Drum Indicator Scale Details

Drum NWL* Yellow Yellow Red Red


Hight
(Bottom to mm Below** Above** Below** Above**
Top) (Low) (High) (L.Low) (H.High)
mm mm mm mm mm

HP Alarm Set Point 1343 0 -635 +130 -785 +275

Level (From Bottom) 835 200 965 50 1100

Percent ( % ) 62.2 14.9 71.9 3.7 81.9

LP Alarm Set Point 1990 0 -890 +610 -1090 +750

Level (From Bottom) 1140 250 1750 50 1890

Percent ( % ) 57.3 12.6 87.9 2.5 95.0

Note :
* NWL is measured from the centerline of the drum.

** High and low alarm limits are measured from the centerline of drum.
NEW
NEW TECHNOLOGY™ METER NTM-4
Pat. Pend.
Current Loop, Signal or External Powered
Replaces: Chessell 700 or Any 10” Bargraph Meter

FEATURES:
S ź
*Automatic Tricolor Bar with Intensity Control
*4 Digits at 0.3” (9.9.9.9 or -1.9.9.9)
ź 0.8” *,137)$,/Alarm with Run Time Stamp
*Self Diagnostics
Build Your Own Part *Isolated Serial I/O
*USB/RS485
Number/Receive a *Con¿gurable Bar Direction (Up/Down/Center Zero)/Pointer
Quote at: *Only 100mW@5VDC!
http://www.otekcorp.com/ *Intensity Control
* Math functions (+, -, x, ¥, ÷, X-Y tables, polynomials)
configurator/nts/ *Averaging: None to 255
*Addressable: 8 Characters
*Many Power Input Options
(External Powered Models Only)
Panel Cutout * >30 Isolated Input Signals
*4 Relays or O.C.T.
10.9 x 1.25”
11.32” *4-20mA/30V Output
*Ethernet
*—SD Flash Memory: 32 GB
*Lifetime Warranty

DESCRIPTION: The New Technology Meter (NTM) series combines over 40 years of experience with
the latest ASIC uC and ultra-ef¿cient multicolor LED technology to bring you into the 21st century. The
NTM external power series features over 30 signal conditioners (1” square) which are housed in many
industry's standard packages to replace form, ¿t and function any analog or digital panel meter. If not, we'll
make it!

Our patented hardware and ¿rmware gives you the highest reliability (we have a lifetime warranty) at
the lowest cost, with features such as: automatic (programmable) tricolor bargraph (like a traf¿c light);
ź automatic signal fail detect (open or short); indication and serial transmission with run time stamp and units
Ź
Ż
1.4” ID, isolated retransmission (4-20mA), and universal power inputs (5-32VDC or 90-265VAC). The NTM
Series offers several math functions such as X-Y tables, polynomials and log-anti-log functions.
The NTM signal and external power series also feature isolated USB, RS485 or ethernet, open collector
transistors (4/channel) and SPDT relays (4/channel). You can tell us your
NEW TECHNOLOGY METER BLOCK DIAGRAM/CHANNEL custom needs and we'll make it (or might already have it)!
CONTROLLER/DISPLAY ONLY
The NTM-4 is available in either a loop (4-20mA), A.C. signal or ex-
CURRENT
I LOOP REL AYS O.C. T. (4) ternal power version. The external powered versions can accommodate
(LOOP POWER) O.C.T RELAYS (4)
DISPLAYS,
CPU,
ANALOG OUT
4-20mA OUT (1)
4 relays, isolated DAC and power for the analog output (per channel),
ETHERNET

V AC/DC
SIGNAL DETECT,
KEEP ALIVE,
USB/485 30V OUT (1) include >30 signal conditioners and isolated input power options, as well
IN V, A,W, Hz • ISOLATORS
FOR ALARMS,
FLASH
MEMORY
RS485 as ethernet and Àash memory (—SD). Standard factory set color changes
A (SIGNAL POWER) USB/
SERIAL I/O,
PWM,
ETHERNET are: red: <10, >90%, yellow: <20, >80%, green: >20, <80% of F.S.
RS

SIGNAL
ZERO/SPAN 485 Use digit 14, option 9 for custom con¿guration (you can change it with
5-32 VDC
CONDITIONERS
IN
(EXTERNAL POWER)
90-265 VAC
POWER POWER
simple commands).
USB SUPPLY INPUT

DISPLAY ONLY

520-748-7900 4016 E. TENNESSEE ST.


TUCSON, AZ. 85714 U.S.A.
FAX: 520-790-2808
MADE
E-MAIL:sales@otekcorp.com SINCE 1974 IN
http://www.otekcorp.com USA
NTM-4
THE PRODUCTS
All New Technology products share the same innovative electronic circuit design. The difference between the models is
their mechanical features (see Block Diagram and mechanical drawings). Some are displays only, some are single or
multi channel, some can have relays, DACs, ethernet and Àash memory, and some require an external power source. But
all products contain the New Technology, which consumes less than 1% of comparable digitals (20-100mW for loop/signal
powered versions) and approaches the power consumption of analog meters.

WHAT CAN YOU DO WITH OTEK’S NEW TECHNOLOGY?


Note on Otek’s Powerless™ Technology: If your signal cannot supply tmW (~ 5V/3mA), contact us or use external
power models.

1. One Channel Models: -0, 2. Two Channel Models: -1, 3. Three Channel Models: 4. Four Channel Models:
-4, -B, -D, -F, -H, -L, -M, -N, -2, -3 and -5 through -9 & -3, -5, -7, -8 and -A: Note: -5, -7 and -8: The four chan-
-P, -S & -X: Implement any -A: Note: Also available in Also available on 4 channel nel models offer all of the
math function, X-Y table (25 models with 3 or 4 channels. models -5, -7 & -8. Otek’s functions outlined in #1, #2
point), polynomials (9th order), Features include all those of the New Technology three chan- and #3. However, with the ad-
offset, tare, zero, scale, log & single channel models and each nel models perform all the ditional channel available, the
anti-logarithmic to affect the channel is 100% isolated from functions outlined in #1 and New Technology barmeters
unit’s display at will. Some ex- each other. In addition, you can #2. Further, one channel can rival Àatscreens with supe-
amples are: change the display add, subtract, multiply, divide, indicate the input variable and rior HMI/MMI functionality
& data using any combination ¿nd the square root between the other two channels can be and ease of viewing/analy-
as commanded by your algo- channels. You can also use setpoint indicators/controllers sis of any combination of 4
rithm, such as +/-/X/÷/¥ or set a one channel to monitor/control (Hi, Hi-Hi, Low and Low-Low variables. For example, Volts/
variable or linearize the display the input signal and the second limits), or subject the input/ Amps/Watts/Hertz or tempera-
using X-Y tables or polynomi- channel to indicate devia- output to any mathematical ture/pressure/pH/humidity.
als. This works well for odd tion, differential such as PID, function or algorithm such as The four channel models can
shape containers. You can also alarm override or one channel PID or display the input vs. also be used to monitor/con-
change the reading from ƕF to setpoint can be used to control output and derivative, or switch trol the product of the other 3
ƕC or ƕK or compress/expand another channel function. You scales when the input reaches a variables, making them ideal
the display (and data out) using can also use one channel as limit/band such as for Àow-vol- for the petrochemical industry.
the log and antilog functions. a backup if the other channel ume-pressure or temperature.
In addition, you can change the becomes disabled or use them Monitor Volts, Amps and Watts Data Logging? Some models
factory default alarm pointers as volume & Àow (¥) monitors/ AC or DC or any of 3 vari- offer optional —SD memory to
and colors or delete them. Zero controllers. The New Tech- ables, including Hertz, lead/lag, record 24/7 anything available
& Span potentiometers are in- nology two channel models power factor, peak/valley or for via the serial I/O. Maximum
cluded for manual adjustment. are also perfect as REM/RAD synchronizing of power lines capacity (and growing) is 32
indicators/controllers (also with the bipolar (center zero) GB!
Note: Models -D and -F have see our RPM series with log- tricolor bargraph.
internal USB serial I/O that is antilog functions for radiation REDUNDANT CONTROL:
not accessible to the customer. monitoring). The New Technology series Because all channels are
Contact Otek for access brings Process Automation 100% isolated from each
Contact OTEK for algorithms Control (PAC) within your other, you can use any
OTEK’s New Technology and formulas or any idea you reach and affordability. These multi-channels model as a
series is only limited by your wish to share with our audienc- models are compatible with redundant controller. If you
needs and imagination. Just es via our Youtube or Facebook any DCS/SCADA system using need the “Democratic vote,”
give us a call at 520-748- page posts. their USB/RS485/Ethernet I/O algorithm, contact OTEK or
7900 or email us at sales@ options and allow for ease of see our Model TRC (Triple
otekcorp.com and give us the interface with wireless systems. Redundant Controller).
challenge to develop the best
algorithm for your process.

-2-
520-748-7900 4016 E. TENNESSEE ST.
TUCSON, AZ. 85714 U.S.A.
FAX: 520-790-2808
MADE
E-MAIL:sales@otekcorp.com SINCE 1974 IN
http://www.otekcorp.com USA
NTM-4 Description, Notes & Order (Continued) Industrial Grade Common
Digit 5, Serial I/O & Memory: Digit 6, Grade: Electrical Specifications
Settings: 8N1N, 1200-19,200 Baud, Industrial Grade (Options 0 or 1) is per
ASCII. these published speci¿cations. Grades Input & Display:
M and E per agreed speci¿cations. Op- *A/D: Accuracy, Linearity & Reso-
LOOP/SIGNAL POWER ONLY: tions M and E typically include EMI/ lution: +/- 0.05% of F.S. 12 Bits,
RFI shield all around and ¿ltered con- Conversion Rate: 40/sec, Averaging:
Digit 5, Serial I/O: Option 0, USB nectors to meet EPRI-TR-102323-R3 0-255, zero, span, offset, tare, math
Complies 100% with V2.0 and if digit (requiring ~2” deeper case). OTEK functions, 25 point X-Y tables and
10, option 1 is selected (USB pow- polynomials (9th).
ered) then digit 5 must be option 0. will build to certain nuclear or MIL-
Standards but testing and con¿rmation *Bargraph: 51 Automatic Tricolor
Digit 5, Option 1, RS485: Complies of compliance, if required, will need to (R/Y/G) Segments
with industry standard and requires be done by third party and at customer’s *Digits: Four Full Digits (9.9.9.9 &
5VDC@<3mA and a terminating 330 expense. Option 0 is 94VO plastic, -1.9.9.9).
Ohm resistor at ¿rst and last unit in the *Typical Power Consumption of Dis-
BUS. option “I” is aluminium nickel plated
to Mil-Specs. Typical Mil-Specs: play: 10-100mW@3.3V-5V
EXTERNAL POWER ONLY: 461, 462, 169, 901, 801, RTCA-160, I *Temperature Coef¿cient:
EEE344, etc. Contact Otek for custom +/-50PPM/°C
Option 0, USB & Option 1, RS485 housing colors. *Operating Temperature: -10 to +60;
(see above), plus: Storage: -20 to +70°C
Other Important Data:
*CCMR: >90dB@50-60Hz
Math Functions: +, -, x, ÷, √, Polyno-
Digit 5, Option 2 Ethernet: Com- *Isolation: >500VDC to any other I/O
mials to 9th order, 25 Point X-Y table,
plies with 10 Base-T/100Base-TX & P.S.
zero, offset, span and tare. You can
RJ45 up to 19,200 Baud. Maximum *Humidity: 5-95% RH non-condens-
add, subtract, multiply, divide (etc.) one
power consumption is <300mA@5V ing
channel to/from another channel and
(1.5W). *Front Panel: NEMA 3. NEMA 4x
display the result in the other channel
on request.
(i.e. V (Ch.1)xA(Ch.2)=W(Ch.3).
Digit 5, Options 3 & 4: uSD Flash *Failed Signal Detect: ~ 20 seconds
Memory: Internal —SD Àash memory Signal Failure Alarm: Requires ap-
after > 1 minute “On” @50% of F.S.
with up to 32 gigabytes capacity. You proximately 1 minute of normal (mid-
can store selected data at-will via serial Note 1: See page 12 of the master
scale) operation for it to alarm the
command and download it as required. catalog for environmental specs vs.
display and output the serial data after
A 32 GB card logging 3 times per sec- housing, bar length and digit size.
the signal (Powerless™) has ceased.
ond can hold approximately 4 year’s
worth of data. Note 2: E and M grades are the same
Serial I/O: Setting: 8N1N, 1200-19,200
as Industrial unless otherwise speci-
BAUD, 8 Character Address
PID: Programmable (best with >dual ¿ed.
Need a Transmitter?
See model NTY channel models) automatic or manual
with external 10K Ohm potentiometer
(option 56). If You Don't
See It
High Quality: No matter their size or Ask For It!
number of channels all use the same
(SV & V) ¿rmware, hardware and com-
mands. No matter their grade (Indus-
trial, Mil-Spec, Nuclear) they all carry a
lifetime warranty

-3-
520-748-7900 4016 E. TENNESSEE ST.
TUCSON, AZ. 85714 U.S.A.
FAX: 520-790-2808
MADE
E-MAIL:sales@otekcorp.com SINCE 1974 IN
http://www.otekcorp.com USA
NTM-4
INPUT SIGNAL SPECIFICATIONS (Digits 8 & 9)
Industrial Grade Common INPUT SIGNALS (Digits 8 & 9): Options 01 through 16 for A. C. Sig-
Electrical Specifications Note: Otek’s exclusive Input Fail nal Powered Only {Continued}:
detect (open or short) is standard on all
(Continued) inputs. Use option 29 and specify if Option 03, Watts A.C. (C.T. &
you want it disabled (also ¿eld con¿gu- P.T.): Burden: <100mW, Range:
AVAILABLE ON EXTERNAL rable). IMPORTANT NOTE: Actual >30<750W/50-60Hz; Accuracy & Lin-
POWER MODELS ONLY: connection will vary. See the User’s earity: ±0.2% of F.S. at 90-140VAC
Manual or the NT Catalog for speci¿c & 1-5 AAC. Worst case: ±3% outside
Outputs: connection information. this range. Best operating range to
specification: 100-500 Watts.
*Analog Output: Accuracy & Lin- Option 00 & 17 For Loop Power Option 04, Hertz VAC: Burden:
earity: rF.S.; r0.1 LSB, Range: Only: <100mW, Range: >30V<150V &
3-24mA (max. load: <1K Ohm). Option 00, Loop Powered: Burden: >30<750Hz; Accuracy & Linearity:
*Analog Output Temperature Coef- <3V@4mA, d5V@ 20mA; Range: ±0.2% of F.S.
ficient: +/-50PPM°C 3-26mA; Accuracy & Linearity: Option 05-14: Same as options 01
*Analog Output Isolation To All ±0.05% of F.S.
Other I/O & Power: >500VDC Option 17: 10-50mA Loop Powered: VAC/AC Signal Power Only:
Burden: >3V@10mA, ”5V@ 50mA;
*Relays: 4 Each/Channel (except Range: 3-50mA; Accuracy & Linear- Option 16, 5-150 VDC Signal
NTY, 2): SPDT Form C, 1A Max @ ity: ±0.05% of F.S. Power: Now you can monitor and
120VAC/30VDC resistive load only,
control your UPS, battery bank or
Contact Protection: 300VAC/DC on all Options 01 through 16 for A. C. Sig-
power supply from 4-150VDC, with
contacts. Speed: +40mS (main loop). nal Powered Only
only power from the signal. The NTM
requires >10<80mW (~3mA-20mA).
O.C.T. (Open Collector Transis- Important Note: C.T. are sensitive Imagine the possibilities! Almost like
tors): VCE Max: 30VDC; Ice Max: and limited to the secondary (output) analog (only signal wires), but with
30mADC, Speed: +40mS (main loop). impedance. OTEK A.C. signal pow- 21st century digital technology ready
ered products present and input imped- for your PAC/DCS/SCADA system.
Note 1: Relays & O.C.T. have P.O.D. ance of ~0.2 Ohms (~1v@5A). Make Scaling: 4-150VDC in =4.0-150.0
(~100mS) and can be set to fail safe sure your C.T. can drive a >0.3 Ohm Digital Display & 0-100% bargraph
operation (normally on). load without saturating or losing linear- with alarm pointers. See Digits 13 &
ity. Contact Otek for assistance. Best 14 for custom calibration and scale.
Note 2: See Digit 11 for default set C.T. to use: >100:5. Accuracy & Linearity: r0.1% of
points and User’s Manual for com- Option 01, VAC (P.T.): Burden: full scale.
mand set via serial control. <100mW; Range: 30-150V/40-100Hz; Alarm Outputs (Signal Power):
Accuracy & Linearity: ±0.2% of F.S. Open collector transistors (4) optional.
Best operating range to specification: See the ordering information on pages
90-150VAC. 10/11, digit 11, option 1. For relays,
Option 02, 5 AMP A.C. (C.T.): Bur- contact Otek (custom).
den: <100mW; Range: .3-5A; Accu- 4-20mA Analog Output: Custom,
racy & Linearity: ±0.2% of F.S. Best contact Otek (requires >1 watt from
operating range to specification: 1-5 input signal).
Amps.
Option 17: 10-50mA Loop Pow-
ered: See Loop Power options in
previous column.
-4-
520-748-7900 4016 E. TENNESSEE ST.
TUCSON, AZ. 85714 U.S.A.
FAX: 520-790-2808
MADE
E-MAIL:sales@otekcorp.com SINCE 1974 IN
http://www.otekcorp.com USA
NTM-4 INPUT SIGNAL SPECIFICATIONS (Digits 8 & 9)
AVAILABLE ON EXTERNAL POWER MODELS ONLY
AVAILABLE ON EXTERNAL Options 30-34, Volts RMS: Here we Option 40 (120VACx5AAC C.T.):
POWER ONLY use a True RMS-DC Converter for Zin: 1M for V & 0.04Ÿ for I
accurate (+ 0.1%) measurement of sine Range: 0-750W
Option 20: 4-20mA: The burden on waves up to 10KHz. For 10-20KHz Accuracy & Linearity: ±0.2% of F.S.
the loop is only 0.5V@20mA (25 Ohm) and SCR accuracy is + 1%. r 1 digit
and you can use the math functions for
converting to Àow, instantaneous or VRMS: Zin: 1MŸ Note: Option 40 (120V/5A) includes
totalizer. Range; per options; the shunt (0.04 Ohms/20W) on con-
Accuracy: +0.1% of F.S. r 1 digit Accuracy & Linearity: ±0.1% of F.S. r nector only for 5A C.T.
1 digit
Options 21-24: VDC: Input imped- Options 41-44, Hertz: We use an F-V
ance is 1 Mega Ohms on all VDC Options 35-37, Amps RMS: We use a to accept frequencies up to 20KHz
ranges. True RMS-DC Converter for accurate and amplitudes from 1-400V peak or
(+ 0.1%) measurement of sine waves dry contact or open collector transistor
Input impedance 1M Ÿ up to 10KHz. For 10-20KHz and SCR (O.C.T.). For 50 to 440 Hz power line
Range: Per Option accuracy is + 1%. frequency measurement, use Option #
Accuracy & Linearity: ±0.05% of F.S. “44.”
r 1 digit Zin: 35 (0.1A): 2Ÿ; 36 (1A): 0.2Ÿ;
37 (5A): 0.04Ÿ Option 41 (10KHz/5V Logic):
Options 25 & 26, mADC: Since the Range: Per option Zin: 1M
NTM is 2V full scale (2,000 Counts) Accuracy & Linearity: ±0.1% of F. S. Range: 30-10KHz
the “Shunt” resistors used are 100 r 1 digit Accuracy & Linearity: ±0.1% of F.S.
Ohms for 10mA and 10 Ohms for r 1 digit
100mADC. Options 38 & 40, Watts RMS:
Here we use a True RMS-DC Con- Option 42 (120V, 40-100Hz):
Input impedance 25: 50Ÿ; 26: 5Ÿ; verter for accurate (+ 0.1%) measure- Zin: 1M
Accuracy & Linearity: ±0.05% of F.S. ment of sine waves up to 10KHz. For Range: 50-150VC/30-100Hz
r 1 digit 10-20KHz and SCR accuracy is + 1%. Accuracy & Linearity: ±0.1% of F.S.
Input impedances vs. range are the r 1 digit
Option 27, Watts DC: same as for VDC & mADC ranges.
VZin: 10M Ÿ/AZin: 1.0Ÿ, 5W
Option 43 (240V, 30-100Hz):
Range: 1W Option 38 (1Vx1VAC): Zin 1 M; Range: 100-260V/30-100Hz
Accuracy & Linearity: ±0.1% of F.S. Zin: 1MŸ for both inputs Range: 1V
Accuracy & Linearity: ±0.1% of F.S.
r 1 digit RMS r 1 digit
Accuracy & Linearity: ±0.2% of F.S. r
Option 28, Watts DC (1Vx1V): VZin: 1 digit Option 44 (120V, 500 Hz):
1M for both inputs Zin: 1 M
Range: 0-1V Note: Always use P.T. & C.T. for op- Range: 50-150V/300-500Hz
Accuracy & Linearity: ±0.1% of F.S. r tions 33, 34, 40, 42, 43 & 44. Accuracy & Linearity: ±0.2% of F.S.
1 digit r 1 digit

Option 29: Custom: Use this option


to describe any custom input, scale or
modi¿cation to the NTM and contact
us for feasibility and cost.

-5-
520-748-7900 4016 E. TENNESSEE ST.
TUCSON, AZ. 85714 U.S.A.
FAX: 520-790-2808
MADE
E-MAIL:sales@otekcorp.com SINCE 1974 IN
http://www.otekcorp.com USA
NTM-4
INPUT SIGNAL SPECIFICATIONS (Digits 8 & 9)
AVAILABLE ON EXTERNAL POWER MODELS ONLY
Option 45: Strain-Gage (>300 < 4K Option 48: RTD (PT1000): Same as Option 53: pH (Acidity): We use a
Ohm): These are typically "Mono- PT100 except it is 1000 Ohms at 00C FET input (1015) ampli¿er and calibrate
lithic" S-G that require constant volt- instead of 100 Ohms @ 00C. The same the NTM for 0-14.00 pH using the
age (preferably) excitation. We use technique is used for copper RTD (10 Industry's standard + 413 mV = + 7pH
4.096V for high stability and accu- Ohm), contact OTEK. Same connec- co-ef¿cient.
racy. Use option 29 and specify your tion as Option 47 apply. Note: Not temperature compensated,
S-G sensitivity and the NTM display contact OTEK for auto temperature
at Zero and Full Scale. Accuracy: +0.5% of F.S. r 1 digit, plus compensation.
sensor's error. Accuracy: +0.05% of F.S. r 1 digit
Excitation: 4.096V, 50 PPM/qC
Range: ±300-4K Ÿ Note: For long distances (> 300’) Option 54: ORP (Oxygen Reduction
Accuracy & Linearity: ±0.1% of F.S. use a 4-20mA transmitter such as our Potential): Our FET ampli¿er (109)
r 1 digit model NTY from our New Technol- accepts the industry standard 2000mV
ogy series. F.S. of the probe and the NTM dis-
Note on S-G: Some S-G offer +/- plays it in % (0-100.0%).
1VDC or 4-20mA condition output. Option 50: Thermocouple (Type
Use Option 29 and specify. J): This TC has a range of -210 to + Accuracy: +0.05% of F.S. r 1 digit
7600C (-350 + 13900F). Its color is
Option 47: RTD (PT100): Note: For white (+) and Red (-), cold junction Option 55: %RH: This conditioner is
options 47 & 48 you can change °C to (CJ) is at the connector. Make sure the designed to interface to a typical (ca-
°F and RTD type via serial port. connections from the NTM and your pacitance type) 2-3 pF/% of RH made
TC are as close to the NTM entrance
as possible to avoid errors. If you by several manufacturers. Use Option
We excite your 2 , 3 or 4 wire RTD
short out the NTM's +TC & -TC to- "29" and contact OTEK to specify your
with 200—A to avoid the "self heating"
gether, the NTM will read the ambient sensor's speci¿cations.
effect. The range of the NTM is the temperature at the junction due to its Accuracy: + 0.05% RH of signal input,
same as your RTD typically -2000C built-in C.J.C. r 1 digit.
to +8000C (-328 + 15620F). You can Note: You can change °C to F and TC
place the decimal point at will (typi- type via serial port. Option 56 Resistance (0-10K Ohm):
cally -200.0 to 800.0. The PT100 has Want a simple 4-20mA transmitter?
a temperature coef¿cient of 0.00385 Accuracy: + 20 F.S. of signal input. Just connect a 10K Ohm (others on
Ohms/Ohm/0C. (For legacy 0.00392 request) potentiometer to the NTM and
TC (known as ANSI 392) contact Option 51: TC (Type K): This is yel- control any 4-20mA input valve, motor,
OTEK and use Option "29". low (+) and red (-) and has a range of transducer, etc.
-270 + 13700C (-440 + 25000F). The
Accuracy: +0.5% of F.S. r 1 digit , same notes as Option 50 apply. Accuracy & Linearity is ±0.1% of F. S.
plus sensor's error. Accuracy: + 10 F.S. of signal input. r 1 digit.
Note: For 2 wire, jump - S to -E and Option 52: TC (Type T): This blue Standard Calibration: 0-10K Ohms=4-
+S to +E. For 3 wire only jump -S to (+) and red (-) TC has the range of 20mA. Use option #29 and specify
-E. -2700 + 4000C (-440 + 7500F). Same your calibration. Ideal for linear trans-
notes as Option 50 apply. ducers.

Accuracy: + 20 F.S. of signal input.

-6-
520-748-7900 4016 E. TENNESSEE ST.
TUCSON, AZ. 85714 U.S.A.
FAX: 520-790-2808
MADE
E-MAIL:sales@otekcorp.com SINCE 1974 IN
http://www.otekcorp.com USA
NTM-4 Description, Notes & Order (Continued)
Option 57, 10-50mA Range: 10 Digit 10 (Power Input): Digit 11 (Control Outputs): (Contin-
Ohms input resistance ued)
Accuracy & Linearity: ±0.1% of F.S. EXTERNAL POWER ONLY (Con-
r1 Digit tinued): Digit 11, Option 2: Relays: are
S.P.D.T. (1C) and can switch maximum
Option 58: Serial Input Remote Dis- Digit 10, Option 2, 5VDC: 5VDC is resistive loads of 1 Amp @ 120 VAC or
play/Controller: Here you can use the used to drive the relays (<50mA/relay) 30 VDC. They include 300V varistors
unit as a remote display & controller and/or the DAC via internal isolated at their contacts. Inductive loads must
with modi¿ed ASCII to alpha-numeric 5-30VDC-DC (<200mA). If you order be attenuated by the user.
display for DCS SCADA, PLC sys- relays and analog out, you will need
tems. ~300mA/channel. This option is also
isolated from the input signal. AVAILABLE ON EXTERNAL
See the user’s manual for simple com- POWER ONLY
mands to use the NTM in PAC (Process Digit 10, Option 3, 7-32VDC: Same
Automation Control) applications. as option 2 but with wide input range of AUTOMATIC BAR COLORS:
7-32VDC. Ef¿ciency: >80%.
Digit 10 (Power Input): Limits/Colors Factory default (% of
Digit 10, Option 4, 90-265VAC: This Full Scale): Also see digit 14.
option accepts 50-60Hz. For 100-
LOOP & SIGNAL POWER ONLY:
300VDC or 400 Hz, use Digit 10, op- Low-Low Limit (<10%): Red Bar,
Digit 10, Option 0, Powerless,
tion 9 and specify. Ef¿ciency: >80%. OCT1/K1 “ON”
No Power Required: The Input
Fail detect/Alarm (patent pending)
Àashes the display “INPT FAIL (,137 Digit 11 (Control Outputs): Low Limit (<20%): Yellow Bar,
)$,/)” and transmits this serial mes- OCT2/K2 “ON”
sage for ~20 seconds, after which it AVAILABLE ON EXTERNAL
will cease. This feature is available POWER ONLY High Limit (>80%): Yellow Bar,
in all Powerless™ models. If desired OCT3/K3 “ON”
on powered models, use option 9 on Digit 11, Control Outputs: Op-
Digit 14 and specify “input fail detec- tions 1: Open Collector Transistors Hi-Hi Limit (>90%): Red Bar, OCT4/
tion.” Signal Fail Requirement: Unit (O.C.T.): They are NOT isolated from K4 “ON”
must be “On” for at least 1 minute at each other (common emitter) but are
>50% of full scale for it to operate. isolated between channels and can Safe Area (>20<80%): Green bar
sink a maximum of 30 mA and sustain will follow signal input and if outside
EXTERNAL POWER ONLY: a maximum of 30VCE ( the O.C.T. are the limits, it will change its color to the
normally used to drive S.S.R.) When limit’s color (yellow or red).
Digit 10, Option 1, USB Powered: you order option 2 (Relays), we use the
The NTM series requires >.1<1.5 O.C.T. to drive the relays. See commands in user’s manual to
Watts/Channel (worst case, fully customize your bargraph colors.
loaded) meaning that you can power NOTE: You can use the internal iso-
it through the USB port, but this lated 5VDC power to drive loads with For other con¿gurations , use option
option eliminates the isolation from the O.C.T. Total maximum current 9 on Digit 14 (¿eld con¿gurable).
USB to input signal. Analog output Max power consumption per relay:
available is 50mADC.
remains isolated contact OTEK for 50mA@5VDC (0.25W). See Digit 14.
more details or use options 2-4.

-7-
520-748-7900 4016 E. TENNESSEE ST.
TUCSON, AZ. 85714 U.S.A.
FAX: 520-790-2808
MADE
E-MAIL:sales@otekcorp.com SINCE 1974 IN
http://www.otekcorp.com USA
NTM-4 Description, Notes & Order (Continued)
Digit 11 (Control Outputs) {Contin- Digit 12 (Analog /Power Output) Digit 14 (Range/Calibration):
ued}: (Continued):
0= Factory Default: 0-Full Scale
AVAILABLE ON EXTERNAL Analog Output External Control Input=0-100% bar and 0-100.0 digits.
POWER ONLY (Use Option 9 and specify): A) Colors: <10>90%: Red; <20>80%:
0-100mVDC in=4-20mA out; B) Yellow; >20<80%: Green. Use Option
External Control: You can control 0-10K Ohm in=4-20mA out; C) Use 9 (custom) and contact Otek. Also see
the O.C.T./Relays via the serial port options 58, 68, 78 or 88 and control it Control Outputs (Digit 11).
at will with simple commands. They via serial port.
don’t have to be assigned to the bar Bargraph Default: 0-full scale=
colors/set points, but are by default. Digit 12, 30 VDC Out, Option 2: 0-100%. You can program it for sin-
Use this option to power your 4-20mA gle pointer, or three or ¿ve bars via the
Notes: transmitter or other transducer. Maxi- serial port.
1. Digit 11 is governed by Digit 7 (# mum current is 25mADC. It’s isolated
of Channels) & Digit 4 (Housing). and is the same power source we use
ABOUT OUR INPUT
Reason: Digit 11 can NOT have more for 4-20mA out. Power consumption:
channels than permitted by Digit 7 or it 200mA@5VDC (1W)/channel. FAIL DETECTION
cannot ¿t in the housing (Digit 4). Only available on Powerless™
1. This digit 12 is governed by dig- models. While in normal operation,
its 4 (Housing) & 7 (# of Channels). we store excess energy and use it to
Digit 12 (Analog /Power Output): Reason: Digit 12 cannot have more power the NTM if and when the signal
outputs than input channels (Digit 7), fails (post mortem).
AVAILABLE ON EXTERNAL which is governed by Digit 4 (Hous-
POWER ONLY ings).
Digit 12, Analog Output, Option 1:
This isolated output is factory set to Digit 13 (Scale Plate):
follow the input (0-F.S. in=4-20 out)
but can also be set for other outputs or Digit 13, Scale Plate: Option 0 is a
serially controlled by simple com- standard scale plate that reads 0-100%.
mands via the serial port. For other Use option 9 for custom printing and
outputs, use option 9 and specify, contact Otek.
including reverse scale (4-20=20-4),
bipolar and PID. Power consumption:
200mA@5VDC (1W). Accuracy & SEE CUSTOMIZED USER’S
Linearity: ±0.5% of full scale. MANUAL FOR SPECIFIC
CONNECTIONS AT:

http://www.otekcorp.com/
configurator/nts/

-8-