6. ELECTRIC PERFORMANCE :
Primary Voltage Secondary Voltage
6-1 Insulation Class : 17,5 kV 7,2 kV
6-2 Basic Impulse Level : 95 kV 60 kV
6-3 Applied Voltage Test During 1 Minute : 28 kV 20 kV
6-4 Induced Voltage Test : Apply 2 times of the rate voltage at 350 cycles per second for 18 second
o
6-5 Temperature Rise : The coil temperature rise measured by resistance method will not exceed 65 C
o
and the oil temperature rise will not exceed 60 C
6-6 Losses at Rated Voltage 11 / 0,4 kV
No Load Losses : 2.000 Watt Note : - HV Juction Box for IPB
Load Losses ( at 75 °C ) : 30.000 Watt - LV Juction Box for NSPB
Total Losses : 32.000 Watt
6-7 Efficiency at % Rated Capacity : 100 75 50 25 %
at P.F. = 1,0 : 98,43 98,76 99,06 99,23 %
6-8 Exciting Current / Off load Current at Nominal Voltage : 2,00 % Date of Approval :
6-9 Percent Impedance : 7,50 % PROPOSER :
6 - 10 Voltage Regulation at P.F. = 1,0 : 1,77 %
Voltage Regulation at P.F. = 0.8 : 5,73 % hp
0820/ENG/2016 - Af