Type Selection
Mounting Output Supply: Supply: Supply: Supply:
208 to 240 VAC 380 to 415 VAC 440 to 480 VAC 600 to 690 VAC
DIN-rail 2 x SPDT DPC 02 D M23 DPC 02 D M48 DPC 02 D M49 DPC 02 D M69
Input Specifications
Input Ranges
L1, L2, L3, N DPC02: Terminals L1, L2, L3, N Upper voltage level +2 to +22%
Measures its own supply of the nominal voltage
Note: Connect the neutral only Lower voltage level -22 to -2%
if it is intrinsically at the star of the nominal voltage
centre Frequency window 10 to 110%
of the selected range
Measuring ranges (voltage)
M23 177 to 275 ∆VAC Hysteresis (frequency)
M48 323 to 475 ∆VAC 2 Hz range ~ 0.05 Hz
M49 374 to 552 ∆VAC 15 Hz range ~ 0.25 Hz
M69 510 to 793 ∆VAC
Note: The input voltage
Measuring ranges (frequency) Upper level Lower level must not exceed the maxi-
Selectable by DIP-switches mum rated voltage or drop
2 Hz range +0.2 to +2.2 Hz -2.2 to -0.2 Hz below the minumum rated
50 Hz 50.2 to 52.2 Hz 47.8 to 49.8 Hz voltage reported above.
60 Hz 60.2 to 62.2 Hz 57.8 to 59.8 Hz
15 Hz range +1.5 to +16.5 Hz -16.5 to -1.5 Hz
50 Hz 51.5 to 66.5 Hz 33.5 to 48.5 Hz
60 Hz 61.5 to 76.5 Hz 43.5 to 58.5 Hz
Mode of Operation
Connected to the 3 phases releases after the set time Example 1 Example 2
(and neutral) DPC02 operates period. If the mains frequen- (Generator monitoring - (Mains monitoring - DPDT
when all 3 phases are present cy gets out of the symmetri- 2xSPDT relays - phase- relay)
at the same time and the cal window across the nomi- phase voltage) DPC02 monitors phase loss
phase sequence is correct. nal frequency the red LED The relay monitors phase and correct phase
starts flashing 2 Hz and the loss and correct phase sequence, over and under
Voltage and frequency respective output relay sequence, over and under voltage and the frequency.
level monitoring: releases after the set time voltage and the frequency of Every failure is detected
if one or more phase-phase period. the system. A voltage failure through relays 1 and 2 at the
or phase-neutral voltage is detected through relay 1 same time to allow indepen-
exceed the upper set level or and a frequency failure is dent operations.
drop below the lower set detected through relay 2.
level, the red LED starts
flashing 2 Hz and the
respective output relay
Function/Range/Level/Time Setting
Adjust the input range set- Lower knobs: Output
ting the DIP-switches 3 and Setting of delay on alarm ON: 2 x SPDT relays
4. Select the desired func- time on absolute scale: OFF: 1 x DPDT relay
tion setting the DIP-switches 0.1 to 30 s.
5 and 6 as shown on the left. Monitoring
To access the DIP-switches ON: Phase-Neutral voltages
open the plastic cover using OFF: Phase-Phase voltages
a screwdriver as shown
below. Measuring range
SW3 ON ON OFF OFF
Upper left knob:
Setting of upper voltage SW4 ON OFF ON OFF
level on relative scale. M23 Ph-Ph 208 VAC 220 VAC 230 VAC 240 VAC
Centre left knob: Voltage
Setting of lower voltage level M48 Ph-Ph 380 VAC 400 VAC 415VAC 415VAC
on relative scale. Voltage
Centre right knob: M48 Ph-N 220 VAC 230 VAC 240 VAC 240 VAC
Setting of frequency window Voltage
width on relative scale. M49 Ph-Ph 440 VAC 440 VAC 480 VAC 480 VAC
Voltage
M49 Ph-N 254 VAC 254 VAC 277 VAC 277 VAC
Voltage
M69 Ph-Ph 600 VAC 600 VAC 690 VAC 690 VAC
Voltage
M69 Ph-N 347 VAC 347 VAC 400 VAC 400 VAC
Dimensions Voltage
System frequency
45 99.5 ON: 60 Hz
OFF: 50 Hz
63
28.5
Operation Diagrams
Phase sequence, total phase loss
L1 or
L1-L2
Upper voltage
Hysteresis
L2 or
L2-L3
Hysteresis
Lower voltage
L3 or
L3-L1
Power ON T1 T1 T1
Relay 1 Voltage
Power ON
Red LED ON
Power ON T2 T2
Relay 2 Frequency
Power ON T1 T1 T1
Relays (DPDT NE)
Frequency (+)
Hysteresis
Nominal Frequency
Hysteresis
Frequency (-)
Wiring Diagrams
Ex.1 Ex.2