Академический Документы
Профессиональный Документы
Культура Документы
FIRESTOP PRODUCTS
TREMSTOP IA.................................................................................................... 24
Printed in U.S.A.
09/08 supercedes 08/07 ©2008 Carlisle Corporation
1
TWO PART II SEALING SYSTEM ™
PRECAUTIONS
Surfaces must be clean and free of moisture, contamination and For additional information contact:
foreign matter. Do not apply when rain or freezing temperatures
will occur within 72 hours. Do not apply where temperatures
will exceed 200ºF. Store DT Tape in DRY ATMOSPHERE. Keep
out of the reach of children. Review MSDS for complete safety
information prior to use. DO NOT use where acidic or alkaline
900 Hensley Lane
chemicals are present (ie., lab fume hood, vents, etc.)
Wylie, Texas 75098
For Industrial Professional Use Only. Phone: (800) 527-7092 FAX: (972) 442-0076
www.hardcast.com
1. HARDCAST recommends the use of our Two Part II Dispenser. When using the dispenser, the bottom guide roller is
submerged in the sealant. The coating control roller should be adjusted to apply a liberal coating of adhesive on the tape as
it emerges from the dispenser. Only DT-5300 and DT-5400 will fit the Two Part II Dispenser.
2. Pull the tape slowly through the dispenser so that it can absorb sufficient sealant and cut to the desired length. The easiest sizes
to handle are 12” to 18” lengths which can be overlapped on each other to form a continuous band around the duct.
3. Apply the tape to duct joint with the heavier coated side down and press firmly to ensure total contact with duct surface. Work
out any air bubbles entrapped under tape. Apply tape to surface immediately after coating with sealant.
4. Apply a top coat of RTA-50 sealant over the tape with a brush.
5. IF A TWO PART II DISPENSER IS NOT AVAILABLE, THE TAPE CAN BE APPLIED USING THE FOLLOWING METHOD:
Cut the tape to the desired (manageable) length and place it on a flat surface. Using a paintbrush apply sealant directly to
both sides of the tape then apply tape to duct joint.
6. Allow a minimum of 72 HOURS drying time before turning on the system (on interior duct only).
7. After the sealant has dried a minimum of 72 HOURS, on exterior duct apply an additional coat of RTA-50 to tape surface. Drying
time may take longer depending on temperature and relative humidity conditions.
CAUTION: Surface must be clean and free of moisture, contamination and foreign matter for best results. Do not apply when
rain or freezing temperatures will occur within 72 hours. Use only latex or epoxy based paints to cover Hardcast products.
CAUTION: If product freezes, return to room temperature and stir before use.
LEAKAGE TEST: Use smoke method only. Do not use soap and water for test.
RTA-50
LIQUID SEALANT
CAUTION
HARMFUL IF SWALLOWED OR INHALED
Avoid breathing vapors. Keep container closed when not in use. Use with adequate ventilation. Wash thoroughly after handling. If swallowed DO NOT INDUCE
VOMITING. Call a physician. Overexposure to vapors may cause respiratory irritation. If inhaled, remove to fresh air. If not breathing, give artificial respiration.
If breathing is difficult, give oxygen. Contact a physician immediately.
MAY CAUSE SKIN IRRITATION: Prolonged or repeated contact may cause drying, brittleness, cracking or irritation. Use of impervious gloves and clothing recom-
mended. Avoid contact with skin. May be irritating to sensitive skin. Wash thoroughly after handling. In case of contact with skin, remove contaminated clothing
and thoroughly wash affected area with soap and water. Do not use if skin is broken. If rash develops, discontinue use. Contact a physician if symptoms persist.
REVIEW MATERIAL SAFETY DATA SHEET FOR COMPLETE SAFETY INFORMATION PRIOR TO USE.
CONTAINS: ETHYLENE GLYCOL
601236
Printed in U.S.A.
09/08 supercedes 08/07 ©2008 Carlisle Corporation
3
TWO PART II SEALING SYSTEM™
The original, classic Hardcast DT Tape and sealant system invented by Hardcast now comes in this new, easy to
use system. The original tape is now in 150 foot lengths to fit this dispenser. The RTA-50 liquid sealant is available
in 1 gallon pails. The combination offers the same superior seam/joint sealing used for almost 40 years in an easy
to use, easy to maintain dispenser. Save time and money and still get the best duct seal ever invented, just follow
these instructions.
A. Remove Core Roller (1) by slightly D. Pull the tape through the the holder/frame G. Pull the amount of tape needed and cut
pulling on the sides of the holder/frame. towards and over the Tape Cutting Guide (4). with a razor cutter using the Tape Cutting
Insert the Roller into a roll of Hardcast Guide (4) or use scissors.
DT Tape. Replace the Roller with the E. Remove the lid from the Hardcast RTA-50
Tape into the holder/frame. sealant pail. Place the assembled Tape and H. Apply the sealant/coated tape over the
Dispenser in place of the lid and press the duct joint. Overlap the ends of the tape and
B. Guide the leading edge of the tape rim firmly to lock it to the pail. squeeze out air bubbles. Allow to cure as
down, between the the Fixed Coating directed on the sealant label.
Control Roller (2) and the Adjustable F. Adjust the amount of sealant applied to
Coating Control Roller (3). Pull the the tape by loosening the wing nuts of the I. When not in use, remove the Tape and
tape under and around the Bottom Tape Adjustable Coating Control Roller (3) and Dispenser assembly from the pail. Close it
Guide Roller (6). moving it towards the Fixed Coating Control tightly with it’s lid. Cut the tape where it is
Roller (2) until the tape is pressed against dry, use or discard the wet tape. Clean the
C. Pull the tape up and guide it back itself to create a squeegee effect. Move the Dispenser with water.
through the two Coating Control Rollers Adjustable Roller (3) away from (2) to leave
(2) & (3) and over the Adjustable Coat- more sealant on the tape. Tighten the wing
ing Control Roller (3). nuts when adjusted as desired.
TECHNICAL DATA
Color �������������������������������������������� Gray
IRON-GRIP 601 PART NUMBERS
Consistency ������������������������������� Heavy Brush On 1 Case w/ (25) 11 oz. Cartridges.................................304137
Base �������������������������������������������� Synthetic latex
Solvent ���������������������������������������� Water 1 Case w/ (4) 1-Gallon Pails........................................304135
Weight per Gallon ���������������������� 10.7 lbs. 1 - 5-Gallon Pail...........................................................304136
Solids Content ���������������������������� 63%
Viscosity ������������������������������������� >300K cps
Coverage (per gal.) �������������������� Up to 320 lin. ft. at 3” width, 20
mil thickness APPLICATION
Shore A Hardness ���������������������� >20 Apply to entire surface of duct joint
Flexibility ������������������������������������ Passes 1/4 in. mandrel bend
Time to Test �������������������������������� 48 hours* Temperature �������������������� 35°F. to 110°F. (1.7°C to 38°C.)
Service Temperature ������������������ -20°F to 200°F
Water Resistance ����������������������� Excellent Method ����������������������������� Brush, putty knife, caulk gun,
Mildew Resistance ��������������������� Mold & Mildew resistant trowel and spray
VOC ��������������������������������������������� 75 g/l (less water) Preparation ���������������������� Surface must be dry, dirt, oil, and
Pressure Classes ����������������������� SMACNA ½ , 1, 2, 3, 4, 6 and 10 grease free.
inches w.g.
Seal Classes ������������������������������� SMACNA A, B, C Rate ���������������������������������� Apply at joints and fasteners
Packaging ����������������������������������� 11 oz. cartridges, 20 mil thick wet film
1 gal., 5 gal. pails Clean Up Wet ������������������� Soap and water
Freeze/Thaw Stability ���������������� Passed 5 cycles
Specifications Compliance ��������� Passes ASTM C-731, ASTM Clean Up Dry ������������������� UN-TACK™ or Solvent
D-2202. USDA, EPA and FDA (Use safe handling practices.)
*May vary according to
temperature and humidity Approved. LEED compliant Painting ���������������������������� Only latex or epoxy paints
SCAQMD Rule 1168.
STORAGE
CAULKING AND SEALANTS Temperature �������������������� 35°F. to 110°F. (1.7°C to 44°C)
94PF DO NOT FREEZE
SURFACE BURNING CHARACTERISTICS
FLAME SPREAD....................................... 0 Shelf Life �������������������������� One year (unopened)
SMOKE DEVELOPED.............................. 0
*Applied to inorganic reinforced Cement Board *Tested as applied in Flammability �������������������� Non-flammable
one 3 in. (76.2 mm) wide strip, on center covering 16.7 percent of the
exposed test sample area) at a coverage of 80 sq. ft/ gal (2 sq. M/L).
Flash point of finished sealant, closed cup : No flash to boiling.
17NF
UL 181B-M
Mastic closure systems for use with flexible
duct systems or connectors.
Complia nt with
Indoor/Outdoor
ir ements Water Based Duct Sealant
LEE D Requ
FLEX-GRIP 550 is an all purpose, fiber-free, duct sealant for use on all types of metal duct, glass fiber
duct board, and flex duct, as well as duct fabric and flexible tubing runouts. Distinguished by its ability
to accomodate minor vibration and movement, FLEX-GRIP 550 stays flexible to save call-back labor.
FLEX-GRIP’s excellent coverage rates and easy spray and brush-on application provide low installed
cost while providing Hardcast’s proven reliability.
TECHNICAL DATA FLEX-GRIP 550 PART NUMBERS
Color �������������������������������������������� Gray
Consistency ������������������������������� Heavy Brush On/Spray Grade 1 Case w/ (25) 11 oz. Cartridges..............................304134
Base �������������������������������������������� Synthetic latex
1 Case w/ (4) 1-Gallon Pails.....................................304132
Solvent ���������������������������������������� Water
Weight per Gallon ���������������������� 10.7 lbs.
Solids Content ���������������������������� 63%
Viscosity ������������������������������������� >300K cps APPLICATION
Coverage (per gal.) �������������������� Up to 320 lin. ft. at 3” width, 20
mil thickness Temperature �������������������� 35°F. to 110°F. (1.7°C to 38°C)
Shore A Hardness ���������������������� >20 Method ����������������������������� Brush, putty knife, caulk gun,
Flexibility ������������������������������������ Passes ¼ in. mandrel bend trowel or spray.
Time to Test �������������������������������� 48 hours*
Preparation ��������������������� Surface must be dry, dirt, oil, and
Service Temperature ������������������ -20°F to 200°F
Water Resistance ����������������������� Excellent grease free.
Mildew Resistance ��������������������� Mold & Mildew resistant Rate ���������������������������������� Apply at joints and fasteners 20
VOC ��������������������������������������������� 75 g/l (less water) mil thick wet film
Pressure Classes ����������������������� SMACNA ½ , 1, 2, 3, 4, 6 and 10
Clean Up Wet ������������������ Soap and water
inches w.g.
Seal Classes ������������������������������� SMACNA A, B, C Clean Up Dry ������������������� UN-TACK™ or Solvent
Packaging ����������������������������������� 11 oz. cartridges & 1 gallon pails. (Use safe handling practices.)
Freeze/Thaw Stability ���������������� Passed 5 Cycles
Painting ��������������������������� Only latex or epoxy paints
Specifications Compliance ��������� Passes ASTM C-731, ASTM
D-2202. USDA, EPA and FDA STORAGE
*May vary according to Approved. LEED compliant Temperature �������������������������35°F. to 110°F. (1.7°C to 44°C)
temperature and humidity SCAQMD Rule 1168. DO NOT FREEZE
Shelf Life ������������������������� One year (unopened)
CAULKING AND SEALANTS Flammability ������������������� Non-flammable
94PF
SURFACE BURNING CHARACTERISTICS
FLAME SPREAD....................................... 0
SMOKE DEVELOPED.............................. 0
*Applied to inorganic reinforced Cement Board *Tested as applied in
one 3 in. (76.2 mm) wide strip, on center covering 16.7 percent of the
exposed test sample area) at a coverage of 80 sq. ft/ gal (2 sq. M/L).
Flash point of finished sealant, closed cup : No flash to boiling.
17NF
UL 181B-M
Mastic closure systems for use with flexible
duct systems or connectors.
t with Indoor/Outdoor
C omplian
LEED Requir
e ments Water Based Duct Sealant
SPRAY-SEAL is an all purpose sealant for use on all types of metal duct, glass fiber duct board, and flex
duct, as well as duct fabric and flexible tubing runouts. Distinguished by its ability to accomodate minor
vibration and movement, SPRAY-SEAL stays flexible without cracking which saves call-back labor.
SPRAY-SEAL’s excellent coverage rate and easy spray application provide low installed cost while
providing Hardcast’s proven reliability.
TECHNICAL DATA SPRAY-SEAL PART NUMBERS
Color �������������������������������������������� Gray
Consistency ������������������������������� Spray Grade 1 - 5-Gallon Pail........................................................304133
Base �������������������������������������������� Synthetic latex
Solvent ���������������������������������������� Water
Weight per Gallon ���������������������� 11.3 +/- .3 lbs. (5.126 +/- .126 kg) APPLICATION
Solids Content ���������������������������� 67% +/- 2
Temperature �������������������� 40°F to 110°F (4.4°C to 38°C)
Viscosity ������������������������������������� >60 +/- 10K cps
Coverage (per gal.) �������������������� Up to 320 lin. ft. at 3” width, Method ����������������������������� For spray, use Hardcast Sealant
Delivery System
20 mil thickness
Flexibility ������������������������������������ Passes ¼ in. mandrel bend Preparation ��������������������� Surface must be dry, dirt, oil, and
@ -25°F (-31.6°C) grease free.
Time to Test �������������������������������� 48 hours* Rate ���������������������������������� Apply at joints and fasteners 20-
Service Temperature ������������������ -20°F to 200°F (28.8°C to 93.3°C) 30 mil thick wet film
Water Resistance ����������������������� Excellent Clean Up Wet ������������������ Soap and water
Mildew Resistance ��������������������� Mold & Mildew resistant Clean Up Dry ������������������� UN-TACK™ or Solvent
VOC ��������������������������������������������� 52 g/l (Use safe handling practices.)
Pressure Classes ����������������������� SMACNA ½, 1, 2, 3, 4, 6 and 10 inches w.g. Painting ��������������������������� Only latex or epoxy paints
Seal Classes ������������������������������� SMACNA A, B, C
Packaging ����������������������������������� 5 gallon (18.9 liter) pails STORAGE
Freeze/Thaw Stability ���������������� Passed 5 Cycles Temperature �������������������� 35°F to 110°F (1.7°C to 44°C)
Specifications Compliance ��������� Passes ASTM C-731, ASTM DO NOT FREEZE
D-2202. USDA, EPA and FDA Shelf Life ������������������������� One year (unopened)
*May vary according to Approved. LEED compliant
temperature and humidity
SCAQMD Rule 1168. Flammability ������������������� Non-flammable
PRECAUTIONS
For additional information contact:
Surface must be clean and free of moisture, contamination and
foreign matter. Do not allow this product to freeze. Apply when
temperatures will not fall below freezing for at least 36-48 hours,
depending on temperature and humidity. Do not apply this product
where temperatures will exceed 200°F. Keep out of the reach of
children. Review MSDS for complete safety information prior to use. 900 Hensley Lane
DO NOT use where acidic or alkaline chemicals are present (ie., lab Wylie, Texas 75098
fume hood, vents, etc.)
Phone: (800) 527-7092 FAX: (972) 442-0076
For Industrial Professional Use Only. www.hardcast.com
601240
Printed in U.S.A.
09/08 supercedes 08/07 ©2008 Carlisle Corporation
9
DUCT-SEAL 321
™
t with
C omplian
e ments
LEED R equir
17NF
UL 181B-M
Mastic closure systems for use with flexible
duct systems or connectors.
A versatile, all purpose duct sealant for use on all types of metal duct, glass fiber duct board,
and flex duct, as well as duct fabric and flexible tubing runouts. CCWI 181 incorporates a built-
in polyester reinforcement for exceptional strength, with UV inhibitors for outdoor use. UL
181A-M listed / UL 181B-M listed.
TECHNICAL DATA CCWI-181 PART NUMBERS
Color �������������������������������������White & Gray
Consistency �������������������������Heavy textured 1 Case w/ (25) 11 oz. Cartridges (White)....................304142
Base ��������������������������������������Synthetic latex 1 Case w/ (25) 11 oz. Cartridges (Gray)......................304146
Solvent ����������������������������������Water 1 Case w/ (4) 1-Gallon Pails (White)...........................304144
Weight per Gallon ���������������11.6 lbs. 1 Case w/ (4) 1-Gallon Pails (Gray)............................304148
Solids Content ���������������������70%
1 - 2-Gallon Pail (White)..............................................304143
Viscosity �������������������������������Thixotropic
1 - 2-Gallon Pail (Gray)...............................................304147
Coverage (UL 181 A-M) �������Apply 18 mil, scrim, addt. 18 mil
(UL 181 B-M) �������Approximately 214 to 320 lin. ft. per gal. at 1 - 5-Gallon Pail (White)..............................................304145
20 to 30 mil wet film thickness at 3” width. 1 - 5-Gallon Pail (Gray)...............................................304149
Shore A Hardness ����������������>20
Flexibility ������������������������������Passes ¼ inch mandrel bend APPLICATION
Time to Test ��������������������������48 hours* Temperature �����������������35°F. to 110°F. (1.7°C to 44°C)
Service Temperature �����������-20°F to 200°F Method �������� �����������������Brush, putty knife, caulk gun, pump
Mildew Resistance ���������������Mold & Mildew resistant Preparation � �����������������Surface must be dry, dirt, oil, and
VOC ���������������������������������������45 g/l (less water)
grease free.
Surface Burning �������������������Flame Spread...............................0
Rate (UL 181 A-M): �������Apply 18 mil, scrim and 18 mil over scrim.
Smoke Developed........................0
(UL 181 B-M): ������Approx. 214 to 320 lin. ft. per gal. at 20
(When tested in accordance with ASTM E84, UL 723)
to 30 mil wet film thickness at 3” width.
Pressure Classes �����������������SMACNA ½ , 1, 2, 3, 4, 6 and 10 inches w.g.
Seal Classes �������������������������SMACNA A, B, C Clean Up Wet ����������������Soap and water
Packaging �����������������������������11 oz. cart.; 1, 2 & 5 gal. pails Clean Up Dry ����������������UN-TACK™ or Solvent
(Use safe handling practices.)
Freeze/Thaw Stability ����������Passed 5 Cycles
Specification Compliance ���Passes ASTM C-731, D-2202 USDA, Painting ������� �����������������Only latex or epoxy paints
EPA & FDA Approved. LEED compliant Ductboard...................... Scrim required for UL 181A-M
*May vary according to
temperature and humidity SCAQMD Rule 1168. STORAGE
Temperature ������������������35°F. to 110°F. (1.7°C to 44°C)
Underwriters Laboratories Inc.® DO NOT FREEZE
LISTED
17NF Shelf Life ����� �����������������One year (unopened)
UL 181A-M Flammability �����������������Non-flammable
FOR USE WITH U.L. LISTED RIGID
FIBERGLASS AIR DUCTS OR CONNECTORS.
UL 181B-M
FOR USE WITH U.L. LISTED FLEXIBLE
AIR DUCTS OR CONNECTORS
Printed in U.S.A.
09/08 supercedes 08/07 ©2008 Carlisle Corporation
11
SURE-GRIP 404
™
t with
Solvent Based Duct Sealant
C omplian
e ments
LEED Requir
SURE-GRIP 404 is a fiber-free, solvent based, synthetic rubber duct sealant. It’s exceptional strength,
fast drying time, and unmatched flexibility make it ideal for those applications requiring a solvent based
sealant. SURE-GRIP’s low viscosity, no-drip, no-string formulation allows fast application for labor
savings and extended coverage for lower installed cost.
FLAME SPREAD...................................10
SMOKE DEVELOPED............................5
*Tested as applied in two 1/4 inch wide strips 8 inches on center at a coverage of 320
lin.ft./gal. Flash point of finished adhesive, closed cup: less than minus 14OC.
17NF
UL 181B-M
Mastic closure systems for use with flexible
duct systems or connectors.
A cold applied, non-hardening, fire retardent seam sealant for use in rectangular, longitudinal, Pittsburgh™,
snap-lock or similar metal duct seams. COLD-SEAL will not string, saving equipment cleanup labor. In
addition, COLD-SEAL resists drying in equipment hoses, avoiding costly replacement.
TECHNICAL DATA
COLD-SEAL PART NUMBERS
Color �������������������������������������������� Gray
Consistency ������������������������������� Heavy Viscous 1 - 5-Gallon Pail...........................................................302022
Base �������������������������������������������� Synthetic Rubber 1 - 55-Gallon Drum......................................................302023
Solvent ���������������������������������������� Mineral Spirits
Weight per Gallon ���������������������� 9.7 lbs.
Solids Content ���������������������������� 86 %
APPLICATION
Viscosity ������������������������������������� Thixotropic
Coverage ������������������������������������ 1550 linear ft./gal., 1/8 in. bead Temperature �����������������������35°F. to 90°F. (1.7°C. to 32°C.)
Flexibility ������������������������������������ Excellent Method �������������������������������Graco, Binks or Lockformer;
Time to Test �������������������������������� Immediately 1
/8 in. orifice
Service Temperature ������������������ -30°F. to 200°F. Preparation ������������������������Surface must be dry, dirt, oil,
Surface Burning* ������������������������ Flame Spread....................0 and grease free.
Smoke developed..............5 Rate ������������������������������������Apply 1/8 in. bead to seams prior
Water Resistance ����������������������� Excellent to closing
Mildew Resistance ��������������������� Excellent
Clean Up ����������������������������UN-TACK™ or Solvent
VOC ��������������������������������������������� 198 g/l (Use safe handling practices.)
Pressure Classes ����������������������� SMACNA ½ , 1, 2, 3, 4, 6 and 10
inches w.g. STORAGE
Seal Classes ������������������������������� SMACNA A, B, C Temperature �����������������������35°F. to 90°F. (1.7°C. to 32°C.)
Packaging ����������������������������������� 5 gal. and 55 gal. Shelf Life ����������������������������One year (unopened)
Freeze/Thaw Stability ���������������� Excellent
Flammability ����������������������Combustible. Flash Point 150°F
Specification Compliance ����������LEED compliant SCAQMD
(Tcc). Store according to local
Rule 1168. codes.
*When tested in accordance with ASTM E84
PRECAUTIONS
601251
Printed in U.S.A.
09/08 supercedes 08/07 ©2008 Carlisle Corporation
13
AB-151 Scrim
HVAC/Construction Scrim
AB-15-Scrim is an all purpose self-adhering fiberglass ductwork scrim primarily used for temporary
fixation of ductwork prior to sealant application. For use with UL 181 Listed applications.
TECHNICAL DATA
AB-151 Scrim PART NUMBER
Average net weight..............................1.6 (oz./yd²)
1 Case w/ (10) 3” x 150’ Rolls...................................310553
Cross directional strength..................104.8 (lbs./in.)
Treatment % on fabric.........................22.5%
Thicknes ...............................................007 in. Method ���������������������� Cut desired length, peel off release liner,
apply. Overlap at ends. Rub down with
Packaging............................................3” X 150’; 18 rolls per case heavy pressure to assure complete
contact.
STORAGE
Temperature ������������� 35°F. to 110°F. (1.7°C to 44°C)
PRECAUTIONS
For additional information contact:
Surface must be clean and free of moisture, contamination and
foreign matter. Do not allow this product to freeze. Do not apply
this when rain or freezing temperatures will occur within 36 hours.
Do not apply this product where temperatures will exceed 200°F.
Keep out of the reach of children. Review MSDS for complete
900 Hensley Lane
safety information prior to use. DO NOT use where acidic or alkaline
Wylie, Texas 75098
chemicals are present (ie., lab fume hood, vents, etc.) Phone: (800) 527-7092 FAX: (972) 442-0076
For Industrial Professional Use Only. www.hardcast.com
t with
All Purpose Rolled Sealant
C omplian
em ents
LEED R equir
ALL-PURPOSE is a pressure sensitive, 30-year cycle, duct joint and general purpose rolled sealant.
ALL-PURPOSE provides an instant aggressive grip to most surfaces including sheet metal, duct board,
and flex duct for indoor applications. The GRAY MATTER™ butyl adhesive/sealant is a 100% solids
sealant, which stays flexible and does not release from the substrate.
TECHNICAL DATA
ALL-PURPOSE 1602 PART NUMBERS
Appearance................................... White fabric substrate with gray
adhesive/sealant 1 Case w/ (24) 2” x 50’ Rolls.....................................304086
Backing.......................................... DuPont Sontara® polyester 1 Case w/ (16) 3” x 50’ Rolls.....................................304087
1 Case w/ (12) 4” x 50’ Rolls.....................................304088
Thickness...................................... 25 mils
1 Case w/ (8) 6” x 50’ Rolls.......................................304089
Sealant Material............................. Modified Butyl
1 Case w/ (4) 12” x 50’ Rolls.....................................304085
Peel Strength................................. 17 lbs. per linear inch
Tensile Strength............................ 790 psi avg.
Elongation...................................... 560% avg. APPLICATION
Temperature............... 35°F. to 110°F. (1.7°C. to 44°C.)
Flexibility....................................... Excellent, no cracking
Method........................ Cut desired length, peel
Bonding Time................................ Immediate aggressive grip, full
off release liner, and apply.
bond 24 hours (Removal or repositioning may
Time to test.................................... Immediate damage AP-1602 and surface.)
Overlap at ends. Rub down with
Service Temperature..................... -20°F. to 200°F.
heavy pressure to assure complete
Surface Burning............................ Flame Spread:................. 15 contact.
Smoke Developed:.......... 15 Preparation................. Surface must be clean and dry, oil
(When tested in accordance with ASTM E-84) and grease free.
Water Resistance.......................... Excellent. Surface must be dry Clean Up..................... UN-TACK™ or Solvent
before application (Use safe handling practices.)
Mildew Resistance........................ Mold and mildew resistant. Painting....................... Use epoxy or water based paint
or coating. Use weatherized paint
VOC................................................ 0 g/l when applied on exterior surfaces.
Pressure Classes.......................... SMACNA ½ , 1, 2, 3, 4 and 6 in. w.g.
STORAGE
Seal Classes.................................. SMACNA A, B, C
Temperature............... 35°F. to 110°F. (1.7°C. to 44°C.)
Packaging...................................... 50 ft. rolls in 2, 3, 4, 6 & 12 inch
widths. 200 sq. ft. per case. Shelf Life..................... 24 months
Flammability............... Non-flammable
Specifications Compliance.......... LEED compliant SCAQMD
Rule 1168
601246
Printed in U.S.A. 09/08 supercedes 08/07 ©2008 Carlisle Corporation
15
ALUMA-GRIP 701
™
PRECAUTIONS
For additional information contact:
Surfaces must be clean and free of moisture and contamination. Do
not apply this product in areas where temperatures will exceed 200°F.
Keep out of the reach of children. Review MSDS for safety informa-
tion prior to use. DO NOT use where acidic or alkaline chemicals are
present (ie., lab fume hood, vents, etc.)
900 Hensley Lane
For Industrial Professional Use Only. Wylie, Texas 75098
Phone: (800) 527-7092 FAX: (972) 442-0076
www.hardcast.com
FOIL-GRIP 1402 is a pressure sensitive, 40-year cycle, duct joint and general purpose rolled sealant.
It provides an instant water resistant grip to most surfaces including sheet metal, duct board, flex duct,
PVC coated duct, and duct wrap vapor barriers. FOIL-GRIP 1402 is suitable for subgrade application
on PVC coated duct.
*Tested in two 3 inch (76 mm) wide longitudinal strips 8 inches (203 mm)
on center. (Tape coverage: 30% of the exposed test sample area.)
601245
Printed in U.S.A. 09/08 supercedes 08/07 ©2008 Carlisle Corporation
17
FOIL-GRIP 1403-181BFX
™
C omplian
t with Indoor/Outdoor Rolled Sealant
e ments
LEED Requir
FOIL-GRIP 1403-181BFX is a UL 181B-FX listed pressure sensitive, 40-year cycle, duct joint and general
purpose rolled sealant. FOIL-GRIP 1403-181BFX provides an instant water resistant grip to most
surfaces including sheet metal, duct board, flex duct, PVC coated duct, and duct wrap vapor barriers.
FOIL-GRIP 1403-181BFX is suitable for subgrade application on PVC coated duct.
TECHNICAL DATA
FOIL-GRIP 1403-181BFX
Appearance............................. Mill finish aluminum substrate with
butyl adhesive/sealant
PART NUMBERS
Backing.................................... Aluminum 1 Case w/ (24) 2” x 100’ Rolls.....................................309781
Thickness................................ 17 mils 1 Case w/ (16) 3” x 100’ Rolls.....................................309780
Sealant Material........................ Modified Butyl
Peel Strength........................... 7 lbs. per linear inch
Tensile Strength...................... 20 pli/1400 psi avg. APPLICATION
Flexibility................................. Excellent, no cracking Temperature............... 35°F. to 110°F. (1.7°C. to 44°C.)
Bonding Time.......................... Instant high tack, full bond 24 hours
Method........................ Cut desired length, peel off release liner,
Time to Test............................. Immediate apply. Removal or repositioning may
Service Temperature............... -20°F. to 200°F. damage FOIL-GRIP 1403-181BFX
Weather Resistance................ Passes 2000 hours QUV and surface. Overlap at ends. Rub
(When tested in accordance with ASTM G-53) down with adequite pressure to assure
Mildew Resistance.................. Mold and mildew resistant complete contact.
VOC.......................................... 0 g/l Preparation................. Surface must be clean and dry, oil
Pressure Classes.................... SMACNA ½, 1, 2, 3, 4, & 6 in. w.g. and grease free.
Seal Classes............................ SMACNA A, B, C Clean Up..................... UN-TACK™ or Solvent
Packaging................................ 100 ft. rolls in 2 & 3 inch widths; (Use safe handling practices.)
400 sq. ft. per case. Painting....................... Use paint appropriate for aluminum.
Specifications Compliance.... LEED compliant SCAQMD
Rule 1168 STORAGE
Temperature............... 35°F. to 110°F. (1.7°C. to 44°C.)
GENERAL USE TAPES
773S Shelf Life..................... 24 months
SURFACE BURNING CHARACTERISTICS
APPLIED to INORGANIC
Flammability............... Non-flammable
REINFORCED CEMENT BOARD+
FLAME SPREAD............................................... 0
SMOKE DEVELOPED....................................... 5
+Tested as applied in one 50.8 (2 in.) wide strip on center.
(Tape coverage: 11.1 percent of the exposed test sample area).
181B-FX
17NF
PRESSURE SENSITIVE TAPES FOR USE WITH
FLEXIBLE AIR DUCTS FOR CLASS 1 DUCT
PRECAUTIONS
For additional information contact:
601252
Printed in U.S.A. 09/08 supercedes 08/07 ©2008 Carlisle Corporation
19
SILIMAX
®
• Color: Red
pg. 1 of 2
Printed in U.S.A.
09/08 supercedes 08/07 ©2008 Carlisle Corporation
21
SILIMAX
®
pg. 2 of 2
Printed in U.S.A.
09/08 supercedes 08/07 ©2008 Carlisle Corporation
23
TREMstop IA
Intumescent Acrylic Firestopping Sealant
TREMstop IA
Printed in U.S.A.
09/08 supercedes 08/07 ©2008 Carlisle Corporation