Вы находитесь на странице: 1из 10

ANSIlIEEE

C57.109-1985

An American National Standard


IEEE Guide for
Transformer Through-Fault-Current Duration

Sponsor
Transformers Committee of the

Secretariat
Institute of Elec
National Electri

Approved June 23,1983


IEEE Standards Board

Ap
American M

Copyright 1985 by

The Institute of Electrical and Electronics Engineers, Inc


345 East 47th Street, New York, NY 10017, USA

No part of this publication m a y be reproduced in any form,


in an electwnic rehieVal system or ot&rwise,
without the prior written permission of the P M i a h e r .

Authorized licensed use limited to: ABB Inc. Downloaded on September 15,2010 at 01:11:15 UTC from IEEE Xplore. Restrictions apply.
Foreword
Foreword is not a part of ANSUIEEE C57.1091986, IEEE Guide for Transformer Through-Fault-Current Duration.)
ANSI C57.92-1962, American National Standard Guide for Loadiig Oil-Immersed Distribution and
Power Transformers (Appendix to ANSI C57.12 standards) was issued in 1962. The guide contained a
section entitled Protective Devices which provided information indicating the short-time thermal load
capability of oil-immersed transformers. That information, of articular interest to those responsible for
B
application of overcurrent protective devices for protection of transformers, is summarized as follows:
Times Rated
Time Current
2 s 25.0
10 s 11.3
30 s 6.3
60 s 4.75
5min 3.O
30 min 2.0

During the revision activities o C57.92 it became evident that Times Rated Current cap&-ility of
transformers as stated therein did not recognize the mechanical withstand considerations of transfor-
mers. Consequently,
removed and considered separately.
In 1978, following particular urging b Committee, a working group
was formed under the auspices of the the assignment to prepare a
guide that would document the thou of transformers in sufEcient
detail to facilitate CO
the product of that workin
Since its issue in 1978 VIEEE C57.12.oOb-1978 has
been incorporated in the Standard General Require-
ments for Liquid-Immerse rs. This guide supplements,
but does not in any way supersede, ANSI/IEE)ff(C57.12.@1980.

At the time it approved this standard, the C57 Committee had the following membership:

R E. Uptegraff, Jr, Chairman R L. Ensign, Vice Chairman


E
Chyanization R e p m s d Name of Representcrtive
Bonneville Power A m‘ o n . . . . .................................................. Vacant
Electric Light and Power Group ...................................................... N. Derwianka
R. L. Ensign
I. H. Koponen
B. F. Smith
E. F. Vlllesuso, Jr
J. P. Markey (AU)
Institute of Electrical and ElectroNca Engineers.. ...................................... J. V. Bonucchi
0. Compton
J. C. Dutton
L. w. Long
L S. McCormick
W.J. Neiswender
B. Stanleigh (AU)

Authorized licensed use limited to: ABB Inc. Downloaded on September 15,2010 at 01:11:15 UTC from IEEE Xplore. Restrictions apply.
Cbganhtion Repmsented Name of Rqmentutive
National Electrical Manufacturers Association ........... :. ............................. J. D. Douglaaa
W.C. Kendall
K. R. Linsley
W. J. McNutt
H. Robin
M. Sam@
R. E. Uptesraff, Jr
R. J. Stahara (A&)
Naval Facilities E n g i n e e m Command ................................................ H. P. Stickley
Rural ElechWcation Adminkmm'on ................................................... J. C. Arnold, Jr
Tennessee Valley Authority ........................................................... L. R. Smith
Underwriters Laboratories ............................................................ T. O'Grady
R. W. Seelbnch (Alt)
Water and Power Resources Service .................................................. F. W. Cook, Sr
Western Area Power AdmhMrah'on ................................................... D.R. T o r g e m n

At the time this guide was approved, the Working Group on Short Circuit Duration of the Perform-
ance Characteristics Subcommittee of the Transformers Committee had the following membership:
W. F. Grif'fard, Chairman
E. J. Adolphson C. G. Evans J. W. McGill
J. Alacchi D. A. GiUies C. J. McMfflen
E. H. Arjeski A. W. Gofdman W. J. McNutt
0.R. Compton C. H. Gril3n E. W. Schmunk
J. C. Dutton R. E. F. Troy
J. A. Ebert M. D. A. Yannucci
E. T.Jauch

At the time this guide was approved the ance Characteristics Subcommittee
were as follows:
0.R.
E. J. Adolphson L. S. McCormick
D. J. Allan C. J. McMillen
E. H. Arjeski W. J. McNutt
J. C. Arnold D. A. Roach
J. J. Bergeron L. J. Savio
J. D. Borst J. L. Harbell R. L. Schmid
E. Chitwood C. N. Hendrickson D. S. Takach
F. W. Cook E. L. Hook D. E. Truax
D. A. Duckett C. P. Kappeler S. G. Vargo
J. A. Ebert R. H. Kellogg R. A. Veitch
C. G. Evans J. R. Woodall
W. R. Farber W. E. Wrenn
S. L. Foster D. A. Yannucci

At the time the IEEE Standard Board approved this guide on June 23, 1983, it had the following
members:

James H. Beall, Chairmun Edward Chelotti, Vice Chairman


Sava I. Sherr, Secretary
J. J. Archambault Donald H. Heirman John P. Rigamti
John T. Boettger Irvin N. Howell, Jr FrankL.ROtW3
J. V. Bonucchi Joseph L. Koepfinger' Robert W. Seelbach
Rene Castenschiold Irving Kolodny Jay A. Stewart
Edward J. Cohen George Konomos Clifford 0.Swanson
Len S. Corey R. F. Lawrence Robert E. Weiler
Donald C. Fleckenstein John E. May W. B. Wilkens
Jay Forster Donald T. Michael' Charles J. Wylie

'Member Emeritus

Authorized licensed use limited to: ABB Inc. Downloaded on September 15,2010 at 01:11:15 UTC from IEEE Xplore. Restrictions apply.
Contents
SECI'ION PAGE
1. Scope .................................................................................. 7
2. Purpose ................................................................................. 7
3. General ................................................................................. 7
4. References .............................................................................. 7
5. Transformer Coordination Curves ......................................................... 8
5.1 Category I Transformers .............................................................. 8
5 2 Category 11 Transformers ............................................................. 9
53 Category III Transformers ............................................................. 10
5.4 Category IV Transformers ............................................................. 11
5.5 Recommended Duration Limit Summary ................................................ 11
FIGURES

Fig 1 Category I Transformers ............................................................. 8


Fig 2 Category 11 Transformers ............................................................ 9
Fig 3 Category III Transformers ........................................................... 10
Fig 4 Category IV Transformers ........................................................... 11
TABLE
Table 1 Minimum Nameplate Kilovoltamperes ............................................... 12

Authorized licensed use limited to: ABB Inc. Downloaded on September 15,2010 at 01:11:15 UTC from IEEE Xplore. Restrictions apply.
An American National Standud
IEEE Guide for
Transformer Through-Fault-CurrentDuration

1. scope the frequency of fault occurrence is high. The


point of transition between mechanical concern
and thermal concern cannot be precisely defined,
This guide applies to transformers referenced but mechanical effects tend to have a more
in ANSIlIEEE C57.12.00-1980[2] as Categories I, prominent role in larger kilovoltampere ratings,
11, III, and IV. because the mechanical stresses are higher.

4. References
2. Purpose

When the following American National Stand-


ards referred to in this guide are superseded by a
ion approved by the American National
Standards Institute, Inc, the latest revision shall
apply:

transformers that relate duration and fault magni- 111 ANSIIIEEE C37.91-1985,IEEE Guide for Pro-
tude to withstand capability. tective Relay Applications to Power Transfor-
This guide sets forth recommendations be- mers.
lieved essential for the application of overcurrent
protective devices applied to limit the exposure 121 ANSIlIEEE C57.12.00-1980, IEEE Standard
time of transformers to short-circuit current (see General Requirements for Liquid-Immersed Dis-
ANSIlIEEE C37.91-1985[l]). This guide tributtm, Power, and Regulating Transformers.
tended to imply overload capability.
[31 AlUSIlIEEE C57.91-1981, IEEE Guide for
Loading Mineral-Oil-Immersed Overhead and Pad-
Mounted Distribution Transformers Rated 500 kVA
3. General and Less with 65"C or 55 "CAverage Winding Rise.

[4]ANSIlIEEE C57.92-1982, IEEE Guide for


The magnitude and duration of fault current Loading Mineral-Oil-Immersed Power Transfor-
are of utmost importance in establishing a coor- mers up to and Including 100 MVA with 55°C or
dinated protection practice for transformers as 65°C Wmding Rise.
both the mechanical and thermal effects of fault
current should be considered. For fault-current [5]IEEE Std 766,IEEE Trial-Use Guide for Load-
magnitudes near the design capability of the ing Mineralail-Immersed Power Transformers
transformer, mechanical effects are more signifi- Rated in Excess of 100 MVA (65°C Winding
cant than thermal effects. At low, fault-current Rise).
magnitudes approaching the overload range, me-
chanical effects assume less importance unless These documents are availablefrom lEEE Senrice Cen-
ter, 446 Hoes Lane, Piscataway, NJ 08864. Copies of these
documents are also available from the Sales Department,
The numbers in brackets correspond to the numbers of American National Standards Institute, 1430 Broadway, New
the references in Section 4. York, NY 10018.

Authorized licensed use limited to: ABB Inc. Downloaded on September 15,2010 at 01:11:15 UTC from IEEE Xplore. Restrictions apply.
ANSIDEEE
C67.1091986 IEEE GUIDE FOR TRANSFORMER

5. Transformer Coordination Curves macent to current-carrying conductors, while


the dashed portion represents a total fault dura-
tion beyond which cumulative mechanical
For purposes of coordination of overcurrent damage may occur. The increasing significance of
protective devices, Figs 1, 2, 3, and 4 are pre- mechanical effects for higher kilovoltampere
sented as protection curves for different size transformers is reflected in these curves. The va-
transformers. For Categories I and IV, single lidity of these damage limit curves cannot be
curves apply which reflect both thermal and me- demonstratecl by test, since the effects are pro-
chanical damage considerations. For Categories gressive over the transformer lifetime. They are
I1 and HI, double curves apply, one of which re- based principally on informed engineering judg-
flects both thermal and mechanical damage con- ment and favorable, historical field experience.
siderations, while the other reflects primarily
thermal damage considerations. On curves which
have both a solid and a dashed portion, the solid 5.1 For Category I Transformers. The recom-
portion represents a total fault duration beyond mended duration limit is based on the curve of
which thermal damage may occur in insulation Fig 1. The curve reflects both thermal and me-

Fig 1
Category I Transformers

IO OOO IO 000

5000 5000

2000 2000

1000 1000

500 500

200 200

I 100 100
In c
In
n
g50 502
-s
VJ
W
8
c

E 20 20 yc-

CURRENT IN TIMES
NORMAL BASE CURRENT
02 (ANSVIEEE C57.12.00- -0.2
1- I211
0.1 0.1

TIMES NORMAL RASE CURRENT

Authorized licensed use limited to: ABB Inc. Downloaded on September 15,2010 at 01:11:15 UTC from IEEE Xplore. Restrictions apply.
ANSIDEEE
THROUGH-FAULTCURRENTDURATION C67.1091B6

chanical damage considerations and should be upon impedance of the transformer for fault cur-
applied as a protection curve for faults which rent above 70% of maximum possible and is
will occur frequently or infrequently. keyed to the 1% of the worskase mechanical
duty (maximum fault current for 2s).
5.2 For Category I1 Transformers. The recom-
mended duration limits depend upon fault fre- 5.2.2 The righGhand curve reflects primarily
quency and are based upon the curves of Fig 2. thermal damage considerations. It is not depend-
Fault frequency refers to the number of faults ent upon impedance of the transformer and may
with magnitudes greater than 70% of maximum. be applied as a protection curve for faults which
5.2.1 The left-hand curve, reflecting both ther- will occur only infrequently (typically not more
mal and mechanical damage considerations, than 10 in the life of a transformer). This curve
should be applied as a protection curve for faults also may be used for backup protection where
which will occur frequently (typically more than the transformer is exposed to frequent faults nor-
10 in the life of a transformer). It is dependent mally cleared by high-speed relaying.

1 - FOR FAULT CURRENT FROM 70% TO .I


100% OF MAXIMUM POSSIBLE:
P t = K
O.5 -WHERE . 0.5
Z = SYMMETRICAL FAULT CURRENT IN
TIMES NORMAL BASE CURRENT
02 - (ANSVIEEE C57.12.00-1980) ' 0.2
K = CONSTANT DETERMINED AT
MAXIMUM I WITH t = 2 SECONDS
0.1

Authorized licensed use limited to: ABB Inc. Downloaded on September 15,2010 at 01:11:15 UTC from IEEE Xplore. Restrictions apply.
ANSIlIEEE
CS7.1091986 IEEE GUIDE FOR TRANSFORMER

5.3 For Category I11 Transformers. The rec- keyed to the 1% of the worst-case mechanical
ommended duration limits depend upon fault fre- duty (maximum fault current for 2s).
quency and are based upon the curves of Fig 3.
Fault frequency refers to the number of faults 5.3.2 The righGhand curve reflects primarily
with magnitudes greater than 50% of maximum. thermal damage considerations. It is not depend-
5.3.1 The lef&hand curve, reflecting both ther- ent upon impedance of the transformer and may
mal and mechanical damage considerations, be appJied as a protection curve for faults which
should be applied as a protection curve €or faults will occur only infrequently (typically not more
which will occur frequently (typically more than than 5 in the life of a transformer). This curve
5 in the life of a transformer). It is dependent also may be used for backup protection where
upon impedance of the transformer for fault cur- the transformer is exposed to frequent faults nor-
rent above 60% of maximum possible and is mally cleared by high-speed relaying.

Fig 3
Category I11 Traneformers
'Thlscuwe may also be used for backup

r = SYMMETRICAL FAULT CURRENT IN


TIMES NORMAL BASE CURRENT

TIMES NORMAL BASE CURRENT

10

-~
ii

Authorized licensed use limited to: ABB Inc. Downloaded on September 15,2010 at 01:11:15 UTC from IEEE Xplore. Restrictions apply.
ANSIAEEE
THROUGH-FAULT-CURRENT
DURATION C67.1091986

5.4 For Category IV Transformers. The rec- and is keyed to the 1%of the worst-case mechan-
ommended duration limit is based upon the ical duty (maximum fault current for 2s).
curve of Fig 4. The curve reflects both thermal
and mechanical damage considerations and 5.5 Recommended Duration Limit Summary.
should be applied as a protection curve for faults Recommended duration limits designated for
which will occur frequently or infrequently. It is transformers given in ANSI/IEEE C57.12.00-1980
dependent upon impedance of the transformer [2] as Categories I, 11, 111, and IV are as given in
for fault current above 50%of maximum possible Table 1.

Fig 4
Category IV Transformers

5-
1 \ \\.i\,\ ~5
'\\ \ \ \
\\\\ \ ! \ '\

2.
\ \
\ \\ \ \ \\\\\\ \ -2
12 I 0 8 7 6 5 4
X TRANSFORMER IMPECUNCE
1 -FOR FAULT CURRENT FROM 50% TO -1
10046 OF MAXIMUM POSSIBLE:
Pt=K
05 -WHERE 0.5
I = SYMMETRICAL FAULT CURRENT IN
TIMES NORMAL BASE CURRENT
02 - (ANSIIIEEE C57.12.00-1980) ' 0.2
K = CONSTANT DETERMINED AT
MAXIMUM I WITH t = 2 SECONDS
-0 I
2 5 IO 20 50
TIMES NORMAL BASE CURRENT

11

Authorized licensed use limited to: ABB Inc. Downloaded on September 15,2010 at 01:11:15 UTC from IEEE Xplore. Restrictions apply.
ANSIWEE
C67.1091986

Table 1
Minimum Nameplate Kilovoltamperes
~ ~ ~____ ~ _ _ _ _ _ ______ ~~~

Reference
C*gw S i e Phase Three Phase Protection Curves.
I 6to500 16 to 500 Fig1
n 601 to 1667 601 to M)oo Fig2
III 1668tolOOOO 5001tO3OOOO Fig 3
N above 10 OOO above 30 OOO Fig4
'NOTE: In Figs 1 , 2 , 3 , and 4 the Times Normal Base Current Scale relates to minimum nameplate
kilovoltamperes. Low values of 3.5 or less Times Normal Base Current may result from overloads
rather than faults and for such cases,loading guides may indicate allowable time durations dflerent
from those given in Figs 1 through 4. See ANSIlIEEE C57.91-1981 [3] and ANSI/IEEE C67.92-1982 141.

Authorized licensed use limited to: ABB Inc. Downloaded on September 15,2010 at 01:11:15 UTC from IEEE Xplore. Restrictions apply.

Вам также может понравиться