Author:
Revision: 0.00
Objective
IEEE bus systems are used by researchers to implement new ideas and concepts. This
technical note describes the details of the IEEE 30-bus system [1]. The system consists of
loads, capacitor banks, transmission lines, and generators. Figure 1 depicts a part of the
PSCAD model of the IEEE 30-bus system.
P+jQ
T15_23
P+jQ
Bus15
P+jQ
Bus18
Bus14
T15_18
T18_19
T14_15
T12_15
P+jQ
T12_14
Bus16
P+jQ
slack bus
Bus12
Synchronous T12_16
RRL
Condensor
Bus13 T12_13
RRL T16_17
#2
#1
Bus1
P+jQ
Bus4
Bus3
P+jQ
T1_3 T3_4
T1_2
T2_4 T4_6
T2_6
Bus2
T2_5
P+jQ
RRL
Each machine (generator) is represented as a voltage source where its source impedance is
set arbitrarily as 10 Ohms. Table 1 summarizes the characteristics of each source, with a
base of 100 [MVA] for per unitizing.
Transmission lines are modelled using the Bergeron model. Table 2 summarizes the
transmission line parameters.
Line
From R [pu/m] X [pu/m] B [pu/m]
To Bus
Bus
1 2 1.92E-07 5.75E-07 5.28E-07
1 3 4.52E-07 1.65E-06 4.08E-07
2 4 5.70E-07 1.74E-06 3.68E-07
2 5 4.72E-07 1.98E-06 4.18E-07
2 6 5.81E-07 1.76E-06 3.74E-07
3 4 1.32E-07 3.79E-07 8.40E-08
4 6 1.19E-07 4.14E-07 9.00E-08
5 7 4.60E-07 1.16E-06 2.04E-07
6 7 2.67E-07 8.20E-07 1.70E-07
6 8 1.20E-07 4.20E-07 9.00E-08
6 28 1.69E-07 5.99E-07 1.30E-07
8 28 6.36E-07 2.00E-06 4.28E-07
9 10 1.00E-09 1.10E-06 1.00E-09
9 11 1.00E-09 2.08E-06 1.00E-09
10 17 3.24E-07 8.45E-07 1.00E-09
10 20 9.36E-07 2.09E-06 1.00E-09
10 21 3.48E-07 7.49E-07 1.00E-09
10 22 7.27E-07 1.50E-06 1.00E-09
12 13 1.00E-09 1.40E-06 1.00E-09
12 14 1.23E-06 2.56E-06 1.00E-09
12 15 6.62E-07 1.30E-06 1.00E-09
12 16 9.45E-07 1.99E-06 1.00E-09
14 15 2.21E-06 2.00E-06 1.00E-09
15 18 1.07E-06 2.19E-06 1.00E-09
Validation
The PSCAD model was validated against the PSS/E power flow values from [1]. Table 4
depicts line and source power flow comparison.
PSS/E PSCAD
Bus
P [pu] Q [pu] P [pu] Q [pu]
1 2.609 -0.168 2.6070 -0.1530
2 0.400 0.500 0.3992 0.5167
5 0.000 0.369 0.0025 0.3868
8 0.000 0.371 -0.0000 0.4047
11 0.000 0.162 0.0004 0.1662
13 0.000 0.106 0.0009 0.1111
To
From Bus
Bus
1 2 1.732 -0.2130 1.7320 -0.2098
1 3 0.846 -0.0240 0.8442 -0.0128
2 4 0.426 0.0470 0.4253 0.0589
2 5 0.824 0.0180 0.8239 0.0142
2 6 0.603 0.0050 0.6026 0.0169
3 4 0.813 -0.0360 0.8116 -0.0408
4 6 0.715 -0.1760 0.7128 -0.1745
5 7 0.148 -0.1330 0.1469 -0.1465
6 7 0.377 -0.0300 0.3749 -0.0375
6 8 0.296 -0.0810 0.2947 -0.0990
6 28 0.186 0.0110 0.1861 0.0112
8 28 0.005 -0.0040 0.0052 -0.0045
9 10 0.277 0.0590 0.2776 0.0567
9 11 0.000 0.1620 0.0004 0.1662
10 17 0.053 0.0440 0.0531 0.0428
10 20 0.090 0.0370 0.0900 0.0362
10 21 0.157 0.0980 0.1574 0.0980
10 22 0.076 0.0450 0.0754 0.0450
12 13 0.000 0.1060 0.0009 0.1111
12 14 0.078 0.0220 0.0779 0.0227
12 15 0.177 0.0640 0.1771 0.0648
12 16 0.072 0.0340 0.0721 0.0335
14 15 0.016 0.0060 0.0159 0.0067
15 18 0.060 0.0160 0.0590 0.0157
15 23 0.050 0.0290 0.0503 0.0296
Set-up Instructions
Dependencies
New_IEEE_30_CT.pscx
Replace the voltage sources with detailed machine models for dynamic
analysis.
Update short circuit levels of each source to represent specific system
strengths.
Technical References
[1] Illinois Center for a Smarter Electric Grid. (2013). [Online]. Available FTP:
http://publish.illinois.edu/smartergrid/
[2] http://sas.ieee.ca/pesias/seminar_slides/IEEE_PES-IAS_Chapter_24_01_13.pdf
Appendix 1
The line resistances and reactances are provided in [1] for each line segment of the test
system. The following table lists the approximate line length of each segment, based on
typical line data (as listed in Table A-2).
Table A-1- Approximate line lengths based on typical line reactance values as shown in
Table A-2
24 25 57.3249 1.15E+02
25 26 66.2112 1.32E+02
25 27 36.4162 7.28E+01
27 29 72.3096 1.45E+02
27 30 105.0667 2.10E+02
29 30 78.9307 1.58E+02