0.25”
CT200L ............................. 89 mm (3.5”) window
Page 14
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

Ground-Check Termination:
1N5339B ............................ 5-W Axial Lead
Termination Device
SE-TA6 ............................... 50-W Termination
Assembly
SE-TA6-SM ........................ 50-W Stud-Mount
Termination Assembly
SE-TA6ASF-WL ................ 12-W Small-Format
Termination Assembly
with Wire Leads

Remote Indication and Reset:


RK-102 ............................... Includes two LED pilot
lights, a reset push button,
and legend plates
RK-105 ............................... Indication-and-Reset
Assembly
RK-105I .............................. Indication Assembly
RK-13 ................................. Relay Interface Module

Parallel-Path Isolator:
PPI-600V ............................ For system voltages up to
600 Vac
7. WARRANTY
The SE-105 Ground-Fault Ground-Check Monitor is
warranted to be free from defects in material and
workmanship for a period of five years from the date of
purchase.
Littelfuse Startco will (at Littelfuse Startco’s option)
repair, replace, or refund the original purchase price of an
SE-105 that is determined by Littelfuse Startco to be
defective if it is returned to the factory, freight prepaid,
within the warranty period. This warranty does not apply
to repairs required as a result of misuse, negligence, an
accident, improper installation, tampering, or insufficient
care. Littelfuse Startco does not warrant products
repaired or modified by non-Littelfuse Startco personnel.
Page 15
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

8. GROUND-FAULT PERFORMANCE TEST


a) USING SE-400 CT200

To meet the requirements of the National Electrical FROM


POWER LOAD
Code (NEC), as applicable, the overall ground-fault- SOURCE
protection system requires a performance test when first
installed. A written record of the performance test is to
be retained by those in charge of the electrical installation CT1 CT2
L L1
in order to make it available to the authority having N L2
SE-105
jurisdiction. A test record form is provided for recording
11 12
the date and the final results of the performance tests. 3
OP1 OP2

L L1
The following ground-fault system tests are to be N
5
L2
conducted by qualified personnel: 1 SE-400

a) Evaluate the interconnected system in accordance with REMOTE


8
RMT1
TEST
the overall equipment manufacturer’s detailed 9
RMT2

instructions. b) USING SE-100T


CT200

b) Verify proper location of the ground-fault current FROM


POWER LOAD
transformer. Ensure the cable or bus passes through SOURCE
the ground-fault current transformer window, and that
the grounding conductors or shields are not
encompassed by the ground-fault current transformer CT1 CT2
L L1
in such a way as to cause ground-fault current to be N L2
SE-105
missed. These checks can be done visually with
0.65 A
knowledge of the circuit involved. The connection of C LO
2.75 A
L L1 HI
the current-transformer secondary to the SE-105 is not REMOTE
N L2
polarity sensitive. TEST
SE-100T

RMT
c) Verify that the system is correctly grounded and that
alternate ground paths do not exist that bypass the
current transformer. High-voltage testers and FIGURE 13. Ground-Fault-Test Circuits.
resistance bridges can be used to determine the
existence of alternate ground paths. TABLE 2. GROUND-FAULT-TEST RECORD
d) Verify proper reaction of the circuit-interrupting DATE TEST RESULTS
device in response to a simulated or controlled
ground-fault current. To simulate ground-fault
current, use CT-primary current injection. Fig. 13a
shows a test circuit using an SE-400 Ground-Fault-
Relay Test Unit. The SE-400 has a programmable
output of 0.5 to 9.9 A for a duration of 0.1 to 9.9
seconds. Set the test current to 0.6, 2.3, or 4.6 A for
SE-105 units set at 0.5, 2.0, or 4.0 A respectively.
Fig. 13b shows a test circuit using an SE-100T
Ground-Fault-Relay Tester. The SE-100T provides a
test current of 0.65 or 2.75 A for testing 0.5- and 2.0-
A trip levels. Inject the test current through the
current-transformer window for at least 2.5 seconds.
Verify that the circuit under test has reacted properly.
Correct any problems and re-test until the proper
reaction is verified.
e) Record the date and the results of the test on the
attached test-record form.

Retain this record for the authority having jurisdiction.


Page 16
SE-105 Ground-Fault Ground-Check Monitor Rev. 13-D-050315

APPENDIX A
SE-105 REVISION HISTORY
MANUAL MANUAL PRODUCT REVISION
RELEASE DATE REVISION (REVISION NUMBER ON PRODUCT LABEL)
May 3, 2015 13-D-050315
13
April 29, 2015 13-C-042915
September 8, 2014 13-B-090814
12
July 4, 2013 13-A-070413

MANUAL REVISION HISTORY


REVISION 13-D-050315
SECTION 5
FCC certification added.
Updated Fuse F1 part number.
Sections 5.2 and 5.3 added.
APPENDIX A
Revision history updated.
REVISION 13-C-042915
SECTION 5
Updated Fuse F1 part number.
APPENDIX A
Revision history updated.
REVISION 13-B-090814
SECTION 3
Updated Figure 1.
SECTION 4
Updated Figures 5, 6, 8, and 9.
SECTION 5
Updated RK-13 contact ratings.
Updated notes.
APPENDIX A
Revision history updated.
REVISION 13-A-070413
SECTION 3
Updated Figure 1.
SECTION 4
Updated Figure 7.
APPENDIX A
Revision history added.

PRODUCT REVISION HISTORY


REVISION 13
Minor hardware change.
REVISION 12
No change.

Вам также может понравиться