DATOS GENERALES
DATOS DEL GENERADOR TRANSFORMADORES DE CORRIENTE (TERMINAL)
TRANSFORMADORES DE CORRIENTE (NEUTRO) TRANSFORMADOR DE TENSION
RELACIONES DE IMPEDANCIA
VALORES DE AJUSTE
@ AJUSTES GENERALES 87N Restricted earth fault protection (PDIF)
87G Generator differential protection (PDIF) 21 Full-scheme distance measuring, Mho characteristic, PDIS (Impedance Protection)
RDIR Directional impedance Mho 78 Pole slip protection (PPAM).(PERDIDA DE SINCRONISMO)
40 Loss of excitation (PDIS). (PERDIDA DE EXCITACIÓN) 50 INSTANTANEOUS PHASE OVERCURRENT PROTECTION (PIOC)
51_67 Four step phase overcurrent protection (PTOC) 50N INSTANTANEOUS RESIDUAL OVERCURRENT PROTECTION (PIOC)
51N/67NFour step residual overcurrent protection (PTOC) 67N Sensitive directional residual overcurrent and power protection (PSDE)
49 Thermal overload protection, two time constants (PTTR) 50BF Breaker failure protection (RBRF)
DATOS GENERALES
Características nominales
Tipo (CH=Hidráulica, D=Diesel, TV=Turb.Vapor, TG=Turb.Gas, etc.) - CH
Potencia activa nominal MW 9.18
Potencia aparente nominal MVA 10.8
Factor de potencia nominal - 0.85
Potencia activa máxima MW
Potencia activa mínima MW
Potencia reactiva máxima MVAr
Potencia reactiva mínima MVAr
Tensión nominal primaria entre fases kV 5.25
Rango de tensión entre fases %
Velocidad de rotación rpm
Frecuencia Hz 0
Características operativas
Reactancia de secuencia positiva, subtransitoria, no saturada. pu 0.180
Reactancia de secuencia negativa, no saturada. pu 0.201
Reactancia de secuencia cero. pu 0.120
Resistencia estatórica. ohm/fase
Resistencia estatórica. ohm/fase
380201555.xls 02/28/2018 1 de 3
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: PROTECCION GENERADOR Tipo Central: HIDROELECTRICA Región: ZONA SUR
Fabricante: ABB C.H.: CHARCANI VI Dpto:
Modelo: REG670 Tensión Nom.: 5,25 kV Empresa:
Versión: Grupo Gen.: G1 Diag.Unif.N°:
N° Serie: Uprim[kV]: 5,25kV Man.Serv.N°:
Tecnología: NUMÉRICA Fases: RSTN Fecha: 13-Feb-14
Año instal.: Ucc [V]: Respons.: K.V.H.
Código: Uca [V]: 100 Revisión: 0
Ubic.Tabl: Ica [A]: 5
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 (AS BUILT) GRUPO 1 (AECP 2014) OBSERVACIONES
ACTUAL PROPUESTO
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO
I1> Phase current operate level for step1 in % of IBase %IB 1 2500 1 98 103 1287.50
t1 Definitive time delay of step 1 s 0.00 60.00 0.001 0.050 - 0.050 -
TD1 Time multiplier for the inverse time delay for step 1 - 0.05 999.00 0.01 1.10 - 1.10 -
t1Min Minimum operate time for inverse curves for step 1 s 0.00 60.00 0.001 0 - 0 -
MultPU1 Multiplier for current operate level for step 1 - 1.00 10.00 0.1 2.0 - 2.0 -
Selection of reset curve - Instantaneous - - - -
ResetTypeCrv1 type for step 1 IEC Reset
ANSI reset
tReset1 Reset time delay used in IEC Definite Time curve step 1 S 0.0 60.0 0.001 - - - -
tPCrv1 Parameter P for customer programmable curve for step 1 - 0.005 3.0 0.001 - - - -
tACrv1 Parameter A for customer programmable curve for step 1 - 0.005 200.0 0.001 - - - -
tBCrv1 Parameter B for customer programmable curve for step 1 - 0.10 10.0 0.01 - - - -
tCCrv1 Parameter C for customer programmable curve for step 1 - 0.005 3.0 0.10 - - - -
tPRCrv1 Parameter PR for customer programmable curve for step 1 - 0.005 100.0 0.001 - - - -
tTRCrv1 Parameter TR for customer programmable curve for step 1 - 0.10 10.0 0.001 - - - -
tCRCrv1 Parameter CR for customer programmable curve for step 1 - 0.10 10.0 0.10 - - - -
- Disabled - - - -
HarmRestrain1 Enable block of step 1 from harmonic restrain
Enabled
Step 2
DirModeSel2 - Disabled - -
Directional mode of step 2 Non-directional Non-
Forward Non-directional
(Disabled, Nondir, Forward, Reverse) directional
Reverse
Characterist2 - ANSI E. inv., V. inv., N. inv., - -
ANSI Mod. inv., Def. Time,
L.T.E. inv, V. inv., inv.,
Selection of time delay IEC Def
IEC N. inv., V. inv., inv., E. inv., IEC Def Time
curve type for step 2 Time
IEC S.T. inv., L.T. inv., Def. Time,
Reserved, Programmable,
RI type, RD type.
I2> Phase current operate level for step2 in % of IBase %IB 1 2500 1 392 - 392 -
t2 Definitive time delay of step 2 s 0.00 60.00 0.001 0.10 - 0.10 -
TD2 Time multiplier for the inverse time delay for step 2 - 0.05 999.00 0.01 0.05 - 0.05 -
t2Min Multiplier for current operate level for step 2 s 1.00 10.00 0.1 2.0 - 2.0 -
MultPU2 Minimum operate time for inverse curves for step 2 - 0.00 60.00 0.001 0.000 - 0.000 -
Selection of reset curve - Instantaneous - -
ResetTypeCrv2 type for step 2 IEC Reset
ANSI reset
tReset2 Reset time delay used in IEC Definite Time curve step 2 S 0.0 60.0 0.001 - -
tPCrv2 (tReset2)
Parameter P for customer programmable curve for step 2 - 0.005 3.0 0.001 - -
tACrv2 Parameter A for customer programmable curve for step 2 - 0.005 200.0 0.001 - -
tBCrv2 Parameter B for customer programmable curve for step 2 - 0.10 10.0 0.01 - -
tCCrv2 Parameter C for customer programmable curve for step 2 - 0.005 3.0 0.10 - -
tPRCrv2 Parameter PR for customer programmable curve for step 2 - 0.005 100.0 0.001 - -
tTRCrv2 Parameter TR for customer programmable curve for step 2 - 0.10 10.0 0.001 - -
tCRCrv2 Parameter CR for customer programmable curve for step 2 - 0.10 10.0 0.10 - -
- Disabled - -
HarmRestrain2 Enable block of step 2 from harmonic restrain
Enabled
Step 3
DirModeSel3 - Disabled - -
Directional mode of step 3 Non-directional
OFF OFF
(Disabled, Nondir, Forward, Reverse) Forward
Reverse
Characterist3 - ANSI E. inv., V. inv., N. inv., - -
ANSI Mod. inv., Def. Time,
Selection of time delay
curve type for step 3 L.T.E. inv, V. inv., inv.,
IEC N. inv., V. inv., inv., E. inv.,
IEC S.T. inv., L.T. inv., Def. Time,
Characterist4 - ANSI: E. inv., V. inv., N. inv., - -
Selection of time delay ANSI: Mod. inv., Def. Time,
curve type for step 4 L.T.: E. inv, V. inv., inv.,
IEC: N. inv., V. inv., inv., E. inv.,
I4> Phase current operate level for step4 in % of IBase %IB 1 2500 1 - -
t4 Definitive time delay of step 4 s 0.00 60.00 0.001 - -
TD4 Time multiplier for the inverse time delay for step 4 - 0.05 999.00 0.01 - -
t4Min Minimum operate time for inverse curves for step 4 s 0.00 60.00 0.001 - -
tPRCrv2 Parameter PR for customer programmable curve for step 2 - 0.005 100.0 0.001 - -
tTRCrv2 Parameter TR for customer programmable curve for step 2 - 0.10 10.0 0.001 - -
tCRCrv2 Parameter CR for customer programmable curve for step 2 - 0.10 10.0 0.10 - -
TimeChar - L.T.: E. inv, V. inv., inv., - -
IEC: N. inv., V. inv., inv., E. inv.,
IEC: S.T. inv., L.T. inv., Def. Time,
Reserved, Programmable,
RI type, RD type.
t_MinTripDelay Minimum operate time for IEC IDMT curves, in sec s 0.000 60.000 0.001 - -
TDIN IDMT time mult for non-dir res over current protection - 0.00 2.00 0.01 - -
OpVN Operation of non- directional residual overvoltage protection - Disabled
- -
Enabled
VN_PU Set level for non- directional residual over voltage, in %Vb %VB 1.00 200.00 0.01 - -
tVNNonDir Time delay for non-directional residual over voltage, in sec s 0.000 60.000 0.001 - -
INRelPU Residual release current for all directional modes, in %Ib %IB 0.25 200.00 0.01 - -
VNRelPU Residual release voltage for all direction modes, in %Vb %VB 0.01 200.00 0.01 - -
RotResV Setting for rotating polarizing quantity if deg 0 180 1 - -
tReset Time delay used for reset necessary
of definite timers, in sec s 0.000 60.000 0.001 - -
tPCrv Setting P for customer programmable curve - 0.005 3.000 0.001 - -
tACrv Setting A for customer programmable curve - 0.005 200.000 0.001 - -
tBCrv Setting B for customer programmable curve - 0.00 20.00 0.01 - -
tCCrv Setting C for customer programmable curve - 0.1 10.0 0.1 - -
ResetTypeCrv Reset mode when current drops off. (ResetTypeCrv) - Immediate
IEC Reset - -
ANSI reset
tPRCrv Setting PR for customer programmable curve - 0.005 3.000 0.001 - -
tTRCrv Setting TR for customer programmable curve - 0.005 100.000 0.001 - -
tCRCrv Setting CR for customer programmable curve - 0.1 10.0 0.01 - -
49 Thermal overload protection, two time constants (PTTR)
Disabled
Operation Disable/Enable Operation - OFF - OFF -
Enabled
ThetaInit Initial Heat content, in % of heat content trip value % 0.0 95.0 1.0 - -
Warning Time setting, below which warning would be set Min 1.0 500.0 0.1 - -
tPulse Length of the pulse for trip signal (in msec). s 0.01 0.30 0.01 - -
RetripMode
Operation mode of re-trip logic - -
VBase Voltage-Reference (primary voltage kV) KV 0.05 2000.00 0.05 - 5.25 - 5.25
Step 1
OperationStep1 Enable execution of step 1 - Off / On ON - ON -
Characterist1 Definite time
Inverse curve A
Definite
Selection of time delay curve type for step 1 - Inverse curve B Definite time - -
time
Prog. inv. curve
OpMode1 1 out of 3
Number of phases required for op (1 of 3, 2 of 3, 3 of 3) from step
- 2 out of 3 3 out of 3 - 3 out of 3 -
1 3 out of 3
Pickup1 (U1<) Voltage pickup value (Definite-Time & Inverse-Time curve) in % %UB 1 100 1 70.00 - 70.00 -
of VBase, step 1
t1 Definitive time delay of step 1 s 0.00 6000.00 0.01 3.00 - 3.00 -
tReset1 Reset time delay used in IEC Definite Time curve step 1 s 0.000 60.000 0.001 - -
t1Min Minimum operate time for inverse curves for step 1 s 0.000 60.000 0.001 5.00 - 5.00 -
Instantaneous
Frozen timer
ResetTypeCrv1 Selection of reset curve type for step 1 - - -
Linearly
decreased
tIReset1 Time delay in Inverse- Time reset (s), step 1 s 0.000 60.000 0.001 - -
TD1 (K1) Time multiplier for the inverse time delay for step 1 - 0.05 1.10 0.01 0.05 - 0.05 -
ACrv1 Parameter A for customer programmable curve for step 1 - 1.000 200.000 0.001 - -
BCrv1 Parameter B for customer programmable curve for step 1 - 1.00 100.00 0.01 - -
CCrv1 Parameter C for customer programmable curve for step 1 - 0.0 1.0 0.1 - -
DCrv1 Parameter D for customer programmable curve for step 1 - 0.000 60.000 0.001 - -
PCrv1 Parameter P for customer programmable curve for step 1 - 1.000 3.000 0.001 - -
CrvSat1 Tuning param for prog. under voltage Inverse- Time curve, step % 0 100 1 - -
1 Off
IntBlkSel1 Internal (low level) blocking mode, step 1 - Block of trip off - off -
Block all
IntBlkStVal1 Voltage setting for internal blocking in % of VBase, step 1 %UB 1 100 1 20.00 - 20.00 -
tBlkUV1 Time delay of internal (low level) blocking for step 1 s 0.000 60.000 0.001 0.00 - 0.00 -
HystAbs1 Absolute hysteresis in % of VBase, step 1 %UB 0.00 100.00 0.01 0.50 - 0.50 -
Step 2
OperationStep2 Enable execution of step 2 - Off / On OFF - OFF -
VBase Voltage-Reference (primary voltage kV) (VBase) KV 0.05 2000.00 0.05 5.25 5.25
Step 1
Disabled
OperationStep1 Enable execution of step 1 - ON - ON -
Enabled
Characterist1 Definite time
Inverse curve A
Selection of time delay curve type for step 1 - Inverse curve B Definite time - Definite -
time
Inverse curve C
Prog. inv. Curve
OpMode1 1 out of 3
Number of phases required for op (1 of 3, 2 of 3, 3 of 3) from step
- 2 out of 3 3 out of 3 - 3 out of 3 -
1
3 out of 3
Pickup1 (U1>) Voltage pickup value (Definite-Time & Inverse-Time curve) in % %VB 1 200 1 130.00 130.00
of VBase, step 1
t1 Definitive time delay of step 1 s 0.00 6000.00 0.01 0.10 - 0.10 -
tReset1 Reset time delay used in IEC Definite Time curve step s 0.000 60.000 0.001 - -
t1Min Minimum operate time for inverse curves for step 1 s 0.000 60.000 0.001 5.00 - 5.00 -
Instantaneous
Frozen timer
ResetTypeCrv1 Selection of reset curve type for step 1 - - -
Linearly
decreased
tIReset1 Time delay in Inverse- Time reset (s), step 1 s 0.000 60.000 0.001 - -
TD1 (K1) Time multiplier for the inverse time delay for step 1 - 0.05 1.10 0.01 0.05 - 0.05 -
ACrv1 Parameter A for customer programmable curve for step 1 - 1.000 200.000 0.001 - -
BCrv1 Parameter B for customer programmable curve for step 1 - 1.00 100.00 0.01 - -
CCrv1 Parameter C for customer programmable curve for step 1 - 0.0 1.0 0.1 - -
DCrv1 Parameter D for customer programmable curve for step 1 - 0.000 60.000 0.001 - -
PCrv1 Parameter P for customer programmable curve for step 1 - 1.000 3.000 0.001 - -
CrvSat1 Tuning param for prog. under voltage Inverse- Time curve, step % 0 100 1 - -
HystAbs1 1
Absolute hysteresis in % of VBase, step 1 %VB 0.00 100.00 0.01 0.5 - 0.5 -
Step 2
Disabled
OperationStep2 Enable execution of step 2 - Disabled - Disabled -
Enabled
Characterist2 Definite time
Inverse curve A
Selection of time delay curve type for step 2 - Inverse curve B - -
Inverse curve C
Prog. inv. Curve
OpMode2 1 out of 3
Number of phases required for op (1 of 3, 2 of 3, 3 of 3) from step
- 2 out of 3 - -
2
3 out of 3
Pickup2 (U2>) Voltage pickup value (Definite-Time & Inverse-Time curve) in % %VB 1 200 1 - -
of VBase, step 2
t2 Definitive time delay of step 2 s 0.000 60.000 0.001 - -
tReset2 Reset time delay used in IEC Definite Time curve step 2 s 0.000 60.000 0.001 - -
t2Min Minimum operate time for inverse curves for step 2 s 0.000 60.000 0.001 - -
380201555.xls 02/28/2018 2 de 3
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: PROTECCION GENERADOR Tipo Central: HIDROELECTRICA Región: ZONA SUR
Fabricante: ABB C.H.: CHARCANI VI Dpto:
Modelo: REG670 Tensión Nom.: 5,25 kV Empresa:
Versión: Grupo Gen.: G1 Diag.Unif.N°:
N° Serie: Uprim[kV]: 5,25kV Man.Serv.N°:
Tecnología: NUMÉRICA Fases: RSTN Fecha: 13-Feb-14
Año instal.: Ucc [V]: Respons.: K.V.H.
Código: Uca [V]: 100 Revisión: 0
Ubic.Tabl: Ica [A]: 5
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 (AS BUILT) GRUPO 1 (AECP 2014) OBSERVACIONES
ACTUAL PROPUESTO
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO
Instantaneous
Frozen timer
ResetTypeCrv2 Selection of reset curve type for step 2 - - -
Linearly
decreased
tIReset2 Time delay in Inverse-Time reset (s), step 2 s 0.000 60.000 0.001 - -
TD2 (K2) Time multiplier for the inverse time delay for step 2 - 0.05 1.10 0.01 - -
ACrv2 Parameter A for customer programmable curve for step 2 - 1.000 200.000 0.001 - -
BCrv2 Parameter B for customer programmable curve for step 2 - 1.00 100.00 0.01 - -
CCrv2 Parameter C for customer programmable curve for step 2 - 0.0 1.0 0.1 - -
DCrv2 Parameter D for customer programmable curve for step 2 - 0.000 60.000 0.001 - -
PCrv2 Parameter P for customer programmable curve for step 2 - 1.000 3.000 0.001 - -
CrvSat2 Tuning param for prog. under voltage Inverse- Time curve, step % 0 100 1 - -
HystAbs2 2Absolute hysteresis in % of VBase, step 2 %VB 0.0 100.0 0.1 - -
59N Two step residual overvoltage protection (PTOV)
Disabled
Operation Disable/Enable Operation - ON - ON -
Enabled
Vbase Voltage-Reference (primary voltage kV) KV 0.05 2000.00 0.05 - 5.25 - 5.25
Step 1
Disabled
OperationStep1 Enable execution of step 1 - ON - ON -
Enabled
Characterist1 Definite time
Inverse curve A
Selection of time delay curve type for step 1 - Inverse curve B Definite time - Definite -
time
Inverse curve C
Prog. inv. Curve
OpMode1 1 out of 3
Number of phases required for op (1 of 3, 2 of 3, 3 of 3) from step
- 2 out of 3 - -
1
3 out of 3
Pickup1 (U1>) Voltage pickup value (Definite-Time & Inverse-Time curve) in % %VB 1 200 1 9.00 9.00
- -
of VBase, step 1
t1 Definitive time delay of step 1 s 0.00 6000.00 0.01 1.00 - 1.00 -
tReset1 Reset time delay used in IEC Definite Time curve step 1 s 0.000 60.000 0.001 - -
t1Min Minimum operate time for inverse curves for step 1 s 0.000 60.000 0.001 5.00 - 5.00 -
Instantaneous
Frozen timer
ResetTypeCrv1 Selection of reset curve type for step 1 - - -
Linearly
decreased
tIReset1 Time delay in Inverse- Time reset (s), step 1 s 0.000 60.000 0.001 - -
TD1 (K1) Time multiplier for the inverse time delay for step 1 - 0.05 1.10 0.01 0.05 - 0.05 -
ACrv1 Parameter A for customer programmable curve for step 1 - 1.000 200.000 0.001 - -
BCrv1 Parameter B for customer programmable curve for step 1 - 1.00 100.00 0.01 - -
CCrv1 Parameter C for customer programmable curve for step 1 - 0.0 1.0 0.1 - -
DCrv1 Parameter D for customer programmable curve for step 1 - 0.000 60.000 0.001 - -
PCrv1 Parameter P for customer programmable curve for step 1 - 1.000 3.000 0.001 - -
CrvSat1 Tuning param for prog. under voltage Inverse- Time curve, step % 0 100 1 - -
HystAbs1 1
Absolute hysteresis in % of VBase, step 1 %VB 0.00 100.00 0.01 0.50 - 0.50 -
Step 2
Disabled
OperationStep2 Enable execution of step 2 - OFF - OFF -
Enabled
Characterist2 Definite time
Inverse curve A
Selection of time delay curve type for step 2 - Inverse curve B - -
Inverse curve C
Prog. inv. Curve
OpMode2 1 out of 3
Number of phases required for op (1 of 3, 2 of 3, 3 of 3) from step
- 2 out of 3 - -
2
3 out of 3
Pickup2 (U2<) Voltage pickup value (Definite-Time & Inverse-Time curve) in % %VB 1 100 1
- -
of VBase, step 2
t2 Definitive time delay of step 2 s 0.000 60.000 0.001 - -
t2Min Minimum operate time for inverse curves for step 2 s 0.000 60.000 0.001 - -
TD2 (K2) Time multiplier for the inverse time delay for step 2 - 0.05 1.10 0.01 - -
tReset2 Reset time delay used in IEC Definite Time curve step 2 s 0.000 60.000 0.001 - -
Instantaneous
Frozen timer
ResetTypeCrv2 Selection of reset curve type for step 2 - - -
Linearly
decreased
tIReset2 Time delay in Inverse-Time reset (s), step 2 s 0.000 60.000 0.001 - -
ACrv2 Parameter A for customer programmable curve for step 2 - 1.000 200.000 0.001 - -
BCrv2 Parameter B for customer programmable curve for step 2 - 1.00 100.00 0.01 - -
CCrv2 Parameter C for customer programmable curve for step 2 - 0.0 1.0 0.1 - -
DCrv2 Parameter D for customer programmable curve for step 2 - 0.000 60.000 0.001 - -
PCrv2 Parameter P for customer programmable curve for step 2 - 1.000 3.000 0.001 - -
CrvSat2 Tuning param for prog. under voltage Inverse- Time curve, step % 0 100 1 - -
HystAbs2 2Absolute hysteresis in % of VBase, step 2 %VB 0.0 100.0 0.1 - -
24 Overexcitation protection (PVPH)
PosSeq
MeasuredV
AB
Selection of measured voltage (MeasuredV) - BC PosSeq - PosSeq -
CA
MeasuredI AB
BC
Selection of measured current (MeasuredI) - CA PosSeq - PosSeq -
PosSeq
Disabled
Operation Disable/Enable Operation - OFF - OFF -
Enabled
IBase Base current (rated phase current) in A A 1 99999 1 6890.00 6890.00
VBase Base voltage (main voltage) in kV kV 0.05 2000.00 0.05 15.75 15.75
Pickup1 (V/Hz>) Operate level of V/Hz at no load and rated freq in % of %VB/f 100.0 180.0 0.1 140.00 - 140.00 -
Pickup2 (V/Hz>>) (Vbase/frated)
High level of V/Hz above which tMin is used, in % of (Vbase/fn) %VB/f 100.0 200.0 0.1 110.0 - 110.0 -
Xleakage Winding leakage reactance in primary ohms ohm 0.000 200.000 0.001 0.00 - 0.00 -
t_TripPulse Length of the pulse for trip signal (in sec) s 0.000 60.000 0.001 0.10 - 0.10 -
t_MinTripDelay Minimum trip delay for V/ Hz inverse curve, in sec s 0.000 60.000 0.001 7.00 - 7.00 -
t_MaxTripDelay Maximum trip delay for V/ Hz inverse curve, in sec s 0.00 9000.00 0.01 1800.00 - 1800.00 -
t_CoolingK Transformer magnetic core cooling time constant, in sec s 0.10 9000.00 0.01 1200.00 - 1200.00 -
IEEE
CurveType Inverse time curve selection, IEEE/Tailor made - IEEE - IEEE -
Tailor made
TDForIEEECurve Time multiplier for IEEE inverse type curve - 1 60 1 1.00 - 1.00 -
t1_UserCurve Time delay t1 (longest) for tailor made curve, in sec (t1Tailor) s 0.00 9000.00 0.01 - -
t2_UserCurve Time delay t2 for tailor made curve, in sec (t2Tailor) s 0.00 9000.00 0.01 - -
t3_UserCurve Time delay t3 for tailor made curve, in sec (t3Tailor) s 0.00 9000.00 0.01 - -
t4_UserCurve Time delay t4 for tailor made curve, in sec (t4Tailor) s 0.00 9000.00 0.01 - -
t5_UserCurve Time delay t5 for tailor made curve, in sec (t5Tailor) s 0.00 9000.00 0.01 - -
t6_UserCurve Time delay t6 (shortest) for tailor made curve, in sec (t6Tailor) s 0.00 9000.00 0.01 - -
AlarmPickup Alarm pickup level as % of Step1 trip pickup level % 50.00 120.00 0.1 - -
tAlarm Alarm time delay, in sec s 0.00 9000.00 0.01 5.00 - 5.00 -
60 Voltage differential protection (PTOV)
Disabled
Operation Disable/Enable Operation - - -
Enabled
VBase Base Voltage (VBase) kV 0.05 2000.00 0.05 - 400.00 - 400.00
No
BlkDiffAtULow Block operation at low voltage (BlkDiffAtULow) - - -
Yes
VDTrip Operate level, in % of VBase %UB 1.0 100.0 0.1 - -
tTrip Time delay for voltage differential operate, in milliseconds s 0.000 60.000 0.001 - -
tReset Time delay for voltage differential reset, in seconds s 0.000 60.000 0.001 - -
V1Low Input 1 undervoltage level, in % of VBase %UB 0.0 100.0 0.1 - -
V2Low Input 2 undervoltage level, in % of VBase %UB 0.0 100.0 0.1 - -
tBlock Reset time for undervoltage block s 0.000 60.000 0.001 - -
VDAlarm Alarm level, in % of VBase %UB 0.0 100.0 0.1 - -
tAlarm Time delay for voltage differential alarm, in seconds s 0.000 60.000 0.001 - -
RF_A Ratio compensation factor phase A VCap*RF_A=VBus_A - 0.000 3.000 0.001 - -
RF_B Ratio compensation factor phase B VCap*RF_B=VBus_B - 0.000 3.000 0.001 - -
RF_C Ratio compensation factor phase C VCap*RF_C=VBus_C - 0.000 3.000 0.001 - -
59THD 95% and 100% Stator earthground fault protection based on 3rd harmonic
GenRatedVolt Generator rated (nominal) phase-to-phase voltage in kV kV 1.0 100.0 0.1 - 5.3 - 5.3
NoVoltage
ResidualVoltage
All
Used connection type for gen. terminal voltage transformer AllThreePhases All
TVoltType - - ThreePhas -
(TVoltType) PhaseA ThreePhases
es
PhaseB
PhaseC
TimeDlyOperate Operate time delay in over/ under-frequency Mode. s 0.000 60.000 0.001 1.000 - 1.000 -
TimeDlyReset Time delay for reset. s 0.000 60.000 0.001 0.00 - 0.00 -
TOF3
Disabled
Operation Disable/Enable Operation - Disabled - Disabled -
Enabled
Vbase Base voltage kV 0.05 2000.00 0.05 - 12.50 - 12.50
PUFrequency Frequency gradient start value. Sign defines direct. Hz/s 35.00 75.00 0.01 - -
IntBlockLevel (StartFrequency)
Internal blocking level in % of VBase. %UB 0 100 1 - -
TimeDlyOperate Operate time delay in over/ under-frequency Mode. s 0.000 60.000 0.001 - -
TimeDlyReset Time delay for reset. s 0.000 60.000 0.001 - -
81 Rate-of-change frequency protection (PFRC).
Disabled
Operation Disable/Enable Operation - - -
Enabled
Vbase Base voltage kV 0.05 2000.00 0.05
PUFrequency Frequency setting pickup value. Hz 35.00 75.00 0.01 - -
IntBlockLevel Internal blocking level in % of VBase. %UB 0 100 1 - -
tTrip Operate time delay in pos./ neg. frequency gradient mode. s 0.000 60.000 0.001 - -
RestoreFreq Restore frequency if frequency is above frequency value (Hz) Hz 45.00 65.00 0.01 - -
tRestore Restore time delay. s 0.000 60.000 0.001 - -
tReset Time delay for reset s 0.000 60.000 0.001 - -
@ SECONDARY SYSTEM SUPERVISION
25 Synchrocheck and energizing check (RSYN, 25)
Operation Operation - phase1, phase2,
On - Off phase3 OFF - OFF -
phase1-phase2
phase1, phase2, phase3
SelPhaseBus1 Select phase for bus1 - - -
phase2-phase3
phase1-phase2
phase1, phase2, phase3
SelPhaseBus2 Select phase for bus2 - phase3-phase1 - -
phase2-phase3
phase1-phase2
phase1, phase2, phase3
SelPhaseLine1 Select phase for line1 - phase3-phase1 - -
phase2-phase3
phase1-phase2
SelPhaseLine2 Select phase for line2 - phase3-phase1
phase2-phase3 - -
UBase Base voltage in kV kV 0.001 phase3-phase1
9999.999 0.001 5.70 5.70
PhaseShift Phase Shift Deg -180 180 5 - -
URatio Voltage Ratio - 0.20 5.00 0.01 - -
OperationSync Operation for synchronism check function Off/On - On - Off - -
UHighBusSync Voltage high limit bus for synchrocheck in % of UBase %UB 50.0 120.0 1.0 - -
UHighLineSync Voltage high limit line for synchrocheck in % of UBase %UB 50.0 120.0 1.0 - -
UDiff U difference limit between bus and line in % of UBase %UB 2.0 50.0 1.0 - -
FreqDiffMin Freq. difference Min. Hz 0.003 1.000 0.001 - -
FreqDiffMax Freq. Difference Max. Hz 0.003 1.000 0.001 - -
FreqRateChange gradienteFreq. Difference Max. Hz 0.000 0.500 0.001 - -
tBreaker s 0.000 60.000 0.001 - -
tClose Pulse s 0.000 60.000 0.001 - -
tMaxSynch s 0.000 60.000 0.001 - -
tMinSynch s 0.000 60.000 0.001 - -
OperationSc - On - Off - -
UHighBusSc Voltage high limit bus for synchrocheck in % of UBase %UB 50.0 120.0 1.0 - -
UHighLineSc Voltage high limit line for synchrocheck in % of UBase %UB 50.0 120.0 1.0 - -
UDiffSc U difference limit between bus and line in % of UBase %UB 2.0 50.0 1.0 - -
FreqDiffA Freq. Difference limit between bus and line Auto Hz 0.003 1.000 0.001 - -
FreqDiffM Freq. difference limit between bus and line Manual Hz 0.003 1.000 0.001 - -
PhaseDiffA F angle difference limit between bus and line Auto Deg 5 90 1 - -
PhaseDiffM F angle difference limit between bus and line Manual Deg 5 90 1 - -
tSCA s 0.000 60.000 0.001 - -
tSCM s 0.000 60.000 0.001 - -
AutoEnerg Automatic energizing check mode - Off, DLLB, DBLL, Both - -
ManEnerg Manual energizing check mode - Off, DLLB, DBLL, Both - -
ManEnerDBDL Manual dead bus, dead line energizing - On - Off - -
UHighBusEnerg Voltage high limit bus for energ. check in % of UBase %UB 50.0 120.0 1.0 - -
UHighLineEnerg Voltage high limit line for energ. check in % of UBase %UB 50.0 120.0 1.0 - -
ULowBusEnerg Voltage low limit bus for energ check in % of UBase %UB 50.0 120.0 1.0 - -
ULowLineEnerg Voltage low limit line for energ check in % of UBase %UB 50.0 120.0 1.0 - -
UMaxEnerg Maximum voltage for energizing in % of UBase %UB 80.0 140.0 1.0 - -
tAutoEnerg Time delay for automatic energizing check s 0.000 60.000 0.001 - -
tManEnerg Time delay for manual energizing check s 0.000 60.000 0.001 - -
Hz 0.003 1.000 0.001 - -
RFUF Fuse failure supervision (RFUF)
FSD1
Operation Operation - On - Off OFF OFF
IBase Base value for current settigns in A A 1 99999 1 - 600.00 - 600.00
UBase Base value for voltage settings in kV kV Off, UNsINs,
0.05 2000.00 UZsIZs,
0.01 - -
5.25 5.25
UZsIZs OR UNsINs,
OpMode Operating mode selection - -
UZsIZs AND UNsINs,
3U0> Operate level of 3U0 overvoltage in % of UBase %UB 1 100
OptimZsNs 1 -
3I0< Operate level of 3I0 undercurrent in % of IBase %IB 1 100 1 -
3U2> Operate level of neg.seq overvoltage in % of UBase %UB 1 100 1 -
3I2< Operate level of neg.seq undercurrent in % of IBase %IB 1 100 1 -
OperationDUDI Operation of change based function Off/On - On - Off -
DU> Op level of change in phase voltage in % of UBase %UB 1 100 1 -
DI< Op level of change in phase current in % of IBase %IB 1 100 1 -
UPh> Operate level of phase voltage in % of UBase %UB 1 100 1 -
IPh> Operate level of phase current in % of IBase %IB 1 100 1 -
SealIn Seal in functionality - On - Off -
USealIn< Op level of seal-in phase voltage in % of UBase %UB 1 100 1 -
IDLD< Op level for open phase curr. detection in % of IBase %IB 1 100 1 -
UDLD< Op level for open phase voltage detec in % of UBase %UB 1 100 1 -