ENGINREERING ASSESSMENT REPORT

NAME OF THE PROJECT:


EXISTING SINGLE STORIED WASTAGE GODOWN STEEL SHED AT
MOMINNAGAR, GORAI, MIRZAPUR, TANGAIL DHAKA
NAME OF THE CLIENT
Uniglory Packaging Industries Ltd.

VOLUME 1 OF 2

Date of Submission: 05.02.18 Submitted By:

Name of the Submitting Engineer

Engr. Abdul Quddus


DESIGN & DEVELOPMENT SOLUTION
B.Sc. Engg(Civil, BUET),
Lane #23, House-#160, Ground Floor, New DOHS,
DMINB/CE-0231 Mohakhali, Dhaka-1206,
MIEB-21384 Mobile: +8801718612966,
E-mail: quddus_ce@yahoo.com
Web: www.ddslt.com
Lane #23, House-#160, Ground Floor, New DOHS,
Mohakhali, Dhaka-1206,
Mobile: +8801718612966,
E-mail: quddus_ce@yahoo.com
Web: www.ddslt.com

TABLE OF CONTENT

Sl No Description
1.0 Introduction
2.0 Scope of Work
3.0 Methodology
4.0 Structural Design Concept and criteria
4.1 Codes and Standards
4.2 General Load Data
4.3 Load applied on structure
4.4 Load Combination
4.5 Materials Data
4.6 Analysis Method and Software Used.
5.0 Structural adequacy check
6.0 Conclusion & Recommendation
Attached documents
A2 As-Built Drawing
A3 Retrofitting Drawing
Lane #23, House-#160, Ground Floor, New DOHS,
Mohakhali, Dhaka-1206,
Mobile: +8801718612966,
E-mail: quddus_ce@yahoo.com
Web: www.ddslt.com

1.0) INTRODUCTION
Existing single storied wastage godown shed for Uniglory Packaging Industries Ltd. Located at
MOMINNAGAR, GORAI, MIRZAPUR, TANGAIL, DHAKA has been analyzed for different loading
conditions & different load combinations accordingly. This report summarizes the analysis and
design related data

2.0) SCOPE OF WORK


The design work of this Project has been carried out following the design criteria and Bangladesh National
Building Code (BNBC). The scope of the work is as follows-

 Arranged As-Built Drawing.


 Analysis & comments on existing structure

Produced retrofitting drawing where required

3.0) WORK METHEDOLOGY


Based on the supplied Architectural Drawing, field measurement we, DESIGN & DEVELOPMENT SOLUTION
(DDS)” developed a computer analysis model and carried out complete analysis of the structure incorporating
various design data as per Bangladesh National Building Code (BNBC). Loading values is considered as
prescribed in BNBC. Strength parameter of steel is considered 50ksi. The results obtained from computer
model analysis were checked against relevant specifications and hand calculations. Finally, the design data is
compared with the As Built drawing of this structure. If it is satisfied then the structure is safe and sound,
otherwise additional treatment is provided for further uses.

4.0) STRUCTURAL DESIGN CONCEPT & CRITERIA


The structural element has been designed and considering the following criteria.

4.1) CODES AND STANDARDS


1) Bangladesh National Building Code (BNBC)-2006
2) American Institute of steel construction (AISC)
3) American Society for Testing Materials (ASTM)
Lane #23, House-#160, Ground Floor, New DOHS,
Mohakhali, Dhaka-1206,
Mobile: +8801718612966,
E-mail: quddus_ce@yahoo.com
Web: www.ddslt.com

4.2) GENERAL LOAD DATA

Dead Load:
Dead load is the vertical load due to the self-weight of the permanent structural and non-structural component of
a building, e.g. Foundation, column, rafters, deck, steel joists, purlins, walls, ceilings, permanent partitions and
fixed service equipment.

Unit weight of materials and the calculation of design dead loads are according to section-2.2, Chapter-2, part-
6, BNBC-Page6-22

Live Load:
Live load is the load superimposed by the use or occupancy of the building not including the environmental
loads such as wind load, rain load, earthquake load or dead load. (Ref. BNBC, Part-6, Chapter-2, Sec-2.3.2)

But it should be not less than the minimum floor live load. (Ref. BNBC, Part-6, Chapter-2, Sec-2.3.3)
Lane #23, House-#160, Ground Floor, New DOHS,
Mohakhali, Dhaka-1206,
Mobile: +8801718612966,
E-mail: quddus_ce@yahoo.com
Web: www.ddslt.com

Wind Load:
The calculation of wind load confirms the sub-clause 2.4, Chapter 2, Part-6 of BNBC. The following equation
has been used to calculate sustained wind pressure of the structure.

Pz=CgCpCcCiCzVb2 [BNBC, 2.4.6.2,2.4.6.3 Page-6-33,6-34]

Wind load was applied in two orthogonal directions X and Y.


GARBAGE SHED
Dead Load, DL (sheeting)= 2 psf
Dead Load, DL (purlin)= 1.5 psf
Live Load, LL= 20 psf
BASIC WIND SPEED DATA
Select your Location
Tangail 160
Building Dimension Data
B 77.52 Feet
L 104.64 Feet
Height (h) 24.0014 Feet

Roof Slope (theta) 6 degree

47.2*10^-
Cc 6
Ci 1
Cz 0.451

Exposure Category A
qz 0.545

Cg 1.556
Pz 0.84802 Cpe
wind load on wall
Winward wall Pressure 14.0975 Psf
Leeward Wall Pressure -7.5779 Psf
Side wall Pressure -12.335 Psf
Wind load on roof (windward uplift)
h/l 0.2293712
THETA
theta 6 THETA 1 1
0 10
h/L 1 0.1 -0.7 -0.9
h/L 2 0.3 -0.7 -0.9
Lane #23, House-#160, Ground Floor, New DOHS,
Mohakhali, Dhaka-1206,
Mobile: +8801718612966,
E-mail: quddus_ce@yahoo.com
Web: www.ddslt.com

OUR H/L 0.2293712 -0.7 -0.9 -0.82


THETA 6
Winward roof -14.45 Psf
Leeward Roof -12.34 Psf
h/b 0.23 cpe(parallel toridge)
0.7
Parallel to ridge Pressure 12.3353 Psf
Wind load on roof (windward downward)
h/l 0.2293712
THETA
theta 6 THETA 1 1
0 10
h/L 1 0.1 -0.7 0.2
h/L 2 0.3 -0.7 0.2
OUR H/L 0.2293712 -0.7 0.2 -0.16
THETA 6
Winward roof -2.82 Psf
Leeward Roof -12.34 Psf
h/b 0.31 cpe(parallel toridge)
0.7
Parallel to ridge Pressure -12.335 Psf

Earth quake Load:


As per specifications of BNBC, Part-6, Chapter-2, section-2.5.51, Equivalent Static Force Method can be
applied to calculate the earth quake force of this structure.
Design Base Shear, V=ZICW/R (Ref. Sec2.5.6.1, Chapter-2, Part-6, BNBC)

Where,
Z=Seismic Zone coefficient factor,
I=Importance factor,
C=Numerical Co-efficient,
R=Response Modification factor,
Lane #23, House-#160, Ground Floor, New DOHS,
Mohakhali, Dhaka-1206,
Mobile: +8801718612966,
E-mail: quddus_ce@yahoo.com
Web: www.ddslt.com

4.3) LOAD APPLIED ON STRUCTURE

Dead Load:
i. Self-weight of structure.

Live Load:

i. Live load on roof=0.5KN/m2


Wind Load:
i. Basic wind speed, Vb=160Km/h
ii. Exposure Type=A
iii. Importance factor, I=1.0

Wind load was applied in two orthogonal directions X and Z.

Seismic Load:
i. Seismic Zone coefficient factor, Z=0.15( Zone-02)
ii. Importance factor, I = 1.0
iii. Response Modification factor, R=6
iv. Site co-efficient, S=1.5

Earth quake load was applied in two orthogonal directions X & Z.

4.4.1 Load Symbol


a) DL = Dead Load ~ self-weight of structure , roof sheet & purlin weight, chequered plate
weight
b) LR = Roof live load
c) WL = Wind Load
d) EQ = Earthquake Load

4.4.2 Load Combination (Alliance Standard)


 1.2DL +0.5Lr
 1.2DL+0.5 Lr +1.3WL
 1.2DL+0.5Lr+1.5EQ
Lane #23, House-#160, Ground Floor, New DOHS,
Mohakhali, Dhaka-1206,
Mobile: +8801718612966,
E-mail: quddus_ce@yahoo.com
Web: www.ddslt.com

4.4.3 Load Combination (BNBC Standard)


 1.4DL
 1.2DL +0.5Lr
 1.2DL+1.6 Lr +0.8WL
 1.2DL+0.5 Lr +1.3WL
 1.2DL+1.5EQ
 0.9DL+1.5EQ
 0.9DL+1.3WL

4.5 Material Data

The following strength parameter is considered for assessment of building

SL/No Strength

01 Flexural strength of Steel Section 50,000 Psi

4.6) METHOD OF ANALYSIS AND SOFTWARE USED:


We used 3d computer modeling of existing structure to simulate the effect of Dead Load, Live Load, Wind and
Earthquake load.

We used STADD Pro V8i for analysis


Lane #23, House-#160, Ground Floor, New DOHS,
Mohakhali, Dhaka-1206,
Mobile: +8801718612966,
E-mail: quddus_ce@yahoo.com
Web: www.ddslt.com

5.0 ADEQUACY CHECK


Lane #23, House-#160, Ground Floor, New DOHS,
Mohakhali, Dhaka-1206,
Mobile: +8801718612966,
E-mail: quddus_ce@yahoo.com
Web: www.ddslt.com

5.1 Member Adequacy check(Before retrofitting)

Member capacity ratio. (Present condition)

Analysis Design Actual Allowable Normalized Ratio


Beam Clause
Property Property Ratio Ratio (Actual/Allowable)
87 Taper Taper 1.16 1 1.16 LRFD-H1-1B-C
84 Taper Taper 1.283 1 1.283 LRFD-H1-1B-C
83 Taper Taper 0.916 1 0.916 LRFD-H1-1B-C
80 Taper Taper 0.852 1 0.852 LRFD-H1-1B-C
79 Taper Taper 0.98 1 0.98 LRFD-H1-1B-C
76 Taper Taper 0.936 1 0.936 LRFD-H1-1B-C
75 Taper Taper 1.174 1 1.174 L/R-EXCEEDS
74 Taper Taper 1.074 1 1.074 L/R-EXCEEDS
72 Taper Taper 1.073 1 1.073 L/R-EXCEEDS
71 Taper Taper 1.172 1 1.172 L/R-EXCEEDS
64 Taper Taper 0.731 1 0.731 LRFD-H1-1B-C
63 Taper Taper 2.233 1 2.233 LRFD-H1-1B-C
52 Taper Taper 0.837 1 0.837 LRFD-H1-1B-T
Lane #23, House-#160, Ground Floor, New DOHS,
Mohakhali, Dhaka-1206,
Mobile: +8801718612966,
E-mail: quddus_ce@yahoo.com
Web: www.ddslt.com

51 Taper Taper 0.636 1 0.636 LRFD-H1-1B-C


28 Taper Taper 1.903 1 1.903 LRFD-H1-1B-C
27 Taper Taper 1.041 1 1.041 LRFD-H1-1B-T
26 Taper Taper 0.779 1 0.779 LRFD-H1-1B-T
25 Taper Taper 5.363 1 5.363 LRFD-H1-1B-C
24 Taper Taper 4.524 1 4.524 LRFD-H1-1A-C
23 Taper Taper 5.454 1 5.454 LRFD-H1-1B-T
18 Taper Taper 0.711 1 0.711 LRFD-H1-1B-C
17 Taper Taper 1.099 1 1.099 LRFD-H1-1B-C
16 Taper Taper 1.246 1 1.246 LRFD-H1-1A-C
15 Taper Taper 4.286 1 4.286 LRFD-H1-1B-T
14 Taper Taper 2.841 1 2.841 LRFD-H1-1A-C
13 Taper Taper 0.748 1 0.748 LRFD-H1-1B-C
12 Taper Taper 1.367 1 1.367 LRFD-H1-1B-C
11 Taper Taper 0.762 1 0.762 LRFD-H1-1B-C
10 Taper Taper 1.465 1 1.465 LRFD-H1-1B-C
9 Taper Taper 1.074 1 1.074 L/R-EXCEEDS
8 Taper Taper 1.174 1 1.174 L/R-EXCEEDS
7 Taper Taper 1.172 1 1.172 L/R-EXCEEDS
6 Taper Taper 1.073 1 1.073 L/R-EXCEEDS
5 Taper Taper 0.705 1 0.705 LRFD-H1-1B-C
4 Taper Taper 0.773 1 0.773 LRFD-H1-1B-C
3 Taper Taper 1.272 1 1.272 L/R-EXCEEDS
2 Taper Taper 2.268 1 2.268 LRFD-H1-1B-T
1 Taper Taper 2.137 1 2.137 LRFD-H1-1B-C

Comments: Several members are inadequate. Inadequate members are proposed to


strengthen.
Lane #23, House-#160, Ground Floor, New DOHS,
Mohakhali, Dhaka-1206,
Mobile: +8801718612966,
E-mail: quddus_ce@yahoo.com
Web: www.ddslt.com

5.2 Member Adequacy check(After Retrofitting)

Member capacity ratio. (After retrofitting condition)


Analysis Design Actual Allowable Normalized Ratio
Beam Clause
Property Property Ratio Ratio (Actual/Allowable)
87 Taper Taper 0.791 1 0.791 LRFD-H1-1B-C
84 Taper Taper 0.926 1 0.926 LRFD-H1-1B-C
83 Taper Taper 0.864 1 0.864 LRFD-H1-1B-C
80 Taper Taper 0.697 1 0.697 LRFD-H1-1B-C
79 Taper Taper 0.873 1 0.873 LRFD-H1-1B-C
76 Taper Taper 0.726 1 0.726 LRFD-H1-1B-C
75 Taper Taper 1.02 1 1.02 L/R-EXCEEDS
74 Taper Taper 0.344 1 0.344 LRFD-H1-1B-C
72 Taper Taper 0.454 1 0.454 LRFD-H1-1B-T
71 Taper Taper 1.018 1 1.018 L/R-EXCEEDS
64 Taper Taper 0.598 1 0.598 LRFD-H1-1A-C
63 Taper Taper 1.056 1 1.056 LRFD-H1-1A-C
52 Taper Taper 0.324 1 0.324 LRFD-H1-1B-T
Lane #23, House-#160, Ground Floor, New DOHS,
Mohakhali, Dhaka-1206,
Mobile: +8801718612966,
E-mail: quddus_ce@yahoo.com
Web: www.ddslt.com

51 Taper Taper 0.162 1 0.162 LRFD-H1-1B-T


28 Taper Taper 0.609 1 0.609 LRFD-H1-1B-T
27 Taper Taper 0.403 1 0.403 LRFD-H1-1B-C
26 Taper Taper 0.641 1 0.641 LRFD-H1-1B-T
25 Taper Taper 0.55 1 0.55 LRFD-H1-1B-C
24 Taper Taper 0.965 1 0.965 LRFD-H1-1B-C
23 Taper Taper 0.925 1 0.925 LRFD-H1-1B-C
18 Taper Taper 0.788 1 0.788 LRFD-H1-1B-C
17 Taper Taper 0.845 1 0.845 LRFD-H1-1B-C
16 Taper Taper 0.805 1 0.805 LRFD-H1-1A-C
15 Taper Taper 0.65 1 0.65 LRFD-H1-1B-C
14 Taper Taper 0.663 1 0.663 LRFD-H1-1B-C
13 Taper Taper 0.152 1 0.152 LRFD-H1-1B-C
12 Taper Taper 0.16 1 0.16 LRFD-H1-1B-C
11 Taper Taper 0.163 1 0.163 LRFD-H1-1B-C
10 Taper Taper 0.165 1 0.165 LRFD-H1-1B-T
9 Taper Taper 0.34 1 0.34 LRFD-H1-1B-C
8 Taper Taper 1.02 1 1.02 L/R-EXCEEDS
7 Taper Taper 1.018 1 1.018 L/R-EXCEEDS
6 Taper Taper 0.338 1 0.338 LRFD-H1-1B-C
5 Taper Taper 0.158 1 0.158 LRFD-H1-1B-T
4 Taper Taper 0.168 1 0.168 LRFD-H1-1B-T
3 Taper Taper 1.004 1 1.004 LRFD-H1-1B-C
2 Taper Taper 0.463 1 0.463 LRFD-H1-1B-C
1 Taper Taper 0.622 1 0.622 LRFD-H1-1B-C
Lane #23, House-#160, Ground Floor, New DOHS,
Mohakhali, Dhaka-1206,
Mobile: +8801718612966,
E-mail: quddus_ce@yahoo.com
Web: www.ddslt.com

5.3 Serviceability check (Existing Condition)

Horizontal Vertical Horizontal


Node L/C X in Y in Z in
Max X 63 36 DL+WXZ- 6.957 -0.007 18.603
Min X 53 33 DL+WX -6.758 0.004 -11.74
Max Y 83 35 DL+WZ 0.537 2.61 -14.488
Min Y 75 36 DL+WXZ- 2.087 -0.205 12.154
Max Z 15 36 DL+WXZ- 0.01 0.003 21.457
Min Z 54 35 DL+WZ -2.155 0.002 -19.659
Max rX 18 36 DL+WXZ- 0.017 0.002 18.91
Min rX 10 33 DL+WX -0.717 0.004 -3.197
Max rY 8 33 DL+WX -0.72 0.001 -2.205
Min rY 9 34 DL+WX- 0.708 0.002 -3.609
Max rZ 64 35 DL+WZ -1.67 -0.002 -18.779
Min rZ 54 36 DL+WXZ- 6.909 0.015 18.487
Max Rst 15 36 DL+WXZ- 0.01 0.003 21.457

Maximum lateral displacement=6.95 inch


Maximum allowable lateral displacement=h/60=23.50*12/60=4.7 inch
Hence lateral displacement not controlled.

Serviceability check (After Retrofit Condition)

Horizontal Vertical Horizontal


Node L/C X in Y in Z in
Max X 64 36 DL+WXZ- 1.263 0.004 3.68
Min X 54 33 DL+WX -1.138 0.006 -1.918
Max Y 83 33 DL+WX -0.106 1.221 -1.138
Min Y 34 35 DL+WZ 0.498 -0.009 -1.159
Max Z 64 36 DL+WXZ- 1.263 0.004 3.68
Min Z 64 35 DL+WZ -0.901 0.002 -3.909
Max rX 89 36 DL+WXZ- 0 0 0
Min rX 78 35 DL+WZ -0.482 0.366 -2.85
Max rY 30 34 DL+WX- 0.319 0.005 0.113
Min rY 53 34 DL+WX- 0.201 0 -0.107
Max rZ 83 33 DL+WX -0.106 1.221 -1.138
Min rZ 86 33 DL+WX -0.143 1.017 -0.256
Max Rst 64 35 DL+WZ -0.901 0.002 -3.909

Maximum lateral displacement=1.263 inch


Maximum allowable lateral displacement=h/60=24.00*12/60=4.8 inch
Hence lateral displacement is controlled after retrofit.
Lane #23, House-#160, Ground Floor, New DOHS,
Mohakhali, Dhaka-1206,
Mobile: +8801718612966,
E-mail: quddus_ce@yahoo.com
Web: www.ddslt.com

5.4 Foundation Adequacy check:


Lane #23, House-#160, Ground Floor, New DOHS,
Mohakhali, Dhaka-1206,
Mobile: +8801718612966,
E-mail: quddus_ce@yahoo.com
Web: www.ddslt.com

Comments: Foundation is adequate to carry prescribed loading.


Lane #23, House-#160, Ground Floor, New DOHS,
Mohakhali, Dhaka-1206,
Mobile: +8801718612966,
E-mail: quddus_ce@yahoo.com
Web: www.ddslt.com

8.0 Conclusion & Recommendation:


1. Lateral displacements exceed the allowable limit.
2. Due to lateral loading a few section are failed. So additional strengthening system has been
provided.
3. RCC beam, column & foundation system is adequate to carry prescribed loading.

Thanking You

Md. Abdul Quddus


B.Sc Engg. (Civil, BUET)
MIEB-21384, DMINB/CE-0231
CEO & Structural Designer
DESIGN & DEVELOPMENT SOLUTION

Attachments:
1.0 Plate test report
2.0 As-built Drawing
3.0 Proposed Retrofitting Drawing
Page
2
Page
3
Page
4
Page
5
Page
6
Page
7
Page
8
Page
9
Page
10
Page
11
Page
12
Page
13
Page
14
Page
15
Page
16
Page
17
Page
18
Page
19
Page
20
Page
21
Page
22
Page
23
Page
24
Page
25
Page
26
Page
27
Page
28
Page
29
Page
30
Page
31
Page
32
Page
33
Page
34
Page
35
Page
36
Page
37
Page
38
Page
39
Page
40
Page
41
Page
42
Page
43
Page
44
Page
45
Page
46
Page
47

Вам также может понравиться