FASIG-TIPTON BARN EXPANSION

2 Case Street, Saratoga Springs, NY 12866


SITE PLAN APPLICATION
February 2, 2018

SITE STATISTICS: SHEET INDEX:


PROPOSED USE: PROPOSED BARN COVER
FASIG-TIPTON TOTAL AREA: 0.482 ACRES S-1 SURVEY
TAX MAP PARCEL NUMBER: 167.70-1-3 L-1 SITE PREPARATION & EROSION CONTROL PLAN

EAST AVE
ZONING: INST-HTR, INSTITUTIONAL HORSE TRACK RELATED L-2 LAYOUT PLAN
GEORGE STREET
L-3 GRADING, DRAINAGE, UTILITY & LIGHTING PLAN
L-4 SITE DETAILS
L-5 SITE DETAILS
CASE STREET

ZONING - INST-HTR REQUIREMENTS: L-6 SITE DETAILS


REQUIRED PROVIDED A2.1 NORTH ELEVATION WEST ELEVATION
MAX BUILDING COVERAGE (%):
PROJECT OKLAHOMA PRINCIPAL BUILDING: 35% 18% A2.2 SOUTH ELEVATION EAST ELEVATION
LOCATION TRAINING
MIT TRACK MIN. YARD SETBACK (FT):
NATIONAL MUSEUM OF CHE FRONT: 30 FT 37'
RACING AND HALL OF FAME LL S REAR: 30 FT N/A
TRE
E T (50' IF LOT ABUTS A RESIDENTIAL DISTRICT)
EACH SIDE: 12 FT 40'
(40' IF LOT ABUTS A RESIDENTIAL DISTRICT)
TOTAL SIDE: 30 FT

PRINCIPAL BUILDING:
PROJECT VICINITY MAP MAX HEIGHT (FT): 60 FT < 60'
SCALE: N.T.S.
MIN. % TO REMAIN PERMEABLE: 20% 22%

PARKING REQUIREMENTS:
REQUIRED PROVIDED

HORSE BARN (1 PER 10 STALLS) 2 3

CITY OF SARATOGA SPRINGS STANDARD NOTES


PROJECT
1. ALL WORK MUST CONFORM TO ALL FEDERAL, STATE AND CITY CODES, SPECIFICATIONS, ORDINANCES, RULES AND REGULATIONS.
LOCATION
2. THE ELEVATION BASE FOR THE CONTOURS AND BENCHMARKS ARE BASED ON THE NATIONAL GEODETIC VERTICAL DATUM, 1929. APPLICANT: PREPARED BY:
3. ALL REFUSE, DEBRIS AND MISCELLANEOUS ITEMS TO BE REMOVED SHALL BE LEGALLY DISPOSED OF OFF-SITE BY THE CONTRACTOR TO A LOCATION
APPROVED BY THE CITY ENGINEER.

4. THE CONTRACTOR MUST SET UP A PRE-CONSTRUCTION MEETING WITH THE CITY ENGINEER PRIOR TO ANY CONSTRUCTION. CONSTRUCTION INSPECTIONS BY
A DESIGNATED REPRESENTATIVE OF THE APPLICANT OR THE DESIGN PROFESSIONAL ARE REQUIRED. THE COST OF THE CONSTRUCTION INSPECTION IS THE
RESPONSIBILITY OF THE APPLICANT/DEVELOPER.

5. THE CONTRACTOR MUST OBTAIN A BLASTING PERMIT FROM THE BUILDING INSPECTOR IF ANY BLASTING IS REQUIRED FOR THE PROJECT.

6. THE CONTRACTOR MUST OBTAIN A STREET OPENING PERMIT ISSUED BY THE DEPARTMENT OF PUBLIC WORKS FOR ANY WORK IN THE STREET OR
SURVEYOR:
RIGHT-OF-WAY OF ANY CITY STREET, ROAD OR ALLEY.

7. ALL POINTS OF CONSTRUCTION INGRESS OR EGRESS SHALL BE MAINTAINED TO PREVENT TRACKING OR FLOWING OF SEDIMENT OR DEBRIS ONTO A PUBLIC
ROAD.
PROJECT LOCATION MAP 8. NO CERTIFICATE OF OCCUPANCY WILL BE ISSUED UNTIL ALL SITE WORK HAS BEEN COMPLETED IN ACCORDANCE WITH THE APPROVED PLANS; AND AN
SCALE: N.T.S. AS-BUILT DRAWING HAS BEEN PREPARED IN ACCORDANCE WITH THE REQUIREMENTS OF THE CITY ENGINEER.
2017132
TEST PIT NOTES
TEST PITS WITTNESSED BY ROB FRASER OF THE LA GROUP ON 11/30/2017.
EXISTING UTILITY POLE TO REMAIN,
CONTRACTOR TO PROTECT DURING
REMOVE PAVEMENT FOR UTILITY WORK SITE PREPARATION NOTES:
CONSTRUCTION 1. PRIOR TO CONSTRUCTION, CONTRACTOR SHALL ARRANGE PRE-CONSTRUCTION MEETING
TP-1 WITH OWNER/OWNER'S REPRESENTATIVE TO REVIEW ALL APPLICABLE PERMIT
CONDITIONS, THE CONSTRUCTION PLANS AND GENERAL CONSTRUCTION SCHEDULE.
0 - 6” 10 YR 4/1 STONE DUST
6 - 12” 10 YR 4/4 FINE SAND AND GRAVEL 2. THE CONTRACTOR'S ATTENTION IS DIRECTED TO THE GENERAL SURVEY NOTES, UTILITY
12 - 24” 10 YR 3/3 FINE SANDY LOAM NOTES AND UTILITY LOCATING SERVICE REQUIREMENTS. NO WORK SHALL COMMENCE

GEORGE STREET
24 - 108” 7.5 YR 4/4 FINE SANDY LOAM UNTIL UNDERGROUND UTILITIES WITHIN THE SITE HAVE BEEN IDENTIFIED AND LOCATED.

3. ALL EROSION CONTROL MEASURES SHALL BE IN PLACE PRIOR TO ANY EARTH DISTURBING
NO SIGN OF SHWT ACTIVITIES. REFER TO PROJECT PLANS, NOTES AND DETAILS.
FALLING HEAD PERMEABILITY TEST AT 72 INCHES
Unauthorized alteration or addition to this
P1 00:04:02 (MINUTES/INCH) 4. THE GENERAL CONTRACTOR SHALL COORDINATE ALL ADJUSTMENT OR ABANDONMENT OF document is a violation of Section 7209 of the
P2 00:04:23 (MINUTES/INCH) UTILITIES WITH THE RESPECTIVE UTILITY COMPANY AND PAY ALL ASSOCIATED COSTS. New York State Education Law.
P3 00:03:49 (MINUTES/INCH)
P4 00:05:45 (MINUTES/INCH) © the LA Group 2018
SAWCUT
P5 00:05:23 (MINUTES/INCH)
PROTECTION NOTES: Prepared for:
TP-2
1. CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE INSIDE AND OUTSIDE THE LIMIT OF
WORK DUE TO THEIR CONTRACT OPERATIONS. Fasig-Tipton
0 - 6” 10 YR 4/1 STONE DUST
6 - 14” 10 YR 4/4 FINE SAND AND GRAVEL
5 2. Company, Inc.
CONTRACTOR SHALL PROTECT AND SUSTAIN IN NORMAL SERVICE ALL EXISTING UTILITIES,
14 - 16” 10 YR 4/1 STONE DUST REMOVE ASPHALT PAVEMENT RELOCATE STOP SIGN INLET PROTECTION STRUCTURES, EQUIPMENT, ROADWAYS AND DRIVEWAYS. 2400 Newtown Pike
16 - 28” 10 YR 3/3 FINE SANDY LOAM L-4 Lexington, KY 40511
28 - 96” 7.5 YR 4/4 FINE SANDY LOAM 3. CONTRACTOR SHALL MAINTAIN NECESSARY TRAFFIC CONTROL DEVICES, DRUMS,
DELINEATORS, SIGNS, FENCES, AND BARRICADES IN ACCORDANCE WITH THE LATEST
EDITION OF THE NATIONAL MUTCD WITH NYS SUPPLEMENT TO PROPERLY PROTECT WORK,
NO SIGN OF SHWT EQUIPMENT, PERSONS, AND PROPERTY FROM DAMAGE.
FALLING HEAD PERMEABILITY TEST AT 72 INCHES
P1 00:00:44 (SECONDS/INCH) 4. BEFORE ANY CLEARING IS DONE, THE CONTRACTOR SHALL ARRANGE A CONFERENCE ON
P2 00:00:49 (SECONDS/INCH) THE SITE WITH THE LANDSCAPE ARCHITECT TO IDENTIFY TREES WHICH ARE TO BE
P3 00:00:38 (SECONDS/INCH) PROTECTED OR REMOVED. DO NO CLEARING WITHOUT A CLEAR UNDERSTANDING OF
P4 00:00:43 (SECONDS/INCH) EXISTING CONDITIONS TO BE PRESERVED.
P5 00:00:35 (SECONDS/INCH) TP-1 5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF ALL EXISTING TREES
AND PLANTS DESIGNATED TO REMAIN FOR THE LENGTH OF THE CONSTRUCTION PERIOD
AND SHALL, AT A MINIMUM, INSTALL TREE PROTECTION FENCE IN ACCORDANCE WITH
PROJECT PLANS, DETAILS AND SPECIFICATIONS. VEHICLES SHALL NOT BE PARKED WITHIN
1 STABILIZED CONSTRUCTION ENTRANCE THE DRIP LINE OR WHERE DAMAGE MAY RESULT TO TREES TO BE SAVED, AND
L-4 CONSTRUCTION MATERIALS SHALL NOT BE STORED BENEATH TREES TO BE SAVED.

6. THE CONTRACTOR SHALL REVIEW THE LOCATIONS OF THE TREE PROTECTION FENCING
FOR APPROVAL BY THE OWNER'S REPRESENTATIVE PRIOR TO INITIATION OF SITE WORK
OPERATIONS.

7. AT ALL LOCATIONS WHERE EXISTING PAVEMENT ABUTS NEW CONSTRUCTION, THE EDGE
OF THE EXISTING PAVEMENT SHALL BE SAW CUT TO A CLEAN, SMOOTH AND SHARP EDGE
AND PROTECTED UNTIL ABUTTING MATERIALS ARE INSTALLED.

3 CONCRETE WASHOUT
L-4
REMOVALS NOTES:
CASE STREET

1. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE WITH THE OWNER'S


REPRESENTATIVE ON ALL MATERIALS TO BE REMOVED AND RECYCLED/DISPOSED OF OFF
SITE. ALL HANDLING OF MATERIALS TO BE REMOVED, RECYCLED, OR DISPOSED OF MUST
BE DONE SO IN A SAFE, LEGAL MANNER, IN ACCORDANCE WITH ALL LOCAL, COUNTY,
STATE, FEDERAL AND ANY OTHER APPLICABLE REGULATIONS.

2. ALL ITEMS REQUIRING REMOVAL SHALL BE REMOVED TO FULL DEPTH TO INCLUDE BASE
MATERIAL AND FOOTINGS OR FOUNDATIONS AS APPLICABLE UNLESS OTHERWISE NOTED.

3. EXISTING ITEMS INDICATED TO BE SALVAGED OR STOCKPILED SHALL BE CAREFULLY


REMOVED AND STORED AS DIRECTED BY THE OWNER'S REPRESENTATIVE.
SAWCUT

Project Title:

Fasig-Tipton
REMOVE AND DISPOSE OF LOADING RAMPS
George Street
Saratoga Springs, NY 12866

LEGEND
PROPERTY LINE

REMOVE STONE DUST EXISTING CONTOURS

EXISTING STORMWATER

EXISTING UNDERGROUND WATER


TP-2
EXISTING SANITARY

EXISTING UTILITY POLE TO REMAIN, CONTRACTOR TO


PROTECT DURING CONSTRUCTION EXISTING OVERHEAD UTILITY
Project No.: 2017132
SILT FENCE
Design: DBH
4 Drawn: DBH Ch'k'd: CMI
File Name: G:\Proj-2017\2017132_Fasig_Tipton_Barn_Expansion_ Area\2017132CAD\L-1.0 Site Preparation & Removals Plan.dwg

SILT FENCE SITE REMOVALS


L-4 Date: 02/02/18 Scale: 1"=10'

REMOVE ASPHALT PAVEMENT Rev: Description: Date:

REMOVE STONE DUST

CONSTRUCTION ENTRANCE

TEST PITS
Drawing Title

Site Preparation
& Erosion Control
INLET PROTECTION

Plan
Plotted By: HANNAH MARSHMAN

Drawing No.
Save Date: 2/2/2018 5:13 PM

10 5 0 2 4 6 8 10

Scale: 1" = 10'

L-1
2017132
EXISTING STREET LIGHT

LAYOUT NOTES:
1. ALL LINE AND GRADE INFORMATION SHALL BE LAID OUT BY A NEW YORK STATE REGISTERED
SURVEYOR ENGAGED BY THE CONTRACTOR.

GEORGE STREET
1 STREET LIGHT
2 EXISTING
7 DECORATIVE FENCE 2 2. ALL NEW WORK SHALL BE STAKED OUT PRIOR TO CONSTRUCTION. THE OWNER'S REPRESENTATIVE
DETECTABLE STREET LIGHT
WARNING STRIP L-5 L-5 UTILITY POLE L-5 L-5 SHALL BE NOTIFIED OF ANY DISCREPANCIES. FIELD ADJUSTMENTS MUST BE APPROVED BY THE
OWNER'S REPRESENTATIVE PRIOR TO CONSTRUCTION.
Unauthorized alteration or addition to this
3. ALL LINES AND DIMENSIONS ARE PARALLEL OR PERPENDICULAR TO THE LINES FROM WHICH THEY
document is a violation of Section 7209 of the
FLUSH CURB CURB TIP-DOWN
3 1 11 CONCRETE SIDEWALK
3 1 8 CURB TIP-DOWN ARE MEASURED UNLESS OTHERWISE NOTED. New York State Education Law.
L-5 AR L-4 L-5 AR L-4 4. DIMENSIONS TO CURBS ARE FROM FACE OR BOTTOM OF CURB TO FACE OR BOTTOM OF CURB.
© the LA Group 2018
5. FIELD ADJUSTMENTS MUST BE APPROVED BY THE OWNER'S REPRESENTATIVE AND APPROPRIATE
MUNICIPAL OFFICIALS. Prepared for:

6. ALL LAYOUTS FOR WALKS AND PATHS SHALL BE ADEQUATELY STAKED BY THE CONTRACTOR AND
APPROVED BY THE OWNER'S REPRESENTATIVE PRIOR TO CONSTRUCTION.
Fasig-Tipton
Company, Inc.

0'
5.0
7. CONTRACTOR SHALL COORDINATE LOCATION OF ALL UTILITIES (LINES, DUCTS, CONDUITS, SLEEVES,

R2
RELOCATED STOP SIGN 2400 Newtown Pike

R1
FOOTINGS, ETC.) WITH LOCATIONS OF PROPOSED LANDSCAPE ELEMENTS (WALLS, FENCE,

0.0
Lexington,
FOOTINGS, TREE ROOTBALLS, PROPOSED LIGHTING FOOTINGS, ETC.). CONTRACTOR SHALL REPORT KY 40511

0'
ANY DISCREPANCIES TO OWNER'S REPRESENTATIVE PRIOR TO CONTINUING WORK.

8. ALL EXISTING UTILITIES ARE SHOWN IN THEIR RELATIVE POSITION. CONTRACTOR IS RESPONSIBLE
6 FOR VERIFYING THE VERTICAL & HORIZONTAL POSITION OF EXISTING UTILITIES PRIOR TO
DECORATIVE CONSTRUCTION.
L-5 POST

12.00'
PROPOSED GATE
CASE STREET

PLANT LIST
1 3 REMARKS /
SYM. QTY. BOTANICAL NAME COMMON NAME SIZE
UA L-5 SPACING

22.00'

23.00'
PROPOSED GATE DECIDUOUS TREES
R12.00' R12.00'
AR 2 Acer rubrum 'Franksred' Red Sunset Maple 2 1/2 -3 " cal. SEE PLAN
LAWN 30' FRONT SETBACK
PROPOSED UA 3 Ulmus americana 'Princeton'Princeton American Elm 2 1/2 -3 " cal. SEE PLAN
PEDESTRIAN GATE Evergreen Trees
PROPOSED
PEDESTRIAN GATE TO 20 Thuja occidentalis 'Nigra' Dark American Arborvitae 7-8' ht. PLANT 5' O.C.
12'-10"

COMMERCIAL DRIVE

00'

40'-10"
R5.

STONE DUST
30' FRONT SETBACK

40.00'

12' SIDE SETBACK


STREET LIGHT
2
L-5

ROOF OVERHANG

82'-10"
ASPHALT PAVEMENT
9 9.00'
1 3
L-4
LEGEND
Project Title:
UA L-5
Fasig-Tipton
PROPOSED BARNS PROPERTY LINE George Street
24'-10"

15.00'
19 STALLS Saratoga Springs, NY 12866
2,580 S.F.
SETBACK LINE
22.00'

CHAIN LINK FENCE

DECORATIVE FENCE

40' SIDE SETBACK STONE DUST

PROPOSED EASEMENT TO BE GRANTED


TO CITY OF SARATOGA SPRINGS CONCRETE

1 PROPOSED
PEDESTRIAN GATE ASPHALT PAVEMENT
6
38.50'

6" CONCRETE
CURB L-4
STREET LIGHT
Project No.: 2017132
Design: DBH
BIKE RACK
4 SIGNAGE
Drawn: DBH Ch'k'd: CMI
L-5 Date: 02/02/18 Scale: 1"=10'

EVERGREEN TREE PLANTING Rev: Description: Date:


R5
8 .00
'
File Name: G:\Proj-2017\2017132_Fasig_Tipton_Barn_Expansion_ Area\2017132CAD\L-2.0 Layout Plan.dwg

CURB TIP-DOWN
L-4

DECIDUOUS TREE PLANTING


1 3 20 5 CHAINLINK FENCE
UA L-5 TO L-5
Drawing Title

Layout Plan
Plotted By: HANNAH MARSHMAN

10 5 0 2 4 6 8 10
Drawing No.
Save Date: 2/5/2018 10:45 AM

Scale: 1" = 10'

L-2
2017132
GRADING NOTES:
1. EXISTING BASE INFORMATION DERIVED FROM FIELD SURVEY DATED 12/09/16 PERFORMED
BY THOMPSON-FLEMING LAND SURVEYORS P.C.

2. ALL PROPOSED GRADES SHALL BE SET IN THE FIELD BY A NEW YORK STATE LICENSED
LAND SURVEYOR.

GEORGE STREET 2 TAP INTO EXISTING 4" 3. CONTRACTOR SHALL ESTABLISH PERMANENT SECONDARY BENCHMARKS PRIOR TO THE
START OF CONSTRUCTION. ALL SECONDARY BENCHMARKS SHALL BE SO LOCATED THAT
L-6 WATER MAIN THEY WILL NOT BE DISTURBED BY CONSTRUCTION.

4. PITCH EVENLY BETWEEN SPOT GRADES. ALL PAVED AREAS MUST PITCH TO DRAIN AT AUnauthorized alteration or addition to this
SMH-1 MINIMUM SLOPE OF ONE-EIGHTH INCH (1/8") PER FOOT. MAXIMUM CROSSPITCH OF ALL document is a violation of Section 7209 of the
RIM: 308.1' EXISTING 12" STORMLINE New York State Education Law.
WYE INTO EXISTING 8" SIDEWALKS IS 2%. ANY DISCREPANCIES NOT ALLOWING THIS TO OCCUR SHALL BE
INV. IN (W): FIELD VERIFY TC 308.03 REPORTED TO THE OWNER'S REPRESENTATIVE PRIOR TO CONTINUING WORK.
SANITARY SEWER
INV. IN (S): 304.6' © the LA Group 2018
BC 307.53 TC 307.81 TC/BC 307.22 INV. (LATERAL)=301.10
INV. OUT (E): FIELD VERIFY 5. SITE PAVEMENT SHALL MEET ALL BUILDING DOOR THRESHOLDS FLUSH AND IN
BC 307.31 INV. (MAIN)=±299.2
ACCORDANCE WITH ADA GUIDELINES. Prepared for:
TC/BC 308.05

12" HDPE (MIN. 307.93


6.
OF CURB UNLESS SHOWN OTHERWISE. Fasig-Tipton
ALL PROPOSED TOP OF VERTICAL CURB ELEVATIONS ARE SIX INCHES (6") ABOVE BOTTOM

WHERE NEW PAVING MEETS EXISTING PAVING, NEW PAVING SHALL MEET THE LINE ANDCompany, Inc.
0.5% SLOPE) 308
7.
308.03 1" CURB STOP GRADE OF THE EXISTING PAVING. 2400 Newtown Pike
Lexington, KY 40511
8. SET CATCH BASIN AND DROP INLET RIMS TO DRAIN SURROUNDING AREAS AND AT SAME
PITCH AS SLOPING PAVEMENT. IF STRUCTURE IS SHOWN ADJACENT TO CURB, SET GRATE
EXISTING FIRE TIGHT TO FACE OF CURB.
HYDRANT
308.20 308.20 30
8 9. EXCAVATION REQUIRED WITHIN 3 FEET OF EXISTING UTILITY LINE SHALL BE DONE BY
308.85
308.50 HAND. CONTRACTOR SHALL REPAIR ANY DAMAGE TO EXISTING UTILITY LINES OR
STRUCTURES INCURRED DURING CONSTRUCTION OPERATIONS AT NO ADDITIONAL COST
CB-1 1 308.45 0.0 0.0 0.0 0.1 0.1
308.45 0.1 0.2 0.3 0.5 0.6 0.7 0.6 0.4 0.3 0.1 0.1 TO OWNER.
CASE STREET
308.40
RIM: 307.7' L-6
INV. OUT: 304.7' 10. ALL AREAS REQUIRING FILL SHALL BE BROUGHT TO REQUIRED GRADE IN 6" MAXIMUM
(CONTRACTOR TO CONFIRM 0.0 0.0 0.1 0.1 0.1 0.2 0.4 0.7 1.2 1.6 1.9 1.5 0.9 0.5 0.2 0.1 COMPACTED LIFTS. GENERAL FILL SHALL BE FREE OF DELETERIOUS MATERIAL, CONTAIN
CONNECTION ELEVATION NO GRAVEL LARGER THAN 2", AND SHALL BE COMPACTED IN ACCORDANCE WITH PROJECT
1" TYPE K PLANS AND DETAILS.
PRIOR TO INSTALLATION) 4 COPPER WATER
0.0 0.0 6' Ø0.1
DRYWELL
YARD DRAIN 'YD5'
L-6 RIM: 308.5'0.1 0.2 0.4 0.6 1.2 2.5 4.3 5.2 3.8 1.9 0.8 0.3 0.1
SERVICE 11. GRADE AREAS ADJACENT TO BUILDING LINES TO DRAIN AWAY FROM STRUCTURE AND
DW 308.80
RIM: 308.4' INV. IN(N):306.3' 309.20 PREVENT PONDING. FINISH SURFACES SHALL BE FREE FROM IRREGULAR SURFACE
TC/BC 308.00 INV. OUT: 306.4' 0.0 0.1 INV.0.1
IN(S): 0.2
306.3' 0.3 0.5 1.0 1.8 3.9 7.4 9.9 6.3 2.6 0.9 0.3 0.1 CHANGES.
10" HDPE PIPE
309.40 12. SLOPE SIDES OF EXCAVATIONS TO COMPLY WITH LOCAL CODES AND ORDINANCES
0.0 0.1 0.1 0.2 0.4 0.9 1.8 3.1 6.1 11.4 16.8 9.3 3.1 0.9 0.3 0.1 HAVING JURISDICTION AND OSHA REGULATIONS. MAINTAIN SIDE SLOPES OF EXCAVATIONS
IN A SAFE CONDITION UNTIL COMPLETION OF BACKFILLING.
308.50 308.60 308.80 3 6" SDR 26 PVC
308.80
308.80 0.1 0.1 0.2 0.3 0.6 1.3 3.0 4.8 6.4 0.0 0.0 0.0 0.0 L-6 SANITARY 13. THE GENERAL CONTRACTOR SHALL MAINTAIN OR ADJUST TO NEW FINISH GRADE AS
SERVICE, MIN. NECESSARY ALL UTILITY AND SITE STRUCTURES SUCH AS LIGHT POLES, SIGN POLES, MAN
2% SLOPE HOLES, CATCH BASINS, HAND HOLES, WATER AND GAS GATES, HYDRANTS, ETC., FROM
0.1 0.1 0.2 0.48" 0.8 1.9 4.9 9.1 14.8 0.0 0.0 0.0 0.0 MAINTAINED UTILITY AND SITE SYSTEMS UNLESS OTHERWISE NOTED ON THE UTILITY
HD DRAWINGS OR AS DIRECTED BY THE OWNER'S REPRESENTATIVE.
PE
P
0.2 0.2 0.3 0.5 0.9 IPE 2.1 5.2 9.4 14.8 0.0 0.0 0.0 0.0 14. CONTRACTOR SHALL BLEND NEW EARTHWORK SMOOTHLY INTO EXISTING, PROVIDING
VERTICAL CURVES OR ROUNDINGS AT ALL TOP AND BOTTOM OF SLOPES.
0.0 0.1 0.1 0.1 0.2 0.2 0.3 0.3 0.3 0.3 0.4 0.5 0.7 1.1 2.2 4.4 6.5 8.1 0.0 0.0 0.0 0.0 15. CONTRACTOR SHALL MAINTAIN THE INTEGRITY OF THE EXISTING DRAINAGE SYSTEM AT
309
ALL TIMES. DURING EARTHWORK OPERATIONS, DRAINAGE OF THE SITE AND ADJACENT
AREAS SHALL BE MAINTAINED CONTINUOUSLY TO PREVENT EROSION OR DAMAGE
0.1 0.1 0.1 0.2 0.3 0.5 0.6 0.6 0.6 0.6 0.7 0.9 1.0 1.4 2.5 4.8 6.9 8.6 YARD DRAIN 'YD4' 0.0 0.0 0.0 0.0 RESULTING FROM CONCENTRATED RUN-OFF. WHEN IT IS NECESSARY TO INTERRUPT THE
308.16 RIM: 309.3' EXISTING DRAINAGE PATTERNS AND/OR UTILITIES, PROVIDE TEMPORARY FACILITIES
INV. IN/OUT: 306.75' UNTIL WORK IS PERMANENTLY STABILIZED AND APPROVED BY OWNER'S
0.1 0.2 0.2 0.4 0.7 1.2 1.6 1.6 1.4 1.3 1.5 1.9 2.0 2.2 3.3 6.5 11.0 16.5 0.0 0.0 0.0 0.0 REPRESENTATIVE.
308.91
8" HDPE (TYP.)
16. THE GENERAL CONTRACTOR SHALL MAINTAIN OR ADJUST TO NEW FINISH GRADE AS
0.2 0.2 0.4 0.7 1.4 2.8 4.3 4.2 3.0 2.5 3.3 4.6 4.7 3.8 4.4 8.0 13.3 18.5 0.1 0.1 0.1 0.1 NECESSARY ALL UTILITY AND SITE STRUCTURES SUCH AS LIGHT POLES, SIGN POLES,
TC 308.81 MAN HOLES, CATCH BASINS, HAND HOLES, WATER AND GAS GATES, HYDRANTS, ETC.,

309
BC 308.31 FROM MAINTAINED UTILITY AND SITE SYSTEMS UNLESS OTHERWISE NOTED ON THE
0.2 0.4 0.6 1.0 1.9 4.9 8.7 8.3 4.8 3.3 5.3 8.9 8.8 5.6 4.8 8.3 13.4 14.3 0.2 0.2 0.2 0.2 UTILITY DRAWINGS OR AS DIRECTED BY THE OWNER'S REPRESENTATIVE.

17. IN ALL LAWN AREAS, ROUGH GRADE SHALL BE BROUGHT TO WITHIN 4" OF FINISHED
309.15 0.8
0.4 1.1 1.6 2.1 6.5 14.3 13.0 5.9 3.7 6.7 14.2 13.8 6.7 4.7 8.3 309.40
16.1 15.0 5.4 1.7 0.6 0.7 0.6 0.6 0.4 GRADE UNLESS OTHERWISE NOTED.
309.40
308.30
0.6 1.4 2.3 2.7 YARD DRAIN 'YD1' 1.8 1.6 1.3 0.7
309.05
RIM: 309.3'
INV. OUT: 307.3'
YARD DRAIN 'YD2' YARD DRAIN 'YD3'
RIM: 309.3'
308.00
UTILITY NOTES: Project Title:
RIM: 309.3'
1.0 2.6 5.3 7.3 INV. IN/OUT: 307.2' INV. IN/OUT: 306.93' 5.7 4.4 3.0 1.4 1. THE CONTRACTOR SHALL CONTACT U.F.P.O. (1-800-962-7962) AND THE PROPER LOCAL
AUTHORITIES OR RESPECTIVE UTILITY COMPANY HAVING JURISDICTION TO CONFIRM THE Fasig-Tipton
TC 308.95 PROPOSED BARNS INV. (BLDG.)=304.0 LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK. ANY COSTS George Street
1.1 3.4 7.9 13.1 14.3 8.9 5.1 1.9
BC 308.45 FFE 309.4 INCURRED BY THE CONTRACTOR DUE TO FAILURE TO CONTACT THE PROPER
Saratoga Springs, NY 12866
AUTHORITIES SHALL BECOME THE RESPONSIBILITY OF THE CONTRACTOR.

308
1.0 2.9 6.2 9.1 15.5 9.5 5.4 2.0 2. ALL UTILITY INSTALLATIONS SHALL BE IN ACCORDANCE WITH ALL REGULATORY, LOCAL
MUNICIPAL AND BUILDING CODE REQUIREMENTS.
309.15 1.7
0.7 3.0 3.6 309.40 309.40 6.8 5.0 3.4 1.5 3. EXCAVATION REQUIRED WITHIN PROXIMITY OF UTILITY LINES SHALL BE DONE BY HAND.

0.5 0.9 1.3 1.6 1.3 4. CONTRACTOR SHALL PROTECT AND SUSTAIN IN NORMAL SERVICE ALL EXISTING
4.2 11.7 16.8 8.9 4.0 4.9 11.6 17.0 9.2 3.9 4.2 10.1 17.1 10.4 3.6 1.1 2.5 2.0 1.6 0.9 UTILITIES, STRUCTURES, EQUIPMENT ROADWAYS AND DRIVEWAYS FOR THE DURATION OF
CONSTRUCTION.
0.3 0.4 0.6 0.8 1.2 3.5 8.1 10.8 6.7 3.7 4.2 8.2 11.0 6.8 3.6 3.7 7.3 10.9 7.3 3.0 1.1 1.0 0.8 0.7 0.4
LEGEND
0.2 0.2 0.3 0.6 1.1 2.7 5.2 6.4 4.7 3.1 3.4 5.4 6.5 4.8 3.0 3.1 4.9 6.4 4.8 2.4 1.0 0.6 0.4 0.3 0.2
PROPERTY LINE
0.1 0.1 0.2 0.4 0.7 1.4 2.1 2.5 2.2 1.8 1.9 2.4 2.6 2.2 1.7 1.7 2.2 2.5 2.0 1.2 0.6 0.4 0.2 0.2 0.1 852 MINOR CONTOUR
308.70 TC 309.35 309 EXISTING MINOR CONTOUR
BC 308.85 309.45 0.1 0.1 0.1 0.2 0.4 0.6 0.8 0.9 0.9 0.8 0.9 0.9 1.0 0.9 0.8 0.8 0.9 0.9 0.8 0.5 0.3 0.2 0.1 0.1 0.1 307.25
EXISTING SPOT ELEVATION Project No.: 2017132
0.0 0.1 0.1 0.1 0.2 0.3 0.3 0.4 0.4 0.4 0.4 Design: DBH
0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.3 0.2 0.2 0.1 0.1 0.1 0.0 307.25
Drawn: DBH Ch'k'd: CMI
PROPOSED SPOT ELEVATION
File Name: G:\Proj-2017\2017132_Fasig_Tipton_Barn_Expansion_ Area\2017132CAD\L-3.0 Grading, Drainage & Utility Plan.dwg

Date: 02/02/18 Scale: 1"=10'


0.0 0.0 0.1 0.1 0.1 0.1 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.1 0.1 0.1 0.1 0.1 0.0 0.0
PROPOSED SANITARY LINE Rev: Description: Date:
308.70 308.00 308 307.55 307.25
0.0 0.0 0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.0 0.0 0.0
PROPOSED WATER LINE
308

PROPOSED STORMWATER LINE

PROPOSED CATCH BASIN/DRYWELL


STATISTICS
DESCRIPTION SYMBOL AVG. MAX. MIN. MAX./ MIN. AVG./MIN.
PROPOSED MANHOLE Drawing Title

Grading, Drainage
Beyond Property 0.1 fc 0.2 fc 0.0 fc N/A N/A
Line
General Calc
Zone
2.5 fc 18.5 fc 0.0 fc N/A N/A
PROPOSED YARD DRAIN
& Utility Plan
LUMINAIRE SCHEDULE
Plotted By: HANNAH MARSHMAN

10 5 0 2 4 6 8 10 Drawing No.
Save Date: 2/5/2018 10:44 AM

SYMBOL LABEL QUANTITY MANUFACTURER CATALOG NUMBER DESCRIPTION LAMP NUMBER FILE NAME LUMENS PER LIGHT WATTAGE
LAMPS LAMP LOSS FACTOR
11 Lithonia WST LED P2 40K WST LED, Performance LED WST_LED_P Scale: 1" = 10'
A 1 3469 0.9 25
Lighting Package 2, 4000 K, visual
L-3
VF MVOLT 240K_VF_M
comfort forward throw, VOLT.ies
MVOLT
2017132
NOTE:
50'-0" NOTES:
EXPANSION JOINTS SPACED PROVIDE CLEAN SQUARE CORNER
1. MINIMUM STONE SIZE SHALL BE 1"-4" STONE, INSTALLED
FINISH ALONG CURB 10' O.C. MAX. WHERE BITUMINOUS WALK ABUTS CURB
OVER FILTER FABRIC TO A MINIMUM DEPTH OF 6". 6" 1/2" RADIUS BROOM FINISH PERPENDICULAR BROOM FINISH PERPENDICULAR
EDGE OF EXISTING ROADWAY GRADE
2. MINIMUM WIDTH SHALL BE 12' FOR ONE WAY TRAFFIC, 24' 6" FINISH GRADE; BITUMINOUS TO WALK TO WALK
1/4" RADIUS

1/2"
FOR TWO WAY TRAFFIC. MINIMUM LENGTH SHALL BE 50'. OR LAWN, SEE PLANS 4" CONCRETE - SEE 6" CONCRETE - SEE
3. ALL SURFACE WATER FLOWING OR DIVERTED TOWARD CONCRETE SPECIFICATIONS CONCRETE SPECIFICATIONS
CONSTRUCTION ACCESSES SHALL BE PIPED BENEATH PAVEMENT

6"
ACCESS. IF IMPRACTICAL, A MOUNTABLE DIVERSION BERM FINISH GRADE 6" X 6" NO66 WOVEN WIRE 6" X 6" NO66 WOVEN WIRE
PREVENTING RUNOFF ONTO ADJACENT ROAD SHALL BE 4,000 PSI MESH EXCEPT A.O.B.E. MESH EXCEPT A.O.B.E.

16"
24'-0"
PERMITTED. CAST-IN-PLACE 6" GRANULAR SUBBASE COURSE NYS 8" GRANULAR SUBBASE COURSE NYS

18"
4. ACCESS SHALL BE MAINTAINED IN A CONDITION WHICH WILL CAST-IN-PLACE CONCRETE CONCRETE CURB DOT SECT. 304, TYPE 4 COMPACTED DOT SECT. 304, TYPE 4 COMPACTED
PREVENT TRACKING OR FLOWING OF SEDIMENT ONTO CURB SEE CONCRETE
TO 95% STANDARD PROCTOR TO 95% STANDARD PROCTOR

6"
PUBLIC RIGHTS-OF-WAY, ALL SEDIMENT SPILLED, DROPPED, SPECIFICATION
WASHED OR TRACKED ONTO PUBLIC RIGHTS-OF-WAY SHALL SUBGRADE COMPACTED TO SUBGRADE COMPACTED TO Unauthorized alteration or addition to this
R. YP

document is a violation of Section 7209 of the


35 .

BE REMOVED IMMEDIATELY. GRAVEL COMPACTED TO 90% STANDARD PROCTOR 90% STANDARD PROCTOR
T
'-0

COMPACTED New York State Education Law.

6"
"

5. ALL VEHICLE WASHING SHALL BE DONE IN A STONE

MIN.
95% STANDARD PROCTOR GRAVEL BASE

6"
STABILIZED AREA WHICH DRAINS INTO AN APPROVED 7" NYSDOT SECT. 304, NOTES: NOTES: © the LA Group 2018
SEDIMENT TRAPPING DEVICE. TYPE 2
SUBGRADE COMPACTED TO EXPANSION JOINT SPACING - 20'-25' O.C. EXPANSION JOINT SPACING - 20'-25' O.C.
6. INSPECT AND MAINTAIN AS NEEDED TO CONFORM TO
50'-0" OF 12" 50/50 MIXTURE OF TYPE 3 90% STANDARD PROCTOR CONTROL JOINT SPACING - 5' O.C. CONTROL JOINT SPACING - 5' O.C.
SPECIFICATIONS AND STORMWATER POLLUTION 6" 6" 6"
AND TYPE 4 GRANULAR MATERIAL NOMINAL CROSS SLOPE - 1/8" TO 1/4" PER FOOT (MAX. SLOPE 1:50 TYP.) NOMINAL CROSS SLOPE - 1/8" TO 1/4" PER FOOT (MAX. SLOPE 1:50 TYP.) Prepared for:
PREVENTION PLAN.
OVER COMPACTED SUBGRADE TOWARDS STREET OR A.O.B.E. MAX. SLOPE ALONG THE LENGTH OF
THE WALK SHOULD NOT EXCEED 1:12 CONSTRUCTION JOINT DETAILS TO THE
TOWARDS STREET OR A.O.B.E. MAX. SLOPE ALONG THE LENGTH OF
BE WALK SHOULD NOT EXCEED 1:12 CONSTRUCTION JOINT DETAILS TO Fasig-Tipton
STABILIZED CONSTRUCTION ENTRANCE 6" CONCRETE CURB
SUBMITTED AND APPROVED BY CITY ENGINEER SIDEWALK WIDTH TO BEBE
MIN. OR AS ORDERED BY CITY ENGINEER
5' SUBMITTED AND APPROVED BY CITY ENGINEER SIDEWALK WIDTH TO
BE 5' MIN. OR AS ORDERED BY CITY ENGINEER Company, Inc.
1 MAX. 2
SCALE: NTS 6 SCALE: NTS
2400 Newtown Pike
Lexington, KY 40511
1

PROPOSED EXISTING PAVING GENERAL DESIGN CRITERIA FOR CONSTRUCTING SIDEWALKS WITHIN GENERAL DESIGN CRITERIA FOR CONSTRUCTING SIDEWALKS WITHIN
PAVING SARATOGA SPRINGS RIGHT OF WAYS: SARATOGA COUNTY RIGHT OF WAYS WITHIN SARATOGA SPRINGS:
6" KEYED PAVEMENT TO BE FLUSH WITH
TOP COURSE EXISTING PAVEMENT TO REMAIN 1.) SIDEWALKS MUST BE PLACED IN THE PUBLIC RIGHT OF WAY AT THE 1.) ALL SIDEWALK INSTALLATIONS MUST BE DESIGNED BY A
PROPERTY LINE. PROFESSIONAL ENGINEER. PLANS MUST BE APPROVED BY THE
BINDER COURSE 1-/2" MINIMUM DEEP KEY COUNTY COMM. OF PUBLIC WORKS.
2.) SIDEWALKS MUST NOT DROP DOWN WHEN CROSSING A DRIVEWAY.
INTO EXISTING PAVEMENT
3.) SIDEWALKS MUST NOT EXTEND ACROSS PUBLIC STREETS OR ALLEYS.2.) SIDEWALKS MUST BE PLACED ON THE BACK SIDE OF DITCHES OR
8'(MIN.) FROM THE EDGE OF SHOULDER.
3.) SIDEWALKS MUST BE CONSTRUCTED SO AS NOT TO INTERFERE
WITH DRAINAGE.
NOTES: COMPACTED BASE MATERIAL
1. AREA CHOSEN FOR STOCKPILING OPERATIONS SHALL BE DRY AND STABLE. COMPACTED SUBGRADE
2. MAXIMUM SLOPE OF STOCKPILE SHALL BE 2:1. MAXIMUM HEIGHT SHALL BE 12 FEET.
3. EACH PILE SHALL BE SURROUNDED WITH EITHER SILT FENCING OR STRAWBALES, INSTALLED PER CORRESPONDING DETAIL.
4. A PERIMETER DIKE/SWALE SHALL BE LOCATED UP-SLOPE OF THE TOPSOIL STOCKPILE.
CONCRETE SPECIFICATIONS OF THE PLANNING BOARD

TEMPORARY STOCKPILE PAVEMENT KEY


2 8' (MIN.)
SCALE: NTS 7 SCALE: NTS
THESE GENERAL CONCRETE SPECIFICATIONS SHALL APPLY TO ALL MOIST CURING IF CONCRETE IS PLACED IN THE FALL AND WILL BE
CONCRETE WORK WITHIN THE CITY OF SARATOGA SPRINGS INSTALLED EXPOSED TO FREEZE-THAW CYCLES AND DEICERS WHEN SATURATED.
WITHIN A CITY RIGHT-OF-WAY AND/OR WITHIN THE APPROVAL THE EXACT LENGTH OF TIME FOR SUFFICIENT DRYING TO TAKE PLACE
AUTHORITY MINIMUM SPECIFICATIONS. MAY VARY WITH CLIMATE AND WEATHER CONDITIONS.
STAPLES (2 PER ALL CONCRETE THAT MAY COME IN CONTACT WITH DEICING CHEMICALSTECHNICAL SPECIFICATIONS FOR CONCRETE AS HEREIN DEFINED
BALE) SHALL MEET OR EXCEED THESE SHALL COMPLY WITH THE APPLICABLE SPECIFICATIONS OF THE "NEW
CONCRETE
STRAW BALE WOOD OR METAL CURB 1' 5' YORK STATE DEPARTMENT OF TRANSPORTATION STANDARD
STAKES (2 PER BALE) CONCRETE SHALL BE ONLY PORTLAND CEMENT CONCRETE SPECIFICATIONS CONSTRUCTION AND MATERIALS", 1985.
10 MIL PLASTIC AIR-ENTRAINED OF DURABLE MATERIALS AND SHALL HAVE (1) A LOW
LINING WATER-CEMENT RATIO (MAXIMUM 0.46), (2) A SLUMP OF 4 INCHES OR ANY CLARIFICATION, REVISIONS, MODIFICATIONS THERETO SHALL ONLY
8' (MIN.)

LESS,* (3) A CEMENT CONTENT OF 606 LB PER CUBIC YARD OR MORE, (4)BE MADE SUBJECT TO APPROVAL OF THE CITY OF SARATOGA SPRINGS
(MIN.)

PROPER FINISHING AFTER BLEED WATER HAS EVAPORATED FROM THE PLANNING BOARD.
2'

6"
SURFACE, (5) ADEQUATE DRAINAGE WITH A SLOPE OF 1/8 INCH PER
10 MIL PLASTIC
LINEAR FOOT OR MORE, (6) A MINIMUM OF 7 DAYS MOIST CURING AT OR *A SUPER PLASTICIZER MAY BE USED TO INCREASE SLUMP AND
LINING
ABOVE 50 DEGREES F, (7) A MINIMUM COMPRESSIVE STRENGTH OF 4000WORKABILITY WITHOUT INCREASING THE WATER-CEMENT RATIO.
NOTE: 3/8" EXPANSION JOINT PSI AT 28 DAYS, AND (8) A MINIMUM 30-DAY DRYING PERIOD AFTER
STRAWBALES STAKED
INTO GROUND ADJACENT FINISH GRADE AT
1. WASHOUT AREA SHALL BE SIZED BY THE CONTRACTOR TO BOTTOM OF CURB
ADEQUATELY CONTAIN CONCRETE CLEANOUT.

CONCRETE WASHOUT TRANSITION CURB CONCRETE PAVEMENT ON GRADE


3 SCALE: NTS 8 SCALE: NTS 11 SCALE: NTS

10' MAX.℄ TO ℄ 36" MIN. FENCE POST

36" MIN., 2" HARDWOOD FENCE Project Title:

Fasig-Tipton
POSTS, DRIVEN MIN. 16" INTO
GROUND

George Street
16" ABOVE

20" MIN.
GRADE

FILTER FABRIC NOTES: Saratoga Springs, NY 12866


1. PAVEMENT SECTIONS SPECIFIED ARE TYPICAL FOR
GRADE
BELOW

STREET, DRIVEWAY AND PARKING LOT CONSTRUCTION


2' OVERALL
FABRIC HT.
6"

FLOW TOP COURSE - NYSDOT ITEM WHERE TRAFFIC VOLUMES AND LOADINGS ARE NOT
402.098302 - 9.5F3 H.M.A., 80 EXCESSIVE. BASED ON ANTICIPATED VOLUMES AND
SERIES COMPACTION LOADS, THE CITY ENGINEER MAY REQUIRE STRUCTURAL CONCRETE APRON SEE
MIN.

16" MIN.

PAVEMENT SECTION TO BE INCREASED TO CARRY DESIGN


6"

CONCRETE SIDEWALK & APRON TYPE 1 AT CONCRETE SPECIFICATIONS


LOADING. NON-VEHICLE TRAFFIC AREAS TYPE 2 AT VEHICLE
TACK COAT - NYSDOT ITEM 2. TACK COAT BINDER BEFORE PLACING TOP COARSE IF TRAFFIC AREAS TURF
407-0102 DILUTED
SUBGRADE AS

W O W MORE THAN 48 HOURS HAVE ELAPSED AFTER PLACING 6" CONCRETE


O FL
REQUIRED

FL
DEPTH TO

PERSPECTIVE VIEW EMBED FILTER BINDER COURSE. CURB


BINDER COURSE - NYSDOT ITEM
CLOTH MIN. 8" 3. THE CITY ENGINEER MAY REQUIRE COMPACTION TESTING
FILTER FABRIC; FASTENED SECURELY TO 402.198902 - 19F9 H.M.A., 80
INTO GROUND AND/OR CORE SAMPLES TO VERIFY PAVEMENT THICKNESS.
FENCE POSTS W/ STAPLES SECTION SERIES COMPACTION PG EXPANSION JOINT (TYP.)
ALL TESTING SHALL BE AS ORDERED BY THE CITY
BINDER (LIQUID ASPHALT) FULL DEPTH OF PAVEMENT
NOTES: ENGINEER AND SHALL BE PAID BY THE CONTRACTOR.
GRADE SHALL BE PG-64-22 TRANSITION CURB
1. WOVEN WIRE FENCE TO BE FASTENED SECURELY TO FENCE POSTS WITH WIRE TIES OR STAPLES. POSTS SHALL BE STEEL EITHER "T" OR "U" 4. NOTIFY THE CITY ENGINEER 48 HOURS MINIMUM PRIOR TO
RADIUS 5' BOTH SIDES
TYPE OR HARDWOOD. COMMENCING PAVING OPERATIONS.
1-1/2" REVEAL
2. FILTER CLOTH TO BE TO BE FASTENED SECURELY TO WOVEN WIRE FENCE WITH TIES SPACED EVERY 24" AT TOP AND MID SECTION. FENCE COMPACTED GRAVEL -
SHALL BE WOVEN WIRE, 12 1/2 GAUGE, 6" MAXIMUM MESH OPENING. NYSDOT TYPE 2 (SECT. PAVEMENT TOP BINDER GRAVEL
3. WHEN TWO SECTIONS OF FILTER CLOTH ADJOIN EACH OTHER THEY SHALL BE OVER- LAPPED BY SIX INCHES AND FOLDED. FILTER CLOTH 304) COMPACTED TO 95% TYPE COURSE COURSE COURSE STREET
SHALL BE EITHER FILTER X, MIRAFI 100X, STABILINKA T140N, OR APPROVED EQUIVALENT. STANDARD PROCTOR 5'
PARKING 1-1/2" 2" 8" MIN.
4. PREFABRICATED UNITS SHALL BE GEOFAB, ENVIROFENCE, OR APPROVED EQUIVALENT. LOT Project No.: 2017132
5. MAINTENANCE SHALL BE PERFORMED AS NEEDED AND MATERIAL REMOVED WHEN 1/3 HEIGHT OF SILT FENCE IS REACHED OR WHEN WARPED PAVEMENT AREA Design:
SUBGRADE - COMPACTED TO CMI
"BULGES" DEVELOP IN THE SILT FENCE. (TYP. BOTH SIDES)
90% STANDARD PROCTOR ROADWAY 1-1/2" 3" 12" Drawn: DBH Ch'k'd: DBH
Date: 2/8/2018 Scale: N.T.S.

SILT FENCE ASPHALT PAVEMENT COMMERCIAL DRIVEWAY


4 SCALE: NTS 9 SCALE: NTS 12 SCALE: NTS
Rev: Description: Date:

NOTE: STONE DUST, NATURAL

4"
F
NT NOF
DEPTH MIN.

E U 1. SILT SACK SHALL BE MAINTAINED & REMOVED CRUSHED LIMESTONE


M
DI R
SE DEN ONLY AFTER ACCEPTANCE OF ROADWAY. SILT JOINT SEAL PER SPEC.

8"
COMPACTED GRANULAR NYS DOT
LA
1 14"

SACK SHALL BE CLEANED PERIODICALLY TO KEEP 2" 2" 2" 2" TYPE 2 (SECT 304) COMPACTED TO
CATCH BASIN WORKING PROPERLY WHILE IN TOOLED JOINT W/ 1/4" 95% STANDARD PROCTOR
PLACE AT REMOVAL OF SILT SACK ALL CATCH TOOLED JOINT 5' O.C. OR
RADIUS EDGES AS
BASINS SHALL BE CLEANED OF DEBRIS AND AS SHOWN ON PLANS & MIRAFI 500X GEOTEXTILE Drawing Title
SHOWN, TYP.
SEDIMENT. OTHER DETAILS OR TO
MATCH EXIST. SCORE SUBGRADE COMPACTED TO
90% STANDARD PROCTOR
2. GRATE SILT SACK SHALL ONLY BE USED FOR
IN-PAVEMENT STRUCTURES ONLY DURING AND
PREMOULDED JOINT FILLER JOINTS. TOOLING SHALL
ALSO OCCUR AROUND STONE DUST Site Details
NR
ENT
SEDIUMNOFF
USE SILT SACK UNDER GRATE TO
CONTROL SEDIMENT RUNOFF.
AFTER INSTALLATION OF PAVEMENT. 1 "
2 JOINT EXPANSION JOINTS TO OCCUR 60' O.C. MAX 1 "
2 JOINT
ENTIRE PERIMETER OF
CONC. PAVEMENT.
13 SCALE: NTS

LADE SACK SHALL BE MAINTIANED AND


& AT ALL CURBS, WALLS, & WHERE SHOWN
ON PLANS OR OTHER DETAILS Drawing No.
CLEANED ON A REGULAR BASIS
(SEE NOTE)

INLET PROTECTION - FINISHED PAVED AREAS CONCRETE PVMT. EXPANSION/SCORE JOINT


5 SCALE: NTS 10 SCALE: NTS
L-4
2017132
Tactile Systems
ENGINEERED PLASTICS, INC. GALV.TURNBUCKLE >1 PER CABLE
300 INTERNATIONAL DR., SUITE 100
WILLIAMSVILLE, NY CONTRACTOR RESPONSIBLE FOR
USA, 14221 KEEPING TREE PLUMB. REFER TO
1 (800) 682-2525 SPECIFICATIONS FOR FURTHER
PHONE: (716) 626-3626 INFORMATION. STAKING NOT ALWAYS
FAX: 1 (800) 769-4463 REQUIRED. IF STAKING, INSTALL 2"X2" SQ.
OR 3" DIA. HARD OR SOFT WOOD STAKES, Unauthorized alteration or addition to this
www.armor-tile.com document is a violation of Section 7209 of the
IN ACCORDANCE WITH THE New York State Education Law.
SPECIFICATIONS. (3) STAKES REQUIRED
DETAIL 1 FOR TREES GREATER THAN 2" CAL.
A © the LA Group 2018

NEATLY WRAP ALL DECIDUOUS TRUNKS


TO A HEIGHT OF THE SECOND LOWEST Prepared for:

B B
BRANCH (FALL PLANTING ONLY)
Fasig-Tipton
ROOT FLARE SHALL BEAR SAME
RELATIONSHIP TO FINISH GRADE AS IT
Company, Inc.
10/16" Ø HOLE THROUGH DOME BORE TO EXISTING GRADE IN THE 2400 Newtown Pike
EMBEDMENT FLANGES (2 PER NURSERY Lexington, KY 40511
FLANGE) A 3" DEPTH SHREDDED BARK MULCH; PULL
SECTION A-A
AWAY FROM TRUNK.
DOME
PLAN - TILE CUT ROPE SURROUNDING BOTTOM OF
TREE TRUNK AFTER BACKFILLING BUT
BEFORE MULCHING. DO NOT REMOVE
BURLAP.
INTERNAL EMBEDMENT 10/16" Ø HOLE THROUGH 3" HT. PLANTING SOIL SAUCER,
EMBEDMENT FLANGES (2 PER EQ. EQ.
FLANGE AT 3" C/C COMPACTED
FLANGE)
SECTION B-B
PLANTING SOIL AS SPECIFIED
45°
6" NATIVE SOIL DRAINAGE MOUND,
COMPACTED TO 92%. (POORLY DRAINED
DETAIL 1 SOILS ONLY)
NOTES:
1. INSTALLATION TO BE COMPLETED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS. UNDISTURBED SUBGRADE
2. DO NOT SCALE DRAWINGS. 2'-0"
3. FOR CUSTOM SIZING CONTACT MANUFACTURER.
4. CONTRACTORS NOTE: FOR PRODUCT AND COMPANY INFORMATION VISIT www.CADdetails.com/info MIN. NOTE:
REFERENCE NUMBER 681-001A. MATCH DECORATIVE POSTS ON MADISON AVE

DETECTABLE WARNING STRIP DECIDUOUS TREE PLANTING DECORATIVE POST DETAIL


1 SCALE: NTS 3 SCALE: NTS 6 SCALE: NTS

+/- 19-3/8"

POWDER COATED BLACK STEEL


BIKE RACK, MODEL 4180-IG-P BY
BELSON OUTDOORS OR
FINIAL -SAME FINISH AS POST APPROVED EQUAL

+/- 34"

+/- 34"
LED ROOF-MOUNTED OPTICS HEAT SINK EXPANSION JOINT
FOR HEAT TRANSFER
STERNBERG ORNAMENTAL FIXTURE CONCRETE WALK
MODEL D650SRLED 67 WATT LED (4ARC22)
2200K COLOR TEMPERATURE
SEALED LED/OPTICAL ASSEMBLY
10"

ACRYLIC LED DRIVER W/ ELECTRIC


3'

3'
LENS QUICK-DISCONNECT 3" HEAVY WALL CAST 3
ALUMINUM FITTER WELDED TO POLE TOP 8" ACHOR ROD
(W/ PHOTO CELL)
Project Title:
CONCRETE FOOTING
STERNBERG MODEL 3" TO 4" TAPERED
POST 6061-T6 STRUCTURAL GRADE 6" 6" 6" 6"
COMPACTED SUBGRADE Fasig-Tipton
ALUMINUM 0.125" WALL NO. 4212-T
BLACK FINISH POLE WELDED FOR SINGLE George Street
UNIT CONSTRUCTION Saratoga Springs, NY 12866
ELEVATION - SIDE ELEVATION - FRONT
12' HEIGHT

ACCESS DOR WITH FLUSH STAINLESS


STEEL ALLEN HEAD SCREWS NOTES:
1. VERIFY DIMENSIONS OF BICYCLE RACK & STAKE LOCATION NOTE:
PRIOR TO START OF FOOTING CONSTRUCTION & MATCH DECORATIVE FENCE ON MADISON AVE
0.250" WALL INSTALLATION
17" DIA. BASE WITH 0.750" FLOOR 2. INSTALL EMBEDDED ANCHORING PER MANUFACTURERS
SPECIFICATIONS
THICKNESS, 4 ANCHOR BOLTS AND 1
BICYCLE RACK DETAIL DECORATIVE FENCE DETAIL
GROUND LUG
3/4" CHAMFER 4 SCALE: NTS 7 SCALE: NTS

FINISHED GRADE
3"

ZINC PLATED ANCHOR BOLT ASSEMBLY END & CORNER POST CHAIN LINK, TOP SELVAGE KNUCKLED
24" MIN.

PER MANUFACTURER'S RECOMMENDATION

ELECTRIC SERVICE WITH 2" PVC SCHEDULE Project No.: 2017132


4'-0" MIN.

80-NO DIRECT BURIAL


Design: CMI
GROUND ROD PER N.E.C. TOP RAIL Drawn: Ch'k'd:
DBH DBH
4000 PSI CONCRETE BASE WITH 20" DIA Date: 2/8/2018 Scale: N.T.S.
LINE POST TOP
SONOTUBE FIBER FORM. REMOVE FORM TO
6" BELOW GRADE AFTER POUR. PROVIDE (6) Rev: Description: Date:
6' - 0"

TENSION BAR SLEEVE CONNECTION


#5 VERTICAL BARS EVENLY. SPACED AND
#4 HORIZONTAL BARS 12" O.C. PROVIDE 3"
COVER ALL SIDES. TENSION BAND WITH CARRIAGE LINE POST
BOLTS AND NUTS
20" UNDISTURBED SUBGRADE OR COMPACTED
TO 90% STANDARD PROCTOR PROVIDE 1/4" WASH ACROSS BOTTTON SELVAGE KNUCKLED
TOP OF FOOTING, TYP.
NOTES:
TENSION WIRE
1.INSTALLATION OF DECORATIVE LIGHTS SHALL BE COORDINATED WITH THE CITY ELECTRICIAN AND DEPARTMENT
OF PUBLIC WORKS. *WATTAGE SHALL BE AS DIRECTED BY CITY ELECTRICIAN.
2. THE OWNER/DEVELOPER IS RESPONSIBLE FOR ELECTRIFYING THE SYSTEM AND PAYING THE ELECTRIC BILLS
UNTIL ACCEPTED AND TAKEN OVER BY THE CITY OF SARATOGA SPRINGS. Drawing Title
3. ELECTRIC SERVICE: SWEEPS AT CONCRETE BASES AND BETWEEN BASES USE 2" SCH. 80 PVC NON-METALLIC
4' - 0"

CONDUIT. FOR WIRE: URD 3-CONDUCTOR NO. 2, 120 VOLT, 100 AMP CABLE. IF CONNECTING TO NATIONAL GRID FROM 3,000 PSI CONCRETE FOOTING 12" DIA.
A POLE, PROVIDE A SEPARATE HANDHOLE TO BE OWNED BY THE CITY FOR THE DISCONNECT AT THE BASE OF
ELECTRIC POLE AT THE BEGINNING OF ELECTRIC SERVICE. WIRE AND CONDUIT FROM HANDHOLE TO POLE PER
NATIONAL GRID STANDARDS. USE POLARIS CONNECTORS, CATALOG NUMBER IT-1/0, FOR CONNECTIONS IN
TYP. 18" DIA. @ GATE POSTS
Site Details
HANDHOLE AND IN BASE OF LIGHTS. EACH LIGHT TO BE FUSED IN BASE OF LAMP POLE WITH 10 AMP FUSE WITH
BUSSMANN HEB-AA IN-LINE FUSE HOLDER. IF CONNECTING MORE THAN THREE LIGHTS FROM THE SAME SOURCE OF
POWER, PROVIDE 30 AMP IN-LINE FUSE WITH WATERTIGHT FUSE HOLDER OF PROPER SIZE FOR WIRE. SEPARATE 10'-0" O.C. MAX Drawing No.
HANDHOLE IS NOT REQUIRED IF CONNECTING TO A NATIONAL GIRD HANDHOLE.

DECORATIVE STREET LIGHT CHAIN LINK FENCE DETAIL


2 SCALE: NTS 5 SCALE: NTS L-5
2017132
HEAVY DUTY FRAME ALLOW 2" FOR FINAL #4 BAR @ 6" O.C. EACH WAY
AND GRATE - CAMPBELL ADJUSTMENT OF FRAME WITH ADDITIONAL #4`S
NO. 2816B OR AROUND OPENING
APPROVED EQUAL FRAME TO BE MORTARED
(BICYCLE - SAFE) TO TOP OF CATCH BASIN
WITH NON-SHRINK GROUT 8"
3'-0
" ALLOW 2" FOR FINAL SAW-CUT EXIST. PVMT. IN TRUE LINE. KEY PVMT. AS MIN EXIST. PVMT.
ADJUSTMENT OF FRAME SHOWN. TACK COAT EXPOSED EDGES OF EXIST. PVMT. KEY
PRIOR TO PLACEMENT OF NEW PVMT. JT.
ITEM DEPTH MATERIAL METHOD OF

3"
CONCRETE COVER 2'-6" LAWN RESTORATION PVMT. RESTORATION
4'-0" PLACEMENT
PRECAST TO FIT MIN. I.D.** TOPSOIL & SEED
MIN. I.D.** NEW. PVMT., SEE DETAIL
GRATE 6" 6" AS SPECIFIED PIPE ZONE BEDDING 6" MIN.
CRUSHED STONE MECHANICAL
COMPACTION
PIPE ZONE BACKFILL 12" MIN. CRUSHED STONE MECHANICAL

18"
A COVER COMPACTION Unauthorized alteration or addition to this
*18" 1

4'-6" MIN. COVER SEWER


5'-0" MIN. COVER WATER
document is a violation of Section 7209 of the
1 1 FINAL TRENCH BACKFILL VARIES SEE NOTE MECHANICAL New York State Education Law.
SUBBASE MAT'L.; COMPACTION

*
1

6"

VARIES - AS REQUIRED
REFER
TO NEW PVMT. DETAIL © the LA Group 2018
A - A' B - B'
BURIED METALLIC NOTES:
1. FINAL TRENCH BACKFILL Prepared for:
TO 6'-0"

B' 8"-12" TYPE 2 CRUSHED STONE ON IDENTIFICATION


Fasig-Tipton
UNDISTURBED SUBGRADE OR
WARNING TAPE 1.a. IN NON-PAVED AREAS, FINAL TRENCH BACKFILL SHALL BE
A' ADDITIONAL FOUNDATION STONE EXCAVATED MATERIAL WHEN DETERMINED SUITABLE BY THE
A.O.B.E. FINAL TRENCH BACKFILL
Company, Inc.

5'-0" MAX.

MIN.
ENGINEER OF RECORD; OTHERWISE IT SHALL BE

12"
SECTIONS (SEE NOTE) STRUCTURAL FILL. MIN. MOD. PROCTOR DENSITY SHALL BE 85
N.T.S. PERCENT. 2400 Newtown Pike
CONCRETE - 4000 PSI @ 28 DAYS MIN.

O.D./2
PIPE ZONE BACKFILL 1.b. IN PAVED AREAS, FINAL TRENCH BACKFILL SHALL BE
3' - 6 REINFORCMENT - 6x6 - 10/10 WWM ALL FOUR STRUCTURAL FILL. MIN. MODIFIED PROCTOR DENSITY SHALL Lexington, KY 40511
"M
IN. IN. SIDES AND BOTTOM (CONFORM TO ASTM STD.
"M E
PIP D.
PIPE ZONE BEDDING BE 95 PERCENT.
B 5'-0 A-615) O. MAT'L 2. ALL PIPE ZONE BEDDING, PIPE ZONE BACKFILL, AND FINAL TRENCH
**CB-2 AND CB-9 TO BE MIN. 5'-0" ID BACKFILL SHALL BE PLACED IN 6 INCH MAX. COMPACTED LIFTS.
PIPE INSULATION ALL BEDDING AND BACKFILL MATERIALS SHALL BE MECHANICALLY
COMPACTED TO THE SATISFACTION OF THE ENGINEER.

6" MIN.
NOTES:
1. ALL CATCH BASINS TO BE PLACED IN ANY TRAFFIC AREAS SHALL MEET N.Y.S.D.O.T. HIGHWAY LOADING H-20 PIPE O.D. + 24" 3. EXCAVATION SHALL BE KEPT DRY AND DEWATERED AT ALL TIMES.
MIN.

CATCH BASIN DETAIL PIPE TRENCH SECTION


1 SCALE: NTS
5 SCALE: NTS

TREE BELT FINISHED GRADE

CURB SIDEWALK
CAST IRON MANHOLE FRAME AND COVER
2'-6" LABELED "STORM"
ROADWAY
FINISHED GRADE CLEAR OPENING

2'-6" MAX.
PRECAST CONCRETE GRADE RINGS
AS REQ'D TO ADJUSTCONE 8" 8" 6"(MIN.) TO 20"(MAX.) NO CONCRETE
CURB BOX; MUELLER 5'-6"± MODEL TO FINISHED GRADE.EXTENSION(S)
H-10314 (IN TURF) MODEL H-10334 (IN BRICK SHIM COURSES
USE PRECAST UNITS
CONCRETE WALK) (SIZE AS REQUIRED
5'-0" MIN.

FOR 1" SERVICE)


5'-0" MIN.

3'-0" MIN.
CURB STOP; MUELLER ORISEAL ECCENTRIC
1" COPPER TUBING MODEL H-15209 COMPRESSION, CONE
(TYPE K) (SIZE AS MODEL H-15219 (W/DRAIN) (SIZE AS SECTION PRECAST CONCRETE SECTIONS -
REQUIRED) REQUIRED FOR 1" SERVICE) 4,000 p.s.i. AT 28 DAYS, AIR-
SEE DETAIL ENTRAINED
CORPORATION STOP WITH FOR SPLICE REINFORCED PLASTIC NON-SLIP
COMPRESSION FITTING, TEMPORARY CAP OR STEPS PER NYSDOT 725-02.01 JOINTS BUTYL SEALED -

12" O.C.
MUELLER H-15008 1" PLUG AS NECESSARY INDUSTRY STD. OR A.O.B.E.

AS REQ'D
1" MIN, SIZE TYPE K
COPPER PIPE RISER
WATER SECTION 5"
45.0

MAIN 4'-0" ID MIN.*


°

SOLID CONC. CIRCUMFERENTIAL


BEARING BLOCK OR REINFORCEMENT 0.12 sq. in. PER LIN.
C.I. FOOT FT. MIN.

3' OR 4'
TYPICAL WATER SERVICE CONNECTION
2
SIZE AND LOCATION OF PIPES
BOTTOM AS SPECIFIED
SCALE: NTS
SECTION Project Title:

8"
12" CRUSHED STONE - #1 OR #2
NOMINAL SIZE OR GRADATION A.O.B.E. Fasig-Tipton
UNDISTURBED SUBGRADE OR ADDITIONAL George Street
6" SADDLE WITH STAINLESS
STEEL STRAP PER
FOUNDATION STONE A.O.B.E. Saratoga Springs, NY 12866
45° OR 30° BEND AS REQ'D
MANUFACTURERS
RECOMMENDATION, ROMAC PRECAST CONCRETE MANHOLE FOR STORM
INDUSTRIES, INC.
6 SCALE: NTS

EXISTING 30" CL HEAVY DUTY FRAME AND GRATE


SEWER MAIN SEWER LATERAL
FLOW

FINISH GRADE
SLOPE: 2% MIN. (1/4" PER FOOT)
45° OR 30° BEND
AS REQ'D
SELECT GRANULAR BACKFILL
NYLOPLAST YARD DRAIN OR
PIPE BEDDING AS REQ'D APPROVED EQUAL

6" MIN.
SUMP
UNDISTURBED SUB-GRADE
6" MIN.

45° CRUSHED STONE


Project No.: 2017132
COMPACTED SUBGRADE
Design: CMI
Drawn: DBH Ch'k'd: DBH

CONNECTION TO EXISTING SEWER MAIN Date: 2/8/2018 Scale: N.T.S.

3 SCALE: NTS 12" MIN. Rev: Description: Date:

FRAME AND COVER, LABELED STORM YARD DRAIN


7 SCALE: NTS

PRECAST CONCRETE RISER RING


FINISHED GRADE SET IN NON SHRINK GROUT.
8" TOP

CRUSHED STONE NYSDOT TABLE


24" DIA. 703-4 SIZE 3
Drawing Title

4'-0"

Site Details
4'-0"

1
1
GEOTEXTILE
SEPARATION
FABRIC, TOPS AND PRECAST CONCRETE DRYWELL Drawing No.
SIDES ONLY FOOTING
12"

DRYWELL
4 SCALE: NTS L-6
2
1

A2.1
A2.1

1/4"=1'-0"
1/4"=1'-0"

WEST ELEVATION (FACING CASE STREET)


NORTH ELEVATION (FACING GEORGE STREET)

T.O. FDN. WALL


T.O. PLATE

EL.=100'-0"
EL.=110'-6"

EL.=95'-8"
T.O. FTG.

4'-4" 10'-6"
T.O. FDN. WALL
T.O. PLATE

EL.=95'-8"
EL.=100'-0"
EL.=110'-6"

T.O. FTG.

4'-4" 10'-6"

1/4"=1'-0"
12.13.17 FASIG TIPTON

NORTH ELEVATION Barn
WEST ELEVATION George Street



Saratoga Springs, NY

T.O. PLATE

Saratoga Springs, NY
EL.=110'-6"

FASIG TIPTON

George Street
10'-6"

Barn
T.O. FDN. WALL
EL.=100'-0"

4'-4"
T.O. FTG.
EL.=95'-8"





1 SOUTH ELEVATION
1/4"=1'-0"
A2.1

1/4"=1'-0"
12.13.17

42" EXHAUST FAN MATCHED


TO EXISTING
FIBERGLASS SHINGLES MATCHED
TO EXISTING

T.O. PLATE
EL.=110'-6"

SOUTH ELEVATION
2" x 4" BRACES
10'-6"

@ 24" o.c.

EAST ELEVATION
5/4" x 6" FASCIA

5/4" x 6" CORNER BOARD

8" SIDING MATCHED TO EXISTING


8" POURED CONCRETE FOUNDATION

T.O. FDN. WALL


EL.=100'-0"
4'-4"

T.O. FTG.
EL.=95'-8"

2 EAST ELEVATION
1/4"=1'-0"
A2.1