Validation of Carpark & VRV Condenser Unit Ventilation Calculated by : Debasis Malick Date : 02.08.2016
Air volume
Air volume
Air-change rate requirement under Supply air quantity
Area Height Volume Air-change rate under requirement under
Parking Zone under fire standard for fan selection
(m2) (m) (m3) standard conditions fire conditions
conditions conditions (m3/s)
3
(m /s)
(m3/s)
Assumptions/Notes:
1. Carpark zone areas were measured directly from CFD fire simulation analysis on 28/07/2016 237.87
2. The above values only indicate the louver requirements for carpark & VRV condenser ventilation only. Malick, Debasis: 39.6453842593
3. Fan and shaft sizes will be based on air volume under fire conditions As per manufacturer
4. Intake louver area will be based on 2.5.m/s face velocity under standard conditions recommendations 85% 2 fan room
of the exhaust air
5. Exhaust Louver area requirement based on a 2.5m/s face velocity under standard conditions
quantity
6. Air volumes are approximate and to be further validated 4 fan room
7. Basement clear height is 3.8m (SSL to SSl is 4m and promenade level slab thickness is approximately 300mm)
8. Supply air quantity for basement carpark is @ 85% of carpark exhaust air quantity.
2.08.2016
148.5 47.5
251.2781513889
Malick, Debasis: 41.8796918981
As per manufacturer Option 1 Option 2
recommendations 85% 61 66
of the exhaust air
quantity
122 132
183 198
6.37m3/s each)
s. Fan second room @ 22.34 m3/s each)
sqm assuming a supply velocity of 10m/s