L&T Construction

Water & Effluent Treatment IC


Sewage Network & Decentralized Sewage Treatment Plants DOCUMENT NO. DATE
PROJECT:
for Nellore Municipal Corporation LE160315-C-WW-SW-DC-3008 10-Jan-17
DESIGNED CHECKED SHEET
STRUCTURE: Design calculation for SBR at Drivers Colony
MCL SURE

Load Calculation

3.1 Hydrodynamic Load calculation for SBR

Ground supported Rectangular Concrete Tank

FGL 20.7

TOW (SBR) 26.25


From GA
top of raft (SBR) 20.75

Maximum Water Level(MWL) '= 25.75

Length of Tank = 30 m

Width of Tank = 21.5 m

Height of wall = 5.5 m

Height of water = 5m

Thickness of Base slab = 0.2 m

Grade of Concrete M 30

Grade of Steel Fe 500

Thickness of Wall = 0.375 m

Projection of Base slab = 0m

Earth quake Zone III

Modulus of Elasticity of concrete E = 5000 fck = 2.74E+07 kN/m2

1 Weight Calculation
L&T Construction
Water & Effluent Treatment IC
Sewage Network & Decentralized Sewage Treatment Plants DOCUMENT NO. DATE
PROJECT:
for Nellore Municipal Corporation LE160315-C-WW-SW-DC-3008 10-Jan-17
DESIGNED CHECKED SHEET
STRUCTURE: Design calculation for SBR at Drivers Colony
MCL SURE

i Self Weight of Wall = 5310.9375 kN

Mass of tank Wall mw = 541380 kg

ii Weight of Base Slab = 3420.9375 kN

Mass of Base slab mb = 348719.4 kg

iii Weight of Water =(30x21.5)x5x10.1 = 32572.5 kN

Mass of Water m = 3320336.391 kg

iv Total seismic weight of tank 41304.375 kN

For Rectangular Tank,

2 Analysis along Y-Direction

Length L= 30 m

Breadth B= 21.5 m

Height of water h= 5m

Unit weight of sewage = 10.1 kN/m3

Mass density of water = ρ= 1029.56 kg/cum.

2.1 Parameters of Spring Mass Model

For h/L = = 5/30 = 0.17


table C1,Pg-
mi/m = tanh(0.866(L/h))/(0.866(L/h) = 0.2
16, GSDMA

mi = 0.2x3320336.4 = 664067.2783 kg
table C1,Pg-
mc/m = 0.264tanh(3.16(h/L))/(0.866(L/h)) = 0.76
16, GSDMA

mc = 0.76x3320336.4 = 2523455.657 kg

hi/h = 0.375 hi = 1.875 m

hc/h = 0.512 hc = 2.56 m


table C1,Pg-
16, GSDMA
hi*/h = 2.422 hi* = 12.11 m

hc*/h = 3.849 hc* = 19.245 m

2.2 Time Period


Cl. 4.3.1.2
Time Period of Impulsive mode Ti = 2π d/g
GSDMA
ℎ  
d = deflection of tank wall on the vertical center-line at a height
L&T Construction
Water & Effluent Treatment IC
Sewage Network & Decentralized Sewage Treatment Plants DOCUMENT NO. DATE
PROJECT:
for Nellore Municipal Corporation LE160315-C-WW-SW-DC-3008 10-Jan-17
DESIGNED CHECKED SHEET
STRUCTURE: Design calculation for SBR at Drivers Colony
MCL SURE

q = Uniformly distributed pressure


ℎ  =  (𝑚_𝑖/2 ℎ_𝑖+𝑚  _𝑤  
Cl. 4.3.1.2 ℎ/2)/(𝑚_𝑖/2+𝑚  _𝑤 )
GSDMA
where,

̄̄̄
𝑚  _𝑤 =
mass of one tank wall perpendiculat to direction of loading

=21.5xtx25x1000/9.81 = 113006.5 kg
ℎ   =
2.03 m
q=  (𝑚_𝑖/2+𝑚  _𝑤 )𝑔/𝐵ℎ
q= 40.61 kN/m2

Deflection per unit width of strip: considered as cantilever and subjected to

concentrated force P= qxhx1 = 203.05 kN


ℎ  
with the length of cantilever =
�=  (𝑃ℎ  ^3)/(3𝐸𝐼_𝑤 )

Iw = Moment of Inertia of Cantilever = 1.0x0.375x0.375x0.375/12 = 4.40E-03 m4

Hence, d = 203.05x2.03³/(3x27386127.88x0.0044) = 4.70E-03 m4

Time Period Ti = 0.138 sec

Time Period of Convective mode T c = Cc L/g

for h/L = 0.17 From C4.3.2.2 GSDMA Cc = 5.04

Time Period Tc = 8.814 sec

2.3 Design of Horizontal Seismic Coefficient

a Design of Horizontal Seismic Coefficient for impulsive mode


(𝐴_ℎ )_𝑖=  𝑍/2  𝐼/𝑅 
(𝑆_𝑎/𝑔)_𝑖 Medium soil

where

(IS 1893(part I): Table 2: Zone III) Z= 0.16

(Table 6) I= 1.5
L&T Construction
Water & Effluent Treatment IC
Sewage Network & Decentralized Sewage Treatment Plants DOCUMENT NO. DATE
PROJECT:
for Nellore Municipal Corporation LE160315-C-WW-SW-DC-3008 10-Jan-17
DESIGNED CHECKED SHEET
STRUCTURE: Design calculation for SBR at Drivers Colony
MCL SURE

IS 1893(part II): Table 3 RC tank is pinned/fixed at base, R = 2.5

for impulsive mode damping = 5 % 0.05

Damping 5% for Medium soil 0.138 < 0.55 (Sa/g)i = 2.5

(Ah)i = 0.16x1.5x2.5/(2x2.5) = 0.1200

b Design of Horizontal Seismic Coefficient for Convective mode


(𝐴_ℎ )_𝑐=  𝑍/2  𝐼/𝑅 
(𝑆_𝑎/𝑔)_𝑐

where

(IS 1893(part I): Table 2: Zone III) Z= 0.16

(Table 6) I= 1.5

RC tank is pinned/fixed at base, R = 2.5

for impulsive mode damping = 0.5 % 0.005

Damping 0.5% for Medium soil 8.814 > 0.55 (Sa/g)c = 0.154
cl 4.5.2, IS
muiltiplying factor 1.75 (Sa/g)c = 0.270
1893 part -2

(Ah)c = 0.16x1.5x0.27/(2x2.5) = 0.013

2.4 Base Shear

Base Shear at the bottom of wall in impulsive mode


cl. 4.6.1,
Vi =(Ah)i (mi+mw+mt) g = 0.12x(664067.28+541380+0)x9.81/1000 = 1419.05 kN
GSDMA

Similarly, Base shear in convective mode


cl. 4.6.1,
Vc =(Ah)c mc g = 0.013x2523455.66x9.81/1000 = 320.86 kN
GSDMA

cl. 4.6.3,
GSDMA
Total base shear at the bottom of wall

V = Vi2+Vc2 = 1419.05²+320.86² = 1454.87 kN

This lateral base shear is about 4% of total seismic weight (41304.4kN ) of tank

2.5 Moment at Bottom of Wall


L&T Construction
Water & Effluent Treatment IC
Sewage Network & Decentralized Sewage Treatment Plants DOCUMENT NO. DATE
PROJECT:
for Nellore Municipal Corporation LE160315-C-WW-SW-DC-3008 10-Jan-17
DESIGNED CHECKED SHEET
STRUCTURE: Design calculation for SBR at Drivers Colony
MCL SURE

Bending Moment at the Bottom of wall in impulsive mode,


cl. 4.7.1.1,
Mi =(Ah)i (mihi+mwhw+mtht) g = 0.12x(664067.28x1.875+3420.94x5.5/2+0)x9.81/1000 = 3218.37 kNm
GSDMA

Bending Moment at the Bottom of wall in convective mode,


cl. 4.7.1.1,
Mc =(Ah)c mchc g = 0.01x2523455.66x2.56x9.81/1000 = 821.39 kNm
GSDMA

Total Bending Moment at the bottom of wall

M = Mi2+Mc2 = 3218.37²+821.39² = 3321.54 kNm

2.6 Overturning Moment

Overturning Moment at the Bottom of Base slab in impulsive mode,


cl. 4.7.1.2,
Mi* = (Ah)i [mi(hi*+tb) + mw(hw+tb) + mt(ht+tb) + mbtb/2] g
GSDMA

= 0.12[664067.28x(12.11+0.2) + 541380x(2.75+0.2)+ 0 +348719.4x0.1]x9.81 = 11544.34 kNm

Similarly, overturning Moment in convective mode,


cl. 4.7.1.2,
Mc* = (Ah)c mc(hc*+tb)
GSDMA

= 0.01 x 2523455.66x(19.245+0.2)x9.81 = 6239.04 kNm


cl. 4.7.1.3,
GSDMA
Total overturning Moment at the bottom of base slab

M* = Mi*2+Mc*2 = 11544.34²+6239.04² = 13122.40 kNm

Stabilizing Moment

(Mass of water + Mass of wall + mass of raft) x ( L/2+tw + raft projn)

(541380+348719.4+3320336.39)x(15.2)x9.81= 627826.5017 kNm

Check for over turning

Restoring moment / Overturning moment =627826.5/13122.4 = 47.84

Hence 47.84>1.4 Safe

2.7 Hydrodynamic Pressure

2.7.1 Impulsive Hydrodynamic Pressure

Impulsive hydrodynamic pressure on wall is


L&T Construction
Water & Effluent Treatment IC
Sewage Network & Decentralized Sewage Treatment Plants DOCUMENT NO. DATE
PROJECT:
for Nellore Municipal Corporation LE160315-C-WW-SW-DC-3008 10-Jan-17
DESIGNED CHECKED SHEET
STRUCTURE: Design calculation for SBR at Drivers Colony
MCL SURE

piw = Qiw(y) (Ah)i ρ g h


cl. 4.9.1(b),
GSDMA
Qiw(y) = 0.866 [ 1- (y/h)2] tanh(0.866 L/ h)

At base of wall, y=0

Qiw(y = 0) = 0.866 [1-(0/5)²]xtanh(0.866x30/5) = 0.87

Impulsive pressure at the base of wall

piw(y = 0) = 0.87x0.12x 1029.56 x 9.81 x5 = 5.25 kN/m2

Impulsive hydrodynamic pressure on the base slab (y=0) is

pib = Qib(x) (Ah)i ρ g h


cl. 4.9.1(b),
GSDMA
Qib(x) = sinh(0.866(x/h))/cosh(0.866 L/ h) x = L/2 = 15

Qib(x) = sinh(0.866x15/5)/cosh(0.866x30/5) = 1.00

Impulsive pressure on top of base slab(y=0)

pib(y = 0) = 1x0.01x 1029.56 x 9.81 x5 = 0.65 kN/m2

2.7.2 Convective Hydrodynamic Pressure

Convective hydrodynamic pressure on wall is

pcw = Qcw(y) (Ah)c ρ g L


cl. 4.9.2(b),
GSDMA
Qcw(y) = 0.4165 cosh(3.162y/L)/cosh(3.162 h/ L)

At base of wall, y=0

Qcw(y = 0) = 0.4165 cosh(3.162x(0/30)/cosh(3.162x5/30) = 0.36

Impulsive pressure at the base of wall

pcw(y = 0) = 0.36x0.12x 1029.56 x 9.81 x30 = 13.26 kN/m2

At y=h

Qcw(y = h) 0.4165

pcw(y = h) = 0.42x0.013x 1029.56x 9.81 x30 = 1.64 kN/m2

Convective hydrodynamic pressure on the base slab is

pcb = Qcb(x) (Ah)c ρ g L


cl. 4.9.2(b),
GSDMA
Qcb(x) = 1.25[x/L-4/3(x/L)3]sech(3.162h/L)

for y=0 at x=L/2 = 15


L&T Construction
Water & Effluent Treatment IC
Sewage Network & Decentralized Sewage Treatment Plants DOCUMENT NO. DATE
PROJECT:
for Nellore Municipal Corporation LE160315-C-WW-SW-DC-3008 10-Jan-17
DESIGNED CHECKED SHEET
STRUCTURE: Design calculation for SBR at Drivers Colony
MCL SURE

Qcw(x) = 1.25[L/2L-4/3(L/2L)³] sech(3.162x5/30) = 0.36

Convective pressure on top of base slab(y=0)

pcb(y = 0) = 0.36x0.013x 1029.56 x 9.81 x30 = 1.41 kN/m2

2.8 Pressure due to wall Inertia


cl. 4.9.5,
pww = (Ah)i ρm g t =0.12x0.375x25 = 1.13 kN/m2
GSDMA

2.9 Pressure Due to Vertical Excitation

Hydrodynamic pressure on tank wall due to vertical ground acceleration


Cl. 4.10.1,
pv = (Av) [ρ g h(1-y/h)]
GSDMA

〖 (𝐴 〗 _𝑣)=  2/3  
𝑍/2  𝐼/𝑅  𝑆_𝑎/𝑔

where

(IS 1893(part I): Table 2: Zone IV) Z= 0.16

(Table 6) I= 1.5

RC tank is pinned/fixed at base, R = 2.5

from cl. 4.10.1, GSDMA T= 0.3 sec

Damping 5% for Medium soil 0.3 < 0.55 (Sa/g)i = 2.5

(Av) = =(2/3)x0.16x1.5x2.5/(2x2.5) = 0.080

At the base of wall (y=0) pv = 0.08x1029.56x9.81x5x(1-0/5) = 4.04 kN/m2

2.10 Maximum Hydrodynamic Pressure

Maximum hydrodynamic pressure p= (piw+pww)2 + pcw2 + pv2

At the base of wall p = (5.25+1.13)²+1.64²+4.04² = 15.26 kN/m2

Maximum hydrodynamic pressure is about 30% of hydrostatic pressure

(ρ x g x h=x9.81x5=50.5kN/m²). Hence, hydrodynamic pressure

will marginally influence container design


L&T Construction
Water & Effluent Treatment IC
Sewage Network & Decentralized Sewage Treatment Plants DOCUMENT NO. DATE
PROJECT:
for Nellore Municipal Corporation LE160315-C-WW-SW-DC-3008 10-Jan-17
DESIGNED CHECKED SHEET
STRUCTURE: Design calculation for SBR at Drivers Colony
MCL SURE

2.11 Equivalent Linear Pressure Distribution

For stress analysis of tank wall, it is conveninet to have linear pressure

distribution along wall height. As per Section 4.9.4(GSDMA), equivalent

linear distribution for impulsive hydrodynamic pressure distribution

will be as follows:

Base shear due to impulsive liquid mass per unit circumferential length,

�_𝑖=  ( 〖 (𝐴_ℎ )_𝑖  = 0.12x664067.28x 9.81/(2x21.5) = 18.18 kN/m


𝑚 〗 _𝑖 𝑔)/2𝐵

𝑎_𝑖=  �_𝑖/ℎ^2  
(4ℎ−6ℎ_𝑖 ) = 18.18x(4x5-6x1.875)/(5^2) = 6.36 kN/m2

�_𝑖=  �_𝑖/ℎ^2  
(6ℎ_𝑖−2ℎ)
= 18.18x(6x1.875-2x5)/(5^2) = 0.91 kN/m2

0.91

0.65 6.36

Similarly , Equivalent linear distribution for convective pressure can be obtained as follows:

Base shear due to convective liquid mass per unit circumferential length, q c

�_𝑐=  ( 〖 (𝐴_ℎ )_𝑐 𝑚 〗 = 0.01x2523455.66x 9.81/(2x21.5) = 7.46 kN/m2


_𝑐 𝑔)/2𝐵

𝑎_𝑐=  �_𝑐/ℎ^2  
(4ℎ−6ℎ_𝑐 ) = 7.46x(4x5-6x2.56)/(5²) = 1.38 kN/m2

�_𝑐=  �_𝑐/ℎ^2  
(6ℎ_𝑐−2ℎ)
= 7.46x(6x2.56-2x5)/(5²) = 1.60 kN/m2

7.46 1.60
L&T Construction
Water & Effluent Treatment IC
Sewage Network & Decentralized Sewage Treatment Plants DOCUMENT NO. DATE
PROJECT:
for Nellore Municipal Corporation LE160315-C-WW-SW-DC-3008 10-Jan-17
DESIGNED CHECKED SHEET
STRUCTURE: Design calculation for SBR at Drivers Colony
MCL SURE

1.64 1.38

2.12 Sloshing Wave height

Maximum wave height,

dmax = (Ah)c R L /2 =0.013 x 2.5 x 30/2= 0.486 m


Cl. 4.11
Hence ,Sloshing height is below Free board height of 0.5m
GSDMA

2.13 Anchorage Requirement

Here, h/ L = 5/30 = 0.166666667

1/(Ah)i = 1/0.12 = 8.33


Cl. 4.12
Since h/L < 8.33, No anchorage is required
GSDMA

Hydrodynamic pressure 15.26 kN/m2

Pr at base of wall =15.26+50.5 = 65.76 kN/m2

equivalent pr for full wall height =0.5xpx5.5²/3 = 0.5x65.76x5²/3 = 274 kN/m2

Hydrodynamic Pressure p= 54.35 kN/m2

Hydrostatic pressure = 10.1x5.5 = 55.55 kN/m2

Design for Hydrostatic pressure


L&T Construction
Water & Effluent Treatment IC
Sewage Network & Decentralized Sewage Treatment Plants DOCUMENT NO. DATE
PROJECT:
for Nellore Municipal Corporation LE160315-C-WW-SW-DC-3008 10-Jan-17

Sewage Network & Decentralized Sewage Treatment Plants DESIGNED CHECKED SHEET
STRUCTURE:
for Nellore Municipal Corporation MCL SURE

For Rectangular Tank,

2 Analysis along X-Direction

Length L= 21.5 m

Breadth B= 30 m

Height of water h= 5m

Unit weight of sewage = 10.1 kN/m3

Mass density of water = ρ= 1029.56 kg/cum.

2.1 Parameters of Spring Mass Model

For h/L = = 5/21.5 = 0.23


table C1,Pg-16,
mi/m = tanh(0.866(L/h))/(0.866(L/h) = 0.27
GSDMA

mi = .27x3320336.4 = 896490.8257 kg
table C1,Pg-16,
mc/m = 0.264tanh(3.16(h/L))/(0.866(L/h)) = 0.71
GSDMA

mc =0.71x3320336.4 = 2357438.838 kg

hi/h = 0.375 hi = 1.875 m

hc/h = 0.521 hc = 2.605 m


table C1,Pg-
16, GSDMA
hi*/h = 1.76 hi* = 8.8 m

hc*/h = 2.274 hc* = 11.37 m

2.2 Time Period


Cl. 4.3.1.2
Time Period of Impulsive mode Ti = 2π d/g
GSDMA

ℎ  
d = deflection of tank wall on the vertical center-line at a height

q = Uniformly distributed pressure


Cl. 4.3.1.2 ℎ  =  (𝑚_𝑖/2 ℎ_𝑖+𝑚  _𝑤  
where,
GSDMA ℎ/2)/(𝑚_𝑖/2+𝑚  _𝑤 )
̄̄̄

𝑚  _𝑤 = mass of one tank wall perpendiculat to direction of loading

=30xtx25x1000/9.81 = 113006.5 kg

ℎ   = 2m
q=  (𝑚_𝑖/2+𝑚  _𝑤 )𝑔/𝐵ℎ
L&T Construction
Water & Effluent Treatment IC
Sewage Network & Decentralized Sewage Treatment Plants DOCUMENT NO. DATE
PROJECT:
for Nellore Municipal Corporation LE160315-C-WW-SW-DC-3008 10-Jan-17

Sewage Network & Decentralized Sewage Treatment Plants DESIGNED CHECKED SHEET
STRUCTURE:
for Nellore Municipal Corporation MCL SURE
q=  (𝑚_𝑖/2+𝑚  _𝑤 )𝑔/𝐵ℎ q= 36.71 kN/m2

Deflection per unit width of strip: considered as cantilever and subjected to

concentrated force P= qxhx1 = 183.55 kN

with the length of cantilever = ℎ  

�=  (𝑃ℎ  ^3)/(3𝐸𝐼_𝑤 )

Iw = Moment of Inertia of Cantilever = 1.0x0.375x0.375x0.375/12 = 4.40E-03 m4

Hence, d = 183.55x2³/(3x27386127.88x0.0044) = 4.06E-03 m4

Time Period Ti = 0.128 sec

Time Period of Convective mode Tc = Cc L/g

for h/L = 0.23 From C4.3.2.2 GSDMA Cc = 4.48

Time Period Tc = 6.63 sec

2.3 Design of Horizontal Seismic Coefficient

a Design of Horizontal Seismic Coefficient for impulsive mode

(𝐴_ℎ )_𝑖=  𝑍/2  𝐼/𝑅  Medium soil


(𝑆_𝑎/𝑔)_𝑖

where

(IS 1893(part I): Table 2: Zone III) Z= 0.16

(Table 6) I= 1.5

IS 1893(part II): Table 2 RC tank is pinned/fixed at base, R = 2.5

for impulsive mode damping = 5 % 0.05

Damping 5% for Medium soil 0.128 < 0.55 (Sa/g)i = 2.5

(Ah)i = 0.16x1.5x2.5/(2x2.5) = 0.1200

b Design of Horizontal Seismic Coefficient for Convective mode


L&T Construction
Water & Effluent Treatment IC
Sewage Network & Decentralized Sewage Treatment Plants DOCUMENT NO. DATE
PROJECT:
for Nellore Municipal Corporation LE160315-C-WW-SW-DC-3008 10-Jan-17

Sewage Network & Decentralized Sewage Treatment Plants DESIGNED CHECKED SHEET
STRUCTURE:
for Nellore Municipal Corporation MCL SURE

(𝐴_ℎ )_𝑐=  𝑍/2  𝐼/𝑅 
(𝑆_𝑎/𝑔)_𝑐

where

(IS 1893(part I): Table 2: Zone III) Z= 0.16

(Table 6) I= 1.5

RC tank is pinned/fixed at base, R = 2.5

for impulsive mode damping = 0.5 % 0.005

Damping 0.5% for Medium soil 6.632 > 0.55 (Sa/g)c = 0.205
cl 4.5.2, IS
muiltiplying factor 1.75 (Sa/g)c = 0.359
1893 part -2

(Ah)c = 0.16x1.5x0.36/(2x2.5) = 0.017

2.4 Base Shear

Base Shear at the bottom of wall in impulsive mode


cl. 4.6.1,
Vi =(Ah)i (mi+mw+mt) g = 0.12x(896490.83+541380+0)x9.81/1000 = 1692.66 kN
GSDMA

Similarly, Base shear in convective mode


cl. 4.6.1,
Vc =(Ah)c mc g = 0.017x2357438.84x9.81/1000 = 398.37 kN
GSDMA

cl. 4.6.3,
GSDMA
Total base shear at the bottom of wall

V = Vi2+Vc2 = 1692.66²+398.37² = 1738.91 kN

This lateral base shear is about 4% of total seismic weight (41304.4kN ) of tank

2.5 Moment at Bottom of Wall

Bending Moment at the Bottom of wall in impulsive mode,


cl. 4.7.1.1,
Mi =(Ah)i (mihi+mwhw+mtht) g = 0.12x(896490.83x1.875+3420.94x5.5/2+0)x9.81/1000 = 3731.39 kNm
GSDMA

Bending Moment at the Bottom of wall in convective mode,


cl. 4.7.1.1,
Mc =(Ah)c mchc g = 0.02x2357438.84x2.605x9.81/1000 = 1037.75 kNm
GSDMA

Total Bending Moment at the bottom of wall

M = Mi2+Mc2 = 3731.39²+1037.75² = 3873.01 kNm


L&T Construction
Water & Effluent Treatment IC
Sewage Network & Decentralized Sewage Treatment Plants DOCUMENT NO. DATE
PROJECT:
for Nellore Municipal Corporation LE160315-C-WW-SW-DC-3008 10-Jan-17

Sewage Network & Decentralized Sewage Treatment Plants DESIGNED CHECKED SHEET
STRUCTURE:
for Nellore Municipal Corporation MCL SURE

2.6 Overturning Moment

Overturning Moment at the Bottom of Base slab in impulsive mode,


cl. 4.7.1.2,
Mi* = (Ah)i [mi(hi*+tb) + mw(hw+tb) + mt(ht+tb) + mbtb/2] g
GSDMA

= 0.12[896490.83x(8.8+0.2) + 541380x(2.75+0.2)+ 0 +348719.4x0.1]x9.81 = 11419.26 kNm

Similarly, overturning Moment in convective mode,


cl. 4.7.1.2,
Mc* = (Ah)c mc(hc*+tb)
GSDMA

= 0.02 x 2357438.84x(11.37+0.2)x9.81 = 4609.10 kNm


cl. 4.7.1.3,
GSDMA
Total overturning Moment at the bottom of base slab

M* = Mi*2+Mc*2 = 11419.26²+4609.1² = 12314.36 kNm

Stabilizing Moment

(Mass of water + Mass of wall + mass of raft) x ( L/2+tw + raft projn)

(541380+348719.4+3320336.39)x(10.95)x9.81= 452282.91 kNm

Check for over turning

Restoring moment / Overturning moment =452282.91/12314.36 = 36.73

Hence 36.73>1.4 Safe

2.7 Hydrodynamic Pressure

2.7.1 Impulsive Hydrodynamic Pressure

Impulsive hydrodynamic pressure on wall is

piw = Qiw(y) (Ah)i ρ g h


cl. 4.9.1(b),
GSDMA
Qiw(y) = 0.866 [ 1- (y/h)2] tanh(0.866 L/ h)

At base of wall, y=0

Qiw(y = 0) = 0.866 [1-(0/5)²]xtanh(0.866x21.5/5) = 0.86

Impulsive pressure at the base of wall

piw(y = 0) = 0.86x0.12x 1029.56 x 9.81 x5 = 5.24 kN/m2


L&T Construction
Water & Effluent Treatment IC
Sewage Network & Decentralized Sewage Treatment Plants DOCUMENT NO. DATE
PROJECT:
for Nellore Municipal Corporation LE160315-C-WW-SW-DC-3008 10-Jan-17

Sewage Network & Decentralized Sewage Treatment Plants DESIGNED CHECKED SHEET
STRUCTURE:
for Nellore Municipal Corporation MCL SURE

Impulsive hydrodynamic pressure on the base slab (y=0) is

pib = Qib(x) (Ah)i ρ g h


cl. 4.9.1(b),
GSDMA
Qib(x) = sinh(0.866(x/h))/cosh(0.866 L/ h) x = L/2 = 10.75

Qib(x) = sinh(0.866x10.75/5)/cosh(0.866x21.5/5) = 1.00

Impulsive pressure on top of base slab(y=0)

pib(y = 0) = 1x0.02x 1029.56 x 9.81 x5 = 0.87 kN/m2

2.7.2 Convective Hydrodynamic Pressure

Convective hydrodynamic pressure on wall is

pcw = Qcw(y) (Ah)c ρ g L


cl. 4.9.2(b),
GSDMA
Qcw(y) = 0.4165 cosh(3.162y/L)/cosh(3.162 h/ L)

At base of wall, y=0

Qcw(y = 0) = 0.4165 cosh(3.162x(0/21.5)/cosh(3.162x5/21.5) = 0.32

Impulsive pressure at the base of wall

pcw(y = 0) = 0.32x0.12x 1029.56 x 9.81 x21.5 = 8.46 kN/m2

At y=h

Qcw(y = h) 0.4165

pcw(y = h) = 0.42x0.0172x 1029.56x 9.81 x21.5 = 1.56 kN/m2

Convective hydrodynamic pressure on the base slab is

pcb = Qcb(x) (Ah)c ρ g L


cl. 4.9.2(b),
GSDMA
Qcb(x) = 1.25[x/L-4/3(x/L)3]sech(3.162h/L)

for y=0 at x=L/2 = 10.75

Qcw(x) = 1.25[L/2L-4/3(L/2L)³] sech(3.162x5/21.5) = 0.32

Convective pressure on top of base slab(y=0)

pcb(y = 0) = 0.32x0.017x 1029.56 x 9.81 x21.5 = 1.20 kN/m2

2.8 Pressure due to wall Inertia


cl. 4.9.5,
pww = (Ah)i ρm g t =0.12x0.375x25 = 1.13 kN/m2
GSDMA
L&T Construction
Water & Effluent Treatment IC
Sewage Network & Decentralized Sewage Treatment Plants DOCUMENT NO. DATE
PROJECT:
for Nellore Municipal Corporation LE160315-C-WW-SW-DC-3008 10-Jan-17

Sewage Network & Decentralized Sewage Treatment Plants DESIGNED CHECKED SHEET
STRUCTURE:
for Nellore Municipal Corporation MCL SURE

2.9 Pressure Due to Vertical Excitation

Hydrodynamic pressure on tank wall due to vertical ground acceleration


Cl. 4.10.1,
pv = (Av) [ρ g h(1-y/h)]
GSDMA

〖 (𝐴 〗 _𝑣)=  2/3  
𝑍/2  𝐼/𝑅  𝑆_𝑎/𝑔

where

(IS 1893(part I): Table 2: Zone IV) Z= 0.16

(Table 6) I= 1.5

RC tank is pinned/fixed at base, R = 2.5

from cl. 4.10.1, GSDMA T= 0.3 sec

Damping 5% for Medium soil 0.3 < 0.55 (Sa/g)i = 2.5

(Av) = =(2/3)x0.16x1.5x2.5/(2x2.5) = 0.080

At the base of wall (y=0) pv = 0.08x1029.56x9.81x5x(1-0/5) = 4.04 kN/m2

2.10 Maximum Hydrodynamic Pressure

Maximum hydrodynamic pressure p= (piw+pww)2 + pcw2 + pv2

At the base of wall p = (5.24+1.13)²+1.56²+4.04² = 11.33 kN/m2

Maximum hydrodynamic pressure is about 22% of hydrostatic pressure

(ρ x g x h=x9.81x5=50.5kN/m²). Hence, hydrodynamic pressure

will marginally influence container design

2.11 Equivalent Linear Pressure Distribution

For stress analysis of tank wall, it is conveninet to have linear pressure

distribution along wall height. As per Section 4.9.4(GSDMA), equivalent

linear distribution for impulsive hydrodynamic pressure distribution

will be as follows:

Base shear due to impulsive liquid mass per unit circumferential length,

�_𝑖=  ( 〖 (𝐴_ℎ )_𝑖 
L&T Construction
Water & Effluent Treatment IC
Sewage Network & Decentralized Sewage Treatment Plants DOCUMENT NO. DATE
PROJECT:
for Nellore Municipal Corporation LE160315-C-WW-SW-DC-3008 10-Jan-17

Sewage Network & Decentralized Sewage Treatment Plants DESIGNED CHECKED SHEET
STRUCTURE:
for Nellore Municipal Corporation MCL SURE

�_𝑖=  ( 〖 (𝐴_ℎ )_𝑖  = 0.12x896490.83x 9.81/(2x30) = 17.59 kN/m


𝑚 〗 _𝑖 𝑔)/2𝐵

𝑎_𝑖=  �_𝑖/ℎ^2  
(4ℎ−6ℎ_𝑖 ) = 17.59x(4x5-6x1.875)/(5^2) = 6.16 kN/m2

�_𝑖=  �_𝑖/ℎ^2  
(6ℎ_𝑖−2ℎ) = 17.59x(6x1.875-2x5)/(5^2) = 0.88 kN/m2

0.88

0.87 6.16

Similarly , Equivalent linear distribution for convective pressure can be obtained as follows:

Base shear due to convective liquid mass per unit circumferential length, q c

�_𝑐=  ( 〖 (𝐴_ℎ )_𝑐 𝑚 〗 = 0.02x2357438.84x 9.81/(2x30) = 6.64 kN/m2


_𝑐 𝑔)/2𝐵

𝑎_𝑐=  �_𝑐/ℎ^2  
(4ℎ−6ℎ_𝑐 ) = 6.64x(4x5-6x2.605)/(5²) = 1.16 kN/m2

�_𝑐=  �_𝑐/ℎ^2  
(6ℎ_𝑐−2ℎ)
= 6.64x(6x2.605-2x5)/(5²) = 1.50 kN/m2

6.64 1.50

1.56 1.16
L&T Construction
Water & Effluent Treatment IC
Sewage Network & Decentralized Sewage Treatment Plants DOCUMENT NO. DATE
PROJECT:
for Nellore Municipal Corporation LE160315-C-WW-SW-DC-3008 10-Jan-17

Sewage Network & Decentralized Sewage Treatment Plants DESIGNED CHECKED SHEET
STRUCTURE:
for Nellore Municipal Corporation MCL SURE

2.12 Sloshing Wave height

Maximum wave height,

dmax = (Ah)c R L /2 =0.017 x 2.5 x 21.5/2= 0.463 m


Cl. 4.11
Hence ,Sloshing height is below Free board height of 0.5m
GSDMA

2.13 Anchorage Requirement

Here, h/ L = 5/21.5 = 0.2325581395

1/(Ah)i = 1/0.12 = 8.33


Cl. 4.12
Since h/L < 8.33, No anchorage is required
GSDMA

Hydrodynamic pressure 11.33 kN/m2

Pr at base of wall =11.33+50.5 = 61.83 kN/m2

equivalent pr for full wall height =0.5xpx5.5²/3 = 0.5x61.83x5²/3 = 257.63 kN/m2

Hydrodynamic Pressure p= 51.10 kN/m2

Hydrostatic pressure = 10.1x5.5 = 55.55 kN/m2

Design for Hydrostatic pressure