Академический Документы
Профессиональный Документы
Культура Документы
CHCK DS BSP/VL/10/078A/15/005/02/BE/07004
VOLTAS PROCESS DESIGN
CALCULATION OF DWTP CONT.DRG NO.
APVD AKR
DWMW/BSP/02/BE/07004
DATE 17.08.17
Velocity through each inlet channel under 50% overloading 0.784 m/s
Velocity through each inlet channel under 70% overloading 0.889 m/s
Velocity through each inlet channel under normal flow 0.523 m/s
Flocculator sizing
Flow Through each CLF under 70% overloading 935 m3/hr
Detention time in flocculator 30 min
Volume of flocculator required 467.5 m3
Liquid depth in flocculator 3.5 m
Plan area of flocculator required 133.57 m2
Plan area of Central column 0.801 m2
Total plan area of flocculator 134.37 m2
Dia of flocculator required 13.08 m
Page 1 of 3
THIS DOC./DRG IS CONFIDENTIAL AND IS THE PROPERTY OF VOLTAS LIMITED. IT MUST NOT BE DISCLOSED TO A THIRD PARTY, COPIED OR LENT WITHOUT THE WRITTEN CONSENT OF VOLTAS
LIMITED.
VOLTAS LIMITED VOLTAS DWG. NO.
PREP DH DWMW/BSP/02/BE/07004
DOMESTIC PROJECT GROUP
= 31.80 m3
Volume of Tube deck deducting loss of volume on account of 201.95 m3
Area required for tube deck 201.95 m2
Area provided for tube deck 201.95 m2
Height of media provided 1.00 m
Settling area of Tube Pack, corresponding to the inclination, 2221.46 m2
based on the effective volume of Tube Pack
Actual Settling rate on the horizontal projected area of Tube 0.42 m3/hr/m2
Pack
Page 2 of 3
THIS DOC./DRG IS CONFIDENTIAL AND IS THE PROPERTY OF VOLTAS LIMITED. IT MUST NOT BE DISCLOSED TO A THIRD PARTY, COPIED OR LENT WITHOUT THE WRITTEN CONSENT OF VOLTAS
LIMITED.
VOLTAS LIMITED VOLTAS DWG. NO.
PREP DH DWMW/BSP/02/BE/07004
DOMESTIC PROJECT GROUP
Q Discharge, m3/sec
A Area of the water flow in launder, m 2
Launder Width x launder wetted depth
n mannings constant, 0.013
A R = Wetted Area /Wetted Perimeter
P
S Slope
Flow into each launder 103.9 m3/hr
Width of launder considered 0.3 m
Length of the channel 4.4 m
Design flow for the channel 0.0289 m3/sec
Difference in elevation from launder highest and lowest 0.025 m
points
Slope available 0.00568
= 1 in 176
In flow 103.89 m3/hr
(LHS) 0.02886 m3/sec
Width of the trench (W) 0.3 m
Mannings coeff, n 0.013
Slope 1 in 176
Water depth (D) in the trench assumed to equate LHS 0.100 m
Page 3 of 3
THIS DOC./DRG IS CONFIDENTIAL AND IS THE PROPERTY OF VOLTAS LIMITED. IT MUST NOT BE DISCLOSED TO A THIRD PARTY, COPIED OR LENT WITHOUT THE WRITTEN CONSENT OF VOLTAS
LIMITED.