Вы находитесь на странице: 1из 2

DESIGN OF 7 M DIA INTAKE WELL & PUMP HOUSE

----------------------------------------------------------------------------------------------------------------

Stress in Foundation Plug

Load of Intake well = 564,485 Kg

Add for plum concrete in uptoIL 313.0 for 3 m

x (3.5.2 – 22 ) x 3 x 2400 = 186.596 Kg

Total = 751,001 Kg

A =  (4.12 ) = 52.81 m2

I =  /4 (4.14 ) = 221.94 m4

Z = 54.13 m3

Gross SBC of soil = 12 + 1.6 x (16) = 37.6 T/m2

It may noted that we have not considered the friction load carrying capacity of 16 m
depth of soil and Intake Well wall which will be considerable and is on very much
conservatives side

751,001
6o = ------------ = 14,221 Kg/m2
52.81

307,274 + 351,190 + 236,335


6b = ------------------------------------- = 16,531 Kg/m2
54.13 ---------------------------
6 max 30,752 Kg/m2

i.e. 30,752< 37.6 T/m2Hence O K

Check for elastic condition of Soil


Refer Analysis and design of sub structure second revision by Swami Saran,
Eq no 9.29a and 9.29b on Pg no 486.

Cos 
K = [ --------------------------------------] 2
\/ Cos + \/ Sin ( + ) Sin

Cos 30 0.866
= [ -----------------------------------]2 = [ ---------------------]2 = 0.2973
\/Cos 20 + \/ Sin 50 x Sin 30 0.9694 + 0.6189

Cos  0.866
KP = [ ---------------------------------]2 = [ ------------------]2 = 6.104
\/ Cos  - \/ Sin + ) sin . 0.9694 - .6189

Refer Analysis and design of sub structure second revision by Swami Saran,
Eq no 9.30 and 9.31 on Pg no 486.

W - ’ p MB
1 = -------------- + ------- < q
A 2I

M 8948
P = ----- = -------------- = 180
r 49.8

A = π x 4.12 = 52.78 m2

7510 – 0.364 x 180 8948 x 8.2


1 = ------------------------ + ----------------
52.78 2 x 1288.5

= 141 + 28 =169kN /m2 <1.25 x qa(Refer on Pg no 549)

= 169 kN/m2< 470 kN/m2

W - ’ P MB
62 = ------------ - ------------
A 2I

= 141 –28> 0 i.e. no Tension O K