Applicant: Date:
Instructions:
This spreadsheet calculates the waste heat, system efficiency and emissions eligibility of Level 3-N systems applying
to the Self-Generating Incentive Program for incentives. Applicants must provide documentation supporting all inputs
including but not limited to system capacity, fuel consumption, waste heat recovery rate, baseline emissions,
operating schedule, equivalent full load operating hours and thermal load. See the 2005 SGIP Handbook for details
of eligibility and documentation requirements. All yellow cells must be completed by Applicant/Host Customer.
Generator Generator
Equivalent Full Electric Output Recovered Useful thermal
Std Hours Per Load Hours per Capacity per Month Waste Heat per Thermal Load energy output Fuel Input (LHV
Month Month (hrs) Month (hrs) Factor (kWh) Month (Btu) per Month (Btu) (Btu) Btu)
Jan 744 400 54% 24,000 150,216,000 150,000,000 150,000,000 292,363,636
Feb 672 400 60% 24,000 150,216,000 150,000,000 150,000,000 292,363,636
Mar 744 400 54% 24,000 150,216,000 150,000,000 150,000,000 292,363,636
Apr 720 600 83% 36,000 225,324,000 80,000,000 80,000,000 438,545,455
May 744 600 81% 36,000 225,324,000 80,000,000 80,000,000 438,545,455
Jun 720 600 83% 36,000 225,324,000 42,000,000 42,000,000 438,545,455
Jul 744 600 81% 36,000 225,324,000 42,000,000 42,000,000 438,545,455
Aug 744 600 81% 36,000 225,324,000 42,000,000 42,000,000 438,545,455
Sep 720 600 83% 36,000 225,324,000 42,000,000 42,000,000 438,545,455
Oct 744 400 54% 24,000 150,216,000 42,000,000 42,000,000 292,363,636
Nov 720 400 56% 24,000 150,216,000 80,000,000 80,000,000 292,363,636
Dec 744 400 54% 24,000 150,216,000 100,000,000 100,000,000 292,363,636
Annual Total 8,760 6,000 68% 360,000 2,253,240,000 1,000,000,000 1,000,000,000 4,385,454,545
Eligibility
Criteria Passes? Reference
AB 1685 Total Efficiency = 72.2% ≥ 60% Yes Public Utilities Code 353.2 and 379.6
P.U. Code 218.5 (a) = 44.9% ≥ 5% Yes Public Utilities Code 218.5(a) & 18CFR Part 292
P.U. Code 218.5 (b) = 39.4% ≥ 42.5% No Public Utilities Code 218.5(b) & 18CFR Part 292
NOx Emissions w/o CHP
NOx EmissionsCredits
w/ CHP= 0.240 ≤ 0.14 lb/MWh No
Credits = 0.132 ≤ 0.14 lb/MWh Yes Public Utilities Code 379.6 and California Air Resources Board, Guidance
Note: Qualified Level 3-N Waste Gas fueled systems are exempt from for the Permitting of Electric Generation Technologies, Appendix D:
the emissions standard. See the 2005 SGIP Handbook for Waste Gas Quantifying CHP Benefits, July 2002.
emission exemption qualification requirements.