Академический Документы
Профессиональный Документы
Культура Документы
Adjustments
Apply Individual
Tolerance Adjustments /Global Percent
Cable Length: No
Apply Individual
Temperature Correction Adjustments /Global Degree C
Load
Bus Initial Voltage Constant kVA Constant Z Constant I Generic
Load
Bus Initial Voltage Constant kVA Constant Z Constant I Generic
Total Number of Buses: 60 15.958 9.730 0.048 0.036 0.000 0.000 0.000 0.000
0.000 0.000
ETAP
Project: PLTMG PACKAGE III SELOR 15 MW Page: 6
12.6.5C
Location: TANJUNG SELOR Date: 17-03-2018
Contract: 0177.PJ/DAN.02.01/DIR/2017 SN: PUSTEKINDO
Engineer: MUHAMMAD FAHMY MADJID Revision: Base
Study Case: LF
Filename: PLTMG PACKAGE III TJ SELOR Config.: SCEN 1 NORM
Line/Cable Length
Line/Cable Length
ID Phase MVA Prim. kV Sec. kV % Z1 X1/R1 + 5% - 5% % Tol. Prim. Sec. %Z Type Angle
AKA-BBA-BAT NGR 40 OHM 3-Phase 11.500 11.000 20.000 8.00 13.00 0 0 0 0 0 8.0000 YNd 0.000
AKA-BBA-BBT 3-Phase 1.600 11.000 0.400 5.00 6.00 0 0 0 -2.500 0 5.0000 Dyn 0.000
AKA-BBB-BAT NGR 40 OHM 3-Phase 11.500 11.000 20.000 8.00 13.00 0 0 0 0 0 8.0000 YNd 0.000
AKA-BBB-BBT 3-Phase 1.600 11.000 0.400 5.00 6.00 0 0 0 -2.500 0 5.0000 Dyn 0.000
AKA-BBA-BAT NGR 40 OHM P-GT#1 * S-GT#1 -10.00 10.00 1.250 S-GT#1 100.00 20.000
AKA-BBB-BAT NGR 40 OHM P-GT#2 * S-GT#2 -10.00 10.00 1.250 S-GT#2 100.00 20.000
ETAP
Project: PLTMG PACKAGE III SELOR 15 MW Page: 9
12.6.5C
Location: TANJUNG SELOR Date: 17-03-2018
Contract: 0177.PJ/DAN.02.01/DIR/2017 SN: PUSTEKINDO
Engineer: MUHAMMAD FAHMY MADJID Revision: Base
Study Case: LF
Filename: PLTMG PACKAGE III TJ SELOR Config.: SCEN 1 NORM
Branch Connections
ID ID Type Library Size Adj. (m) % Tol #/ph T (°C) R X Y Adj.(ohm) % Tol
P-MBV-009 **02-MJV406KP001** Ind. Motor 1.0NCUN4 16 135.0 0.0 1 75 1.31239 .08010 .0000000 .0000 0.0
P-MJN-014 *00-EGC103KP002* Ind. Motor 1.0NCUN4 10 150.0 0.0 1 75 2.08877 .08450 .0000000 .0000 0.0
P-MJ-011 *00-UMX901KN003* Ind. Motor 1.0NCUN4 10 120.0 0.0 1 75 2.08877 .08450 .0000000 .0000 0.0
P-MJ-012 *00-UMX901KN004* Ind. Motor 1.0NCUN4 10 120.0 0.0 1 75 2.08877 .08450 .0000000 .0000 0.0
P-MJQ-004 *00-UMX901KN005* Ind. Motor 1.0NCUN4 16 120.0 0.0 1 75 1.31239 .08010 .0000000 .0000 0.0
P-MJQ-005 *00-UMX901KN006* Ind. Motor 1.0NCUN4 16 120.0 0.0 1 75 1.31239 .08010 .0000000 .0000 0.0
P-MJQ-006 *00-UMX901KN007* Ind. Motor 1.0NCUN4 4.0 115.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MJN-015 *02-MJN404KP001* Ind. Motor 1.0NCUN4 4.0 150.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MJN-016 *02-MJN404KP002* Ind. Motor 1.0NCUN4 4.0 150.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MJN-004 00-EGC101KP001 Ind. Motor 1.0NCUN4 4.0 150.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MJN-009 00-EGC101KP002 Ind. Motor 1.0NCUN4 4.0 150.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MJN-011 00-EGC103KP001 Ind. Motor 1.0NCUN4 10 150.0 0.0 1 75 2.08877 .08450 .0000000 .0000 0.0
P-MJN-006 00-EGC103KP003 Ind. Motor 1.0NCUN4 4.0 150.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MJN-010 00-EGC103KP004 Ind. Motor 1.0NCUN4 4.0 150.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MBV-001 00-LVC104KP001 Ind. Motor 1.0NCUN4 4.0 135.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MBV-002 00-LVC105KP001 Ind. Motor 1.0NCUN4 4.0 135.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MBV-005 00-LVC105KP002 Ind. Motor 1.0NCUN4 4.0 135.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MJ-009 00-UMX901KN001 Ind. Motor 1.0NCUN4 10 120.0 0.0 1 75 2.08877 .08450 .0000000 .0000 0.0
P-MJ-010 00-UMX901KN002 Ind. Motor 1.0NCUN4 10 120.0 0.0 1 75 2.08877 .08450 .0000000 .0000 0.0
P-MJQ-001 00-UMX901KN003 Ind. Motor 1.0NCUN4 16 120.0 0.0 1 75 1.31239 .08010 .0000000 .0000 0.0
P-MJQ-002 00-UMX901KN004 Ind. Motor 1.0NCUN4 16 120.0 0.0 1 75 1.31239 .08010 .0000000 .0000 0.0
P-MJQ-003 00-UMX901KN005 Ind. Motor 1.0NCUN4 4.0 115.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MJG-003 01-MJG407KP001-004 Ind. Motor 1.0NCUN4 4.0 130.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MJG-007~ 01-MJG408KP001-004 Ind. Motor 1.0NCUN4 4.0 130.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MJN-001 01-MJN401KP001 Ind. Motor 1.0NCUN4 4.0 150.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MJN-012 01-MJN403KP001 Ind. Motor 1.0NCUN4 4.0 150.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MJN-013 01-MJN403KP002 Ind. Motor 1.0NCUN4 4.0 150.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MJ-005 01-MJV405KT002 Ind. Motor 1.0NCUN4 4.0 105.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MJG-004 02-MJG407KP002-004 Ind. Motor 1.0NCUN4 4.0 130.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MJG-008~ 02-MJG408KP002-004 Ind. Motor 1.0NCUN4 4.0 130.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MJN-007 02-MJN402KP001 Ind. Motor 1.0NCUN4 4.0 150.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
P-MBV-006~ 02-MJV406KP001 Ind. Motor 1.0NCUN4 25 135.0 0.0 1 75 1.31239 .08010 .0000000 .0000 0.0
P-MJ-007 02-MJV406KT002 Ind. Motor 1.0NCUN4 4.0 105.0 0.0 1 75 5.26102 .00950 .0000000 .0000 0.0
ETAP
Project: PLTMG PACKAGE III SELOR 15 MW Page: 12
12.6.5C
Location: TANJUNG SELOR Date: 17-03-2018
Contract: 0177.PJ/DAN.02.01/DIR/2017 SN: PUSTEKINDO
Engineer: MUHAMMAD FAHMY MADJID Revision: Base
Study Case: LF
Filename: PLTMG PACKAGE III TJ SELOR Config.: SCEN 1 NORM
AC Rating
kV FLA DC Rating Bypass
Operating
ID MVA Input Output Input Output % EFF % PF kV FLA % Imax % PF Switch
ANE-BRC-001 0.030 0.400 0.230 48.11 75.31 90.00 88.00 0.110 253.333 150.0 88.00 No
ANE-BRC-002 0.030 0.400 0.230 48.11 75.31 90.00 88.00 0.110 253.333 150.0 88.00 No
ETAP
Project: PLTMG PACKAGE III SELOR 15 MW Page: 13
12.6.5C
Location: TANJUNG SELOR Date: 17-03-2018
Contract: 0177.PJ/DAN.02.01/DIR/2017 SN: PUSTEKINDO
Engineer: MUHAMMAD FAHMY MADJID Revision: Base
Study Case: LF
Filename: PLTMG PACKAGE III TJ SELOR Config.: SCEN 1 NORM
ANA-00-GC603 0.400 100.624 -0.5 0 0 0.011 0.007 ANA-BBD-02 -0.011 -0.007 18.6 83.7
ANA-00-GNK701 0.400 100.701 -0.6 0 0 0.008 0.005 ANA-BBC-02 -0.008 -0.005 13.1 83.2
ANA-00SGA801 0.400 101.015 -0.8 0 0 0.011 0.007 ANA-BBA -0.011 -0.007 18.8 83.8
ANA-01-MJG407 0.400 100.893 -0.8 0 0 0.010 0.007 ANA-BBE-02 -0.010 -0.007 17.2 80.0
ANA-01-MJV405 0.400 99.813 -0.7 0 0 0.077 0.058 ANA-BBE-02 -0.077 -0.058 139.8 80.0
ANA-02-MJG408 0.400 101.214 -0.9 0 0 0.010 0.000 ANA-BBF-02 -0.010 0.000 13.7 99.9
ANA-02-MJV406 0.400 99.408 -1.0 0 0 0.077 0.005 ANA-BBF-02 -0.077 -0.005 112.6 99.7
ANA-BBC-02 0.400 101.349 -0.8 0 0 0.016 0.011 T-ANE-BKV-001 0.079 0.000 112.1 100.0
ANA-BBD-02 0.400 101.636 -0.8 0 0 0.015 0.011 T-ANE-BKA-001 0.122 0.000 173.9 100.0
ANA-BBE-02 0.400 101.108 -0.8 0 0 0.087 0.053 T-ANK-BTW-001 0.005 0.004 9.0 75.3
ANA-BBF-02 0.400 101.453 -0.8 0 0 0.080 0.048 T-ANK-BTW-002 0.005 0.004 9.1 75.6
NLBusA 20.000 99.514 -3.0 0 0 7.500 4.648 AJA-BBA -7.500 -4.648 256.0 85.0
NLBusB 20.000 99.514 -3.0 0 0 7.500 4.648 AJA-BBB -7.500 -4.648 256.0 85.0
T-*BAA-CXB-001* 0.400 101.170 -0.8 0 0 0.002 0.000 ANA-BBF-02 -0.002 0.000 2.3 100.0
T-00-EGC102KP001 0.400 100.760 -0.5 0 0 0.001 0.001 ANA-BBC-02 -0.001 -0.001 2.1 80.0
T-00-EGC102KP002 0.400 101.049 -0.6 0 0 0.001 0.001 ANA-BBD-02 -0.001 -0.001 2.1 80.0
T-00-EGC102KT001 0.400 99.317 0.0 0 0 0.006 0.004 ANA-BBC-02 -0.006 -0.004 10.9 80.0
T-00-EGC103KP005 0.400 100.760 -0.5 0 0 0.001 0.001 ANA-BBC-02 -0.001 -0.001 2.1 80.0
T-00-GAF901 KP001 0.400 100.126 -0.2 0 0 0.003 0.002 ANA-BBD-02 -0.003 -0.002 4.8 80.0
T-00-MJP505KN001 0.400 98.334 0.0 0 0 0.032 0.020 ANA-BBE-02 -0.032 -0.020 55.1 85.0
T-00-MJP505KN002 0.400 101.184 -0.8 0 0 0.003 0.002 ANA-BBF-02 -0.003 -0.002 5.4 85.0
T-00-MJQ507KT001 0.400 100.931 -0.6 0 0 0.001 0.001 ANA-BBC-02 -0.001 -0.001 2.2 80.0
T-01-MJG510KC001 0.400 99.931 -0.5 0 0 0.099 0.061 ANA-BBC-02 -0.099 -0.061 168.0 85.0
T-02-MJG511KC001 0.400 100.222 -0.5 0 0 0.099 0.061 ANA-BBD-02 -0.099 -0.061 167.5 85.0
T-02-MJQ507KT002 0.400 101.179 -0.6 0 0 0.001 0.001 ANA-BBD-02 -0.001 -0.001 2.2 80.0
T-ANE-BKA-1 0.400 101.022 -0.8 0 0 0.004 0.000 ANA-BBE-02 -0.004 0.000 5.0 100.0
T-ANE-BKA-001 0.400 101.239 -0.9 0 0 0.122 0.000 ANA-BBD-02 -0.122 0.000 173.9 100.0
T-ANE-BKA-002 0.400 101.368 -0.8 0 0 0.004 0.000 ANA-BBF-02 -0.004 0.000 5.0 100.0
T-ANE-BKV-001 0.400 100.168 -0.9 0 0 0.078 0.000 ANA-BBC-02 -0.078 0.000 112.1 100.0
T-ANE-BRC-001 0.400 100.039 -0.5 0 0 0.027 0.014 ANA-BBE-02 -0.027 -0.014 43.7 88.0
T-ANE-BRC-002 0.400 100.388 -0.5 0 0 0.027 0.014 ANA-BBF-02 -0.027 -0.014 43.6 88.0
T-ANK-BTW-001 0.400 100.643 -0.6 0 0 0.005 0.004 ANA-BBE-02 -0.005 -0.004 9.0 75.0
T-ANK-BTW-002 0.400 100.442 -0.3 0 0 0.005 0.004 ANA-BBF-02 -0.005 -0.004 9.1 75.0
T-BAA-CXA-001 0.400 98.394 -0.1 0 0 0.042 0.026 ANA-BBE-02 -0.042 -0.026 72.7 85.0
T-BAA-CXA-002 0.400 98.748 -0.1 0 0 0.042 0.026 ANA-BBF-02 -0.042 -0.026 72.4 85.0
T-BAA-CXB-001 0.400 100.824 -0.8 0 0 0.002 0.000 ANA-BBE-02 -0.002 0.000 2.3 100.0
* T-ENG#1 11.000 100.000 0.0 8.078 5.532 0 0 AKA-BBA 8.078 5.532 513.9 82.5
* T-ENG#2 11.000 100.000 0.0 8.070 5.438 0 0 AKA-BBB 8.070 5.438 510.8 82.9
ANE-BRC-001 0.230 100.000 0.0 0.024 0.018 0 0 L-ANE-BRC-001 0.024 0.018 75.3 80.0
ANE-BRC-002 0.230 100.000 0.0 0.024 0.018 0 0 L-ANE-BRC-002 0.024 0.018 75.3 80.0
* Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA
ETAP
Project: PLTMG PACKAGE III SELOR 15 MW Page: 17
12.6.5C
Location: TANJUNG SELOR Date: 17-03-2018
Contract: 0177.PJ/DAN.02.01/DIR/2017 SN: PUSTEKINDO
Engineer: MUHAMMAD FAHMY MADJID Revision: Base
Study Case: LF
Filename: PLTMG PACKAGE III TJ SELOR Config.: SCEN 1 NORM
* Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).
# Indicates operating load of a bus exceeds the bus marginal limit ( 95.0% of the Continuous Ampere rating).
ETAP
Project: PLTMG PACKAGE III SELOR 15 MW Page: 19
12.6.5C
Location: TANJUNG SELOR Date: 17-03-2018
Contract: 0177.PJ/DAN.02.01/DIR/2017 SN: PUSTEKINDO
Engineer: MUHAMMAD FAHMY MADJID Revision: Base
Study Case: LF
Filename: PLTMG PACKAGE III TJ SELOR Config.: SCEN 1 NORM
Transformer
CKT / Branch Cable & Reactor
Ampacity Loading Capability Loading (input) Loading (output)
Transformer
CKT / Branch Cable & Reactor
Ampacity Loading Capability Loading (input) Loading (output)
Vd
CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop
ID MW Mvar MW Mvar kW kvar From To in Vmag
P-BBA-001 7.501 4.649 -7.500 -4.648 1.3 1.1 99.5 99.5 0.02
P-BBA-003 -7.501 -4.649 7.503 4.651 2.0 1.4 99.5 99.6 0.03
P-BBA-004 7.501 4.649 -7.500 -4.648 1.3 1.1 99.5 99.5 0.02
P-BBA-006 -7.501 -4.649 7.503 4.651 2.0 1.4 99.5 99.6 0.03
P-BBA-007 008 -8.070 -5.528 8.078 5.532 7.9 3.6 99.9 100.0 0.09
P-BBA-009 0.518 0.289 -0.518 -0.289 0.0 0.0 99.9 99.9 0.01
P-MJ-013 014 7.552 5.239 -7.548 -5.238 3.3 1.5 99.9 99.9 0.04
P-BBA-012 013 -8.062 -5.435 8.070 5.438 7.8 3.6 99.9 100.0 0.09
P-BBA-014 0.510 0.196 -0.510 -0.196 0.0 0.0 99.9 99.9 0.00
P-MJ-015 016 7.552 5.239 -7.548 -5.238 3.3 1.5 99.9 99.9 0.04
P-PD-001 -0.011 -0.007 0.011 0.007 0.1 0.0 100.6 101.6 1.01
P-RU-001 -0.008 -0.005 0.008 0.005 0.1 0.0 100.7 101.3 0.65
P-SG-001 -0.011 -0.007 0.011 0.007 0.0 0.0 101.0 101.3 0.33
P-MJG-007 -0.010 -0.007 0.010 0.007 0.0 0.0 100.9 101.1 0.21
P-MBV-007 -0.077 -0.058 0.078 0.059 1.1 0.6 99.8 101.1 1.29
P-MJG-008 -0.010 0.000 0.010 0.000 0.0 0.0 101.2 101.5 0.24
P-MBV-008 -0.077 -0.005 0.079 0.006 1.6 0.4 99.4 101.5 2.04
P-BF-001-003 0.291 0.184 -0.290 -0.184 0.6 0.5 101.3 101.1 0.24
AKA-BBA-BBT -0.516 -0.279 0.518 0.289 1.7 10.3 101.3 99.9 1.44
P-BF-004-006 0.253 0.102 -0.252 -0.102 0.4 0.3 101.6 101.5 0.18
AKA-BBB-BBT -0.509 -0.187 0.510 0.196 1.5 8.8 101.6 99.9 1.73
P-BKV-007 0.079 0.000 -0.078 0.000 0.9 0.2 101.3 100.2 1.18
P-MBV-003 0.000 0.000 0.000 0.000 0.0 0.0 101.3 101.3 0.05
P-MBV-004 0.001 0.001 -0.001 -0.001 0.0 0.0 101.3 101.0 0.37
P-MJ-006 0.001 0.001 -0.001 -0.001 0.0 0.0 101.3 100.9 0.42
P-MJG-001 0.001 0.001 -0.001 -0.001 0.0 0.0 101.3 101.0 0.36
P-MJG-002 003 0.101 0.062 -0.099 -0.061 1.7 0.4 101.3 99.9 1.42
P-MJN-002 0.001 0.001 -0.001 -0.001 0.0 0.0 101.3 100.8 0.59
P-MJN-003 0.001 0.001 -0.001 -0.001 0.0 0.0 101.3 100.8 0.59
P-MJN-005 0.006 0.004 -0.006 -0.004 0.2 0.0 101.3 99.3 2.03
P-SM-001 0.001 0.000 -0.001 0.000 0.0 0.0 101.3 101.1 0.24
P-BF-008 0.122 0.000 -0.122 0.000 0.5 0.2 101.6 101.2 0.40
P-MGJ-004 0.001 0.001 -0.001 -0.001 0.0 0.0 101.6 101.3 0.36
P-MJ-008 0.001 0.001 -0.001 -0.001 0.0 0.0 101.6 101.2 0.46
P-MJG-005 0.101 0.062 -0.099 -0.061 1.7 0.4 101.6 100.2 1.41
ETAP
Project: PLTMG PACKAGE III SELOR 15 MW Page: 22
12.6.5C
Location: TANJUNG SELOR Date: 17-03-2018
Contract: 0177.PJ/DAN.02.01/DIR/2017 SN: PUSTEKINDO
Engineer: MUHAMMAD FAHMY MADJID Revision: Base
Study Case: LF
Filename: PLTMG PACKAGE III TJ SELOR Config.: SCEN 1 NORM
Vd
CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop
ID MW Mvar MW Mvar kW kvar From To in Vmag
P-MJN-008 0.001 0.001 -0.001 -0.001 0.0 0.0 101.6 101.0 0.59
P-PD-004 0.003 0.002 -0.003 -0.002 0.1 0.0 101.6 100.1 1.51
P-SM-002 0.001 0.000 -0.001 0.000 0.0 0.0 101.6 101.5 0.15
P-BAT-001 0.005 0.004 -0.005 -0.004 0.0 0.0 101.1 100.6 0.46
P-BF-1 0.004 0.000 -0.004 0.000 0.0 0.0 101.1 101.0 0.09
P-BFA-001 0.002 0.000 -0.002 0.000 0.0 0.0 101.1 100.8 0.28
P-BR-001 0.027 0.014 -0.027 -0.014 0.4 0.0 101.1 100.0 1.07
P-CUA-001 0.044 0.026 -0.042 -0.026 1.5 0.1 101.1 98.4 2.71
P-SCA-001 0.033 0.020 -0.032 -0.020 1.2 0.1 101.1 98.3 2.77
P-SCA-002 0.001 0.001 -0.001 -0.001 0.0 0.0 101.1 100.8 0.27
P-BAT-004 0.005 0.004 -0.005 -0.004 0.1 0.0 101.5 100.4 1.01
P-BF-010 0.004 0.000 -0.004 0.000 0.0 0.0 101.5 101.4 0.08
P-BFA-002 0.002 0.000 -0.002 0.000 0.0 0.0 101.5 101.2 0.28
P-BR-004 0.027 0.014 -0.027 -0.014 0.4 0.0 101.5 100.4 1.06
P-CUA-002 0.044 0.026 -0.042 -0.026 1.5 0.1 101.5 98.7 2.70
P-SCA-003 0.003 0.002 -0.003 -0.002 0.0 0.0 101.5 101.2 0.27
P-SCA-004 0.000 0.000 0.000 0.000 0.0 0.0 101.5 101.4 0.05
AKA-BBA-BAT NGR 40 OHM 7.548 5.238 -7.503 -4.651 45.2 587.0 99.9 99.6 0.31
AKA-BBB-BAT NGR 40 OHM 7.548 5.238 -7.503 -4.651 45.2 587.0 99.9 99.6 0.31
136.6 1211.6
ETAP
Project: PLTMG PACKAGE III SELOR 15 MW Page: 23
12.6.5C
Location: TANJUNG SELOR Date: 17-03-2018
Contract: 0177.PJ/DAN.02.01/DIR/2017 SN: PUSTEKINDO
Engineer: MUHAMMAD FAHMY MADJID Revision: Base
Study Case: LF
Filename: PLTMG PACKAGE III TJ SELOR Config.: SCEN 1 NORM
% Voltage
Connected Load Cable /Overload Heater Losses Terminal on
% Vd % Vst
ID Type ID Library kW kvar Bus Bus kV Load kV Operating Starting
01-MJN401KP001 Ind. Motor P-MJN-001 1.0NCUN4 0.0 0.0 101.35 101.06 101.06 0.29 99.58
00-EGC101KP001 Ind. Motor P-MJN-004 1.0NCUN4 0.1 0.0 101.35 99.17 99.17 2.18 91.73
00-EGC103KP003 Ind. Motor P-MJN-006 1.0NCUN4 0.0 0.0 101.35 101.06 101.06 0.29 99.55
00-LVC104KP001 Ind. Motor P-MBV-001 1.0NCUN4 0.0 0.0 101.35 101.24 101.24 0.11 95.97
00-LVC105KP001 Ind. Motor P-MBV-002 1.0NCUN4 0.0 0.0 101.35 100.81 100.81 0.54 95.97
01-MJV405KT002 Ind. Motor P-MJ-005 1.0NCUN4 0.1 0.0 101.35 100.20 100.20 1.15 95.89
01-MJG407KP001-004 Ind. Motor P-MJG-003 1.0NCUN4 0.0 0.0 101.35 100.29 100.29 1.06 96.10
02-MJG407KP002-004 Ind. Motor P-MJG-004 1.0NCUN4 0.0 0.0 101.35 100.29 100.29 1.06 96.10
02-MJN402KP001 Ind. Motor P-MJN-007 1.0NCUN4 0.0 0.0 101.64 101.35 101.35 0.29 99.87
00-EGC101KP002 Ind. Motor P-MJN-009 1.0NCUN4 0.1 0.0 101.64 99.46 99.46 2.17 91.99
00-EGC103KP004 Ind. Motor P-MJN-010 1.0NCUN4 0.0 0.0 101.64 101.34 101.34 0.29 99.83
00-LVC105KP002 Ind. Motor P-MBV-005 1.0NCUN4 0.0 0.0 101.64 101.10 101.10 0.54 96.24
02-MJV406KT002 Ind. Motor P-MJ-007 1.0NCUN4 0.1 0.0 101.64 100.49 100.49 1.15 96.16
01-MJG408KP001-004 Ind. Motor P-MJG-007~ 1.0NCUN4 0.0 0.0 101.64 100.58 100.58 1.05 96.38
02-MJG408KP002-004 Ind. Motor P-MJG-008~ 1.0NCUN4 0.0 0.0 101.64 100.59 100.59 1.04 96.43
02-MJV406KP001 Ind. Motor P-MBV-006~ 1.0NCUN4 0.0 0.0 101.11 100.83 100.83 0.28 91.50
00-UMX901KN001 Ind. Motor P-MJ-009 1.0NCUN4 0.3 0.0 101.11 99.12 99.12 1.99 93.76
00-UMX901KN002 Ind. Motor P-MJ-010 1.0NCUN4 0.3 0.0 101.11 99.12 99.12 1.99 93.76
00-UMX901KN003 Ind. Motor P-MJQ-001 1.0NCUN4 0.8 0.1 101.11 98.56 98.56 2.54 92.57
00-UMX901KN004 Ind. Motor P-MJQ-002 1.0NCUN4 0.8 0.1 101.11 98.56 98.56 2.54 92.57
00-UMX901KN005 Ind. Motor P-MJQ-003 1.0NCUN4 0.0 0.0 101.11 101.02 101.02 0.09 96.52
00-EGC103KP001 Ind. Motor P-MJN-011 1.0NCUN4 0.2 0.0 101.11 99.46 99.46 1.65 94.62
01-MJN403KP001 Ind. Motor P-MJN-012 1.0NCUN4 0.0 0.0 101.11 100.81 100.81 0.29 99.31
01-MJN403KP002 Ind. Motor P-MJN-013 1.0NCUN4 0.0 0.0 101.11 101.08 101.08 0.03 99.35
*00-UMX901KN003* Ind. Motor P-MJ-011 1.0NCUN4 0.3 0.0 101.45 99.47 99.47 1.98 94.08
*00-UMX901KN004* Ind. Motor P-MJ-012 1.0NCUN4 0.3 0.0 101.45 99.47 99.47 1.98 94.08
*00-UMX901KN005* Ind. Motor P-MJQ-004 1.0NCUN4 0.8 0.1 101.45 98.92 98.92 2.53 92.89
*00-UMX901KN006* Ind. Motor P-MJQ-005 1.0NCUN4 0.8 0.1 101.45 98.92 98.92 2.53 92.89
*00-UMX901KN007* Ind. Motor P-MJQ-006 1.0NCUN4 0.0 0.0 101.45 101.36 101.36 0.09 96.85
*00-EGC103KP002* Ind. Motor P-MJN-014 1.0NCUN4 0.0 0.0 101.45 101.29 101.29 0.16 94.94
*02-MJN404KP001* Ind. Motor P-MJN-015 1.0NCUN4 0.0 0.0 101.45 101.16 101.16 0.29 99.65
*02-MJN404KP002* Ind. Motor P-MJN-016 1.0NCUN4 0.0 0.0 101.45 101.42 101.42 0.03 99.69
**02-MJV406KP001** Ind. Motor P-MBV-009 1.0NCUN4 0.0 0.0 101.45 101.17 101.17 0.28 91.81
ETAP
Project: PLTMG PACKAGE III SELOR 15 MW Page: 24
12.6.5C
Location: TANJUNG SELOR Date: 17-03-2018
Contract: 0177.PJ/DAN.02.01/DIR/2017 SN: PUSTEKINDO
Engineer: MUHAMMAD FAHMY MADJID Revision: Base
Study Case: LF
Filename: PLTMG PACKAGE III TJ SELOR Config.: SCEN 1 NORM
% Alert Settings
Critical Marginal
Loading
Bus 100.0 95.0
Bus Voltage
OverVoltage 110.0 107.0
Generator Excitation
OverExcited (Q Max.) 110.0 105.0
MW Mvar MVA % PF
Number of Iterations: 1