Вы находитесь на странице: 1из 12

Technical Sheet

and Installation Guide

Autoclaved Aerated Concrete


Properties

Characteristic Unit Strength Class


AAC-4 AAC-6
Compressive Strength (f’aac) psi 580 870
Nominal Density pcf 31 37
Design Weigth pcf 37 45
Drying Shrinkage % 0.02
Thermal Expansion Coefficient K-1 8 x 10-6
1 Technical Thermal Conductivity BTU-in/ft h F
ng/Pa.s.m
2 0
0.9124 0.9811
Water Vapor Permeability 0.223 0.226
Sheet Moisture Adsortion %
mass
vol.
2.90
1.47
2.87
1.73
Modulus of Elasticity psi 295,000 377,000
Modulus of Rupture (MOR) psi 115 142
1.1 Hebel Masonry
Allowable Bearnig Stress psi 348 523
Componets
Table 1: Physical and design properties.
General Features
Hebel Autoclaved Aerated
Concrete (AAC) Masonry
Components (Stardard Block,
O-Block and U-Block) are
lightweight, fire resistant, fast and Hebel Block Pallet
easy to install and provides
lifelong superior thermal Thickness* Standard Block O-Block U-Block
insulation. Hebel AAC Masonry in(in) pce ft2 3
ft pce 2
ft 3
ft pce ft ft3
Blocks are produced in two 4 (3.937) 180 236.3 77.5 - - - - - -
different ASTM C 1386 strength
classes: AAC-4 and AAC-6. 5 (4.921) 144 189.0 77.5 144 189.0 77.5 54 108.0 29.1

6 (5.906) 120 157.5 77.5 120 157.5 77.5 48 96.0 31.0


Dimensions
7 (6.890) 96 126.0 72.3 96 126.0 72.3 60 120.0 45.2
Block Standard O-Block U-Block
8 (7.874) 84 110.3 72.3 84 110.3 72.3 36 72.0 31.0
Length: [1] 24 in.
10 (9.843) 72 94.5 77.5 72 94.5 77.5 28 56.0 30.1
Height: [1][2] 8 (7-7/8) in.
12 (11.811) 60 78.8 77.5 60 78.8 77.5 24 48.0 31.0
Thickness: [1][3] 4 to 12 in 5, 6, 7, 8, 10 and 12 in.
*Nominal Thickness (Exact Thickness), Height = 8 (7.875)", Length = 24".
Strength Class: AAC-4 and AAC-6
Table 2: Hebel Block packaging.
[1]
Tolerance ± 1/8”, [2] (Exact dimension), [3] Nominal Thickness,
Product manufactured according to ASTM C1386-07.

Uses
Hebel Masonry Components are
used to build reinforced load-
Shipping
bearing and nonload-bearing
exterior and interior walls for
Capacity Dimensions Platform
residencial and multi-family Truck Trailer Platform (ft) Single
housing, hotels, hospitals, office
buildings, fire and shaft walls, lb (Ton) Length Width Pallet [2] ft3
commercial and industrial Hebel (Flat Bed) Trailer 33,100 (15) 21 8 10 723
buildings. Hebel AAC meets the
diverse demands better than any Platform (Flat Bed) Trailer [1] 44,100 (20) 40 8 14 1012
other material due to the [1] FOB Shippings (origin or destination), [2] e.g. Standard Block 8" (AAC-4).
numerous advantages of its
physical, mechanical and energy Table 3. Trailer load capacity.
efficiency properties.

2 Hebel Aerated Concrete


Hebel O-Block
Thickness Diam Ø d1 d2 d3 Cylinder Volume
(in) (in) (in) (in) (in) ft3/yd 24 in

5 2.76 2.46 1.08 20.18 0.1243 d3 d2

6 3.54 2.95 1.18 19.49 0.2054


d2
7 3.54 3.44 1.67 18.80 0.2054

Thickness
8 4.33 3.94 1.77 17.91 0.3069
d1
10 4.33 4.92 2.76 16.93 0.3069 O/

12 4.33 5.91 3.74 15.94 0.3069 Height= 8 in


Table 4: Hebel O-Block dimensions. d1

Hebel U-Block
Thickness a b c d Cylinder Volume
(in) (in) (in) (in) (in) ft3/yd
5 1.48 1.97 1.48 2.17 0.2341
6 1.48 2.95 1.48 2.17 0.3512
7 1.67 3.54 1.67 2.17 0.4214
8 1.67 4.53 1.67 2.17 0.5385 8 in

10 1.87 6.10 1.87 2.17 0.7258


24 in
12 2.36 7.09 2.36 2.17 0.8428
Table 5: Hebel U-Block dimensions. Thickness

Thermal Conductivity
Class
Thermal Conductivity
AAC-4 AAC-6 Fig. 2: Hebel O-Block for vertical reinforcement.
Steady-State
2 0 2 0
0.9124 BTU-in/ft -h- F 0.9811 BTU-in/ft -h- F
Unit: BTU = british thermal unit , in = inches, ft = pie, h = hour, °F = grados fahrenheit
a b c
Table 6: Hebel Block thermal conductivity.

Acoustic Performance
Assembly Type STC Report No. 8 in

Hebel 6” Wall AAC-4 Unfinished 44 AS-TL958AX


d
Hebel 8” Wall AAC-4 Unfinished 47 AS-TL959AX
Hebel 10” Wall AAC-4 Unfinished 50 AS-TL978AX
Thickness
Hebel Double 5” Wall AAC-6 (airspace 4”, no fill) Unfinished 60 AS-TL962AX
Note: Testing performed at Acoustic Systems, Inc. 415 East, Elmo Rd., Austin, TX in accordance
with ASTM E90 “Standard Method for Laboratory Measurement of Airbone Sound Transmission b
Loss of Building Partitions”. STC = Sound Transmission Class.
Table 7: Hebel Block acoustic performance.

Fire Performance
Fire Ratings UL Design
Wall Components Class AAC-4 and AAC-6 (Hours) Number
Non-load bearing Hebel Block Wall 4” min. (Solid) 4 U919 8 in

Load bearing Hebel Block Wall 6” min. (Solid) 4 U919 24 in


Load or non-load bearing Hebel Cored Block Wall 8” min. 4 U919
Thickness
Fire protection for existing column (4” Hebel Block) 4 X901
Note: Testing performed at Underwriters Laboratories, Inc., Northbrook, IL under ASTM E119
(UL/ANSI 263) “Fire Tests of Building Construction and Materials”.
Table 8: Hebel Block fire rating. Fig. 3: Hebel U-Block for horizontal reinforcement.

Hebel Aerated Concrete 3


3 Installation
Guide
Before installation
of Hebel AAC Masonry
Componetns

3.1 Check foundation


Foundation must be designed
according to Local Building Codes.

Reinforced masonry requires


rebars for pilasters -vertical
reinforcement- (see Fig. 6). Rebar
spacing must be according to Local
Building Codes, IBC and ACI
Codes. At opening locations (doors,
Fig. 4: Hebel Block pallets. windows, etc), vertical rebars for
pilaster must be placed on both
2 Design sides (or less than 2 ft) of window
and door openings (see Fig. 20).

Considerations Before concrete is poured, check


slab dimensions and
2.1 General reinforcement to comply with
construction drawings. Ensure the
Considerations pipes, drains and other
penetrations through the slab have
• Hebel Masonry Components been installed properly. A brick
(block units) can be used to build Fig. 5: Forklift and flatbed trailer.
ledge is recommended for the
load-bearing or nonload-bearing exterior walls (see Fig. 8).
walls. Masonry walls built of Hebel • Control joints on Hebel Masonry
AAC Masonry Components must AAC reinforced walls must be Hebel Masonry Components
be designed following guidelines placed at maximum 16 ft o.c. (see installation will be easier on a level
established by IBC Section 2101.2, Fig. 6 and 20). slab.
and Chapter 1 and Appenix A of
The Building Code Requirements
for Masonry Structures (ACI 530/
ASCE 5 /TMS 402).

• Hebel O-Block units (Cored


Blocks) can be used to build
pilasters designed according to
Local Building Codes.

• Hebel U-Block units can be used


to build bond beams and lintels
(to span door and window
openings).

• Special considerations for


construction located on seismic
areas must be followed in
accordance with Section 2106 of
the IBC Code. Fig. 6: Check foundation (pipes, drains, reinforcement, etc).

4 Hebel Aerated Concrete


Hebel block wall Vertical reinforcement
(According to
structural design)
3.2 Receiving and - Masonry Scrub Brush. Mortar (Cement-sand)
- Sanding Float. for leveling bed
Distribution of Hebel - Hebel Plastic Bucket.
(minimum 1/2”)
Thin bed mortar joint
Wall Units - Spatula. Water proofing barrier
- Chalk-Line. 1 1/2”
Carefully unload the Hebel pallets - Nylon Construction Line.
Foundation
using an all terrain forklift. - Wooden Line Blocks. (According to
structural design)
Rubbing between pallets can - Tape Measure.
cause damage to some pieces.
Place pallets around the slab Equipment:
(above ground level) and close to - ½” Power Drill.
work area (see Fig. 4 and 5). - Stirrer for Power Drill.
- Hebel Hand Saw.
- Hebel Square.
- Hebel Electric Band Saw
3.3 Installation (optional).
Vertical reinforcement
- Hebel Chasing Tools. Hebel block wall
Requirements - 4½” Angle Grinder.
(According to
structural design)
Mortar (Cement-sand)
- Safety Equipment (Hard hat, for leveling bed
The actual list of tools, equipment (minimum 1/2”)
face-shield, goggles, dust mask,
and other materials will depend Thin bed mortar joint
ear plugs, gloves, safety shoes,
on type of proyect and workforce. Water proofing barrier
etc). 1 1/2”

Tools:
Other materials: Optional: To anchor
- Hebel Notched Trowel. rebar, drill a hole into
- Hebel Metal Strip Connectors. slab 41/2” long x (rebar
- Rubber Mallet (24 oz min). diam +1/4”), fill up the
- Fiberglass Mesh. hole with epoxy and
- Brick Trowel. insert the rebar.
- Backer-rod & Caulking.
- Masonry Level.

Fig. 8: Anchoring vertical reinforcement to foundation.

- Cement-Sand Mortar.
- Hebel Thin Bed Mortar.
- Hebel Repair Mortar.
- Hebel Stucco.
- Hebel Rustic Finish.
- Base-Coats, Textures, etc.
- Anchors & Hebel Nails.

3.4 Mixing Hebel Thin


Bed Mortar
Hebel Thin Bed Mortar is prepared
in a plastic bucket, adding clean
Fig. 7: Tools and equipment. water (for half bag of mortar add
approximately 1.1 gallons of water)
and mix with a stirrer using a
power drill. Remix before
application.

The consistency should allow


mortar to flow easily through a
notched trowel, leaving the shape
of the teeth in the mortar bed (see
Fig. 15). Mortar workability time is
Fig. 9 4 hours.

Hebel Aerated Concrete 5


Check around the reference wall Bed Mortar to the vertical joints
lines marked on the slab to locate using an appropriate Hebel
the highest point. At this point, add notched trowel -the trowel should
½” (of cement-sand mortar bed) to be as wide as the block-(see Fig.10
7 7/8” (of Hebel Block Height) to to 12). Thin bed mortar joints
obtain the “top of leveling course”. should be 1/16” thick, but no more
than 1/8”.
It is recommended to set the string
line level from the “top of leveling After installing each unit, plumb
course point” to assure level of first and level should be checked
course. The string should be immediately using the mason’s
Fig. 10 stretched, hooking the line blocks level. Any correction must be done
properly. At the same time, the line within 5 minutes by tapping lightly
should be checked using a line with a rubber mallet (see Fig. 13).
3.5 Installing Hebel level.
O-Block for pilasters in
first course. b. Laying the first course (leveling
course)
A simple way to build pilasters is
by using Hebel O-Block units. They Using a brush, clean block surface
should fit over a rebar that is before installation. Lay the first
sticking up from the foundation, course over a semi-dry cement-
according to constrution drawings. sand mortar leveling bed
Optionally, if rebar is not (minimum thickness ½”, max
embedded or misplaced, drill a thickness 2”)-see Fig. 10-.
Fig. 14
hole into the slab, fill up the hole
with epoxy adhesive and insert the Corner blocks are laid first and the
rebar (see Fig. 8). first course should be completed
before second course installation. c. Cutting blocks (adjustments and
Once the corner blocks are placed, chases).
3.6 Hebel Masonry use a brush to clean next block
Components surface before mortar application. A Habel hand saw or a band saw
Installation For next blocks, apply Hebel Thin can be used to cut the block to
specific lengths (adjustment
a. Mark and level the slab pieces) –see Fig. 17.

Once the foundation is ready, it If required, cut a chase for utilities


will be necessary to mark (using not exceeding the maximum depth
a chalk line) the position of the of chases (see Section 3.7 – Utilities
walls, including door openings, in Installations).
accordance with construction
drawings. It is recommended to d. Placing control joints in first
apply a water proofing barrier on course.
the slab anywhere Hebel Block
Components will be installed (see Fig. 12 The location of control joints should
Fig. 8). be specified in construction
drawings.

Thin bed mortar joints


(1/16” to 1/8” thick)
Hebel joints are vertical joints
Fill with
Vertical concrete taken through the full wall
reinforcement thickness and from bottom (first
course) to top. The width of the
control joints should be 3/8” thick
but no more than ½” thick. The
maximum spacing between Hebel
joints should be 15 ft (see Fig. 14
and 20).
Hebel Block Hebel std. Block

Fig. 11: Pilaster located at corner. Fig. 13

6 Hebel Aerated Concrete


h. Fill up pilasters

Procede to pour concrete


(f’c= 3,000 psi min) into pilasters
(cylinders) to complete wall
Fig. 15 installation (see Fig. 18).

e. Laying the subsequent courses.


Fig. 16
For subsequent courses, use only
Hebel Thin Bed Mortar on all joints
between Hebel Blocks (see Fig. Caution: Use safety gear: Hard hat, dust mask and
15). Use a brush to clean the block goggles to avoid excessive inhalation of dust and
surface before mortar application. protection of the eyes when handling Hebel Masonry
After block installation, remove Components.
spilled mortar using a spatula.
Minimum overlapping of vertical
joints between layers should be 4
inches (see Fig. 20). i. Building on-site lintels
using U-Blocks
It is recommended to check
alignment and level after each unit When the use of Hebel Lintels is
installation to achieve a plumed not possible, and depending on the
wall. span and service load, lintels over
door and windows openings can
Hebel metal strip ties should be be made on site using Hebel
placed every two courses at: U-Block.

- Connection of secondary walls Install temporary bearer and prop


to main walls. supports before putting U-Block
- Connection of walls to concrete in place. Apply Hebel Thin Bed
columns. Mortar to the vertical joints (see
Fig. 16).
f. Installing Hebel O-Block in Fig. 17
subsequent layers for pilasters Once the U-Blocks are set, place
rebars according to construction
It’s very important to check that drawings and with concrete (see
O-Block holes between courses Fig. 19 and 20).
are properly aligned when
installing. j. Installing U-Blocks to
build bond beams
Make certain that all rebars
attaches to bars sticking up from Generally, bond beams are
the foundation comply with required through the top of the
reinforcement specifications. exterior and interior walls.
Fig. 18
g. Control joints Lay U-Block course, applying
in subsequent layers Hebel Thin Bed Mortar on all joints Bond beam reinforcement
(vertical and horizontal joints). At (According to structural
design)
Metal strips folded at midpoint each pilaster location, drill a hole
(V-shaped) should be set at every in the bottom side of the U-Block
2 courses unless there are two so the vertical bars can be Fill with

pilasters (vertical reinforcement) attached into the bond beam, to concrete


f’c= 3ksi
Hebel
O-Block
on both sides of control joints (one comply with the reinforcement
pilaster each side) and less than requirements.
10” from control joint (see Fig. 20).
Once the wall is built, fill the gap Before pouring concrete, place Vertical reinforcement

using backer-rod and seal with rebars and anchor bolts according (According to
structural design)

caulking. to construction drawings (see Fig.


19 to 23). Fig. 19: Bond beam and pilaster connection.

Hebel Aerated Concrete 7


Hebel
Vertical Reinforcement (O-Block) Continuous Slab Panel
(1Rebar + Concrete f'c= 3 KSi) to second floor
Smooth Bar 5/8” Diam.
(oiled one end)
Control Joint width:
3/8” to ½” (10-12 mm)

AAC Adhesive Mortar on


vertical and horizontal joints.
(all block thickness) Bond Beam Continuous
Reinforced U-Block

Overlap Rebar Vertical reinforcement on both


(40Ø Min)
sides (<
-2 ft.) of windows

Variable
and doors opening
(except windows < -16 in width)

Bond Beam
Reinforced U-Block 16 in (min)

Standard Block

Variable
O-Block

4 in (min)

Fill and seal with


Wall Max. distance between y y y <-10 inches backer rod and caulking
Extreme vertical reinforcement Waterproof barrier
according to design

Fig. 20: Reinforced Masonry details and specifacations.

2x4 Top plate

Anchor Bolts @ 3’
or according to
Fig. 21: Construction interior view. design requirements

Hebel U-Block
used as bond
beam

Reinforcement
according to
structural design
Roof Trusses

Hebel Block Wall

Fig. 22: Three-story hotel construction. Fig. 23: Anchoring wood top plate to U-Block top bond beam.

8 Hebel Aerated Concrete


Fill with
concrete

6”

Section A-A
Fig. 24: Hebel chasing tools.

3.7 Utilities installation Hebel Masonry

after the walls are built Hebel Wall


Interruption
For electrical conduits and piping After installation, use Hebel rapair
installation, cut a chase using an mortar or cement-sand mortar to
electrical router or a chasing tool. fill the chases (see surface Variable
To lodge electrical boxes, a power patching). During finishing step,
drill (drill bits) or router can be place fiber glass mesh over the 6” #2 Bar
staple
used (see Fig. 24 and 25). repair area according to
recommendations (see Section 4 Two #2 bar staple
Sanitary and
every two courses
When the required depth of chase and Fig. 29). pluvial pipes
(<-4Ø )
is bigger then maximum depth
recommended, use additional
Hebel O-Blocks to lodge the pipes
or interrupt wall continuity (see
Fig. 26).
Hebel Block

Fill with
concrete
Nota: Nail staples into Hebel Block.

Fig. 26: PVC drainage pipe detail.

Fig. 25: Water supply pipes.

Fig. 27: Electrical conduits in Hebel wall.

Hebel Aerated Concrete 9


4 Renders and
Finishes
4.1 Products
Surface Patching
Rasp block joints and other areas
where the AAC surface is out of
plane. Surface must be clean, free
of dirt, oil and any other matter.
Loose or damaged material must
be removed.
Use Hebel Thin Bed Mortar, Repair
Mortar or Cement-Sand Mortar to Fig. 28: Four-story hotel built using Hebel Masonry Components.
patch chips, breaks, chases for
utilities and other imperfections Finishes instructions. Reinforce base-coat
on the wall surface. Products are Hebel Masonry Walls can be using Fiber Glass Mesh embedded
applied using a spatula or trowel. finished with Hebel Stucco, acrylic partially (see Fig. 29) or in 100% of
Before application, clean surface texture coats, or a combination of the surface area according to
using a scrub brush. After stucco as a base-coat and acrylic base-coat manufacturer.
application, a rubber float is texture as a finish coat, also
commonly used to smooth the wall laminated stones, ceramic or clay Finish Coat
surface. tiles, concrete pieces and Apply ready-mix acrylic based
ornamentals products. products as decorative and
Fiber Glass Mesh protective finish coat (top-coat).
Hebel Fiber glass mesh should be Base-Coat Apply finish directly over the
installed directly over one layer of Apply a layer (¼” thickness primed wall surface. Apply product
render (embedded into first coat minimum) of stucco (cement-based by troweling with a stainless steel
of plaster, e.g Stucco) in all control or acrylic) or acrylic base-coats finishing trowel, depending on the
joints, around windows, doors, and (Hebel, STO AAC produts or similar), finish specified (see Fig. 28).
through utility locations (see Fig. 29). according to manufacturer

AAC Adhesive mortar


over U-Block bond beam
Fiberglass Mesh
5½” strip

Slab ring beam

U-Block
Bond Bearn

20” x 12” 20” x 12”


10”
Windows
and doors
opening

5½” Reinforced
U-Block
switches
1/3 central
5½” 10”
x12”width

20” x 12” 20” x 12”

5½” 5½” Variable

Concrete columns Electrical Hydro-Sanitary Sanitary and Control


instalations instalations pluvial pipes <-4Ø joint
Notes:
- Finish coat should have a minimum thickness of one-quarter inch.
- Place fiberglass mesh on both sides of wall (interior and exterior).
- Install fiberglass mesh embeded into finish thickness or a layer of AAC adhesive mortar.

Fig. 29: Fiberglass mesh installation.

10 Hebel Aerated Concrete


Allowable Pull-Out Loads
Anchoring to Autoclaved Aerated Concrete

5. Anchoring AAC Fasteners


Anchor / Nail
Drill Bit Screw
Load Value*
(pull-out strenght)
AAC-4 AAC-6

to AAC & Hebel Nails Length Ø Diam


in in Ø in # or Ø in
Block & Panel
lb lb
(1)
Hebel AAC Nail 4’’
4 1/4 Fixed directly Not 51 88
Fasteners: (min penetration: 3”) with hammer Required

Anchors used with AAC shall be


made of plastic or nylon. Wood, Hebel AAC Nail 6’’(1) 6 1/4 Fixed directly Not 88 137
(min penetration: 5”) with hammer Required
fiber, lead, metal or expansion
anchors are not recommended. Universal 11/8 1/4 1/4 #10 22 26
Plastic Anchor(2) 11/2 5/16 5/16 #12 26 31
Use power drills to make holes for (For use in all solid walls) 2 3/8 5/16 1/4 44 62
fasteners and masonry drill-bits
recommended (diameter) on table Thorsman(2)
9 ( drill-bit diameter may differ Anchor Red TP 2X (4) 13/8 1/4 3/16 #8 37 ---
from recommended by fastener 1/4 #10 --- 42
manufacturer; specifications have Anchor Brown TP 2B 15/8 5/16 1/4 #10 49 62
been adapted for AAC). Percusion Anchor Blue TP 3 13/4 3/8 5/16 #12 73 84
drilling or inverting the rotation
direction when drilling shall be TOX VLF(3)
avoided. Anchor 6/70 23/4 1/4 1/4 Anchor 66 ---
with screws
Anchor 8/80 - 8/135 31/8+ 5/16 5/16 included 102 ---
Anchor 10/100 - 10/160 4+ 3/8 3/8 (pre-assembled) 120 ---
The anchor shall penetrate tightly
in the hole to avoid rotation when
placing the screw. HILTI(2)
Anchor HUD-1 (10x50) 2 3/8 3/8 5/16 71 90
When using Fischer anchors, the Anchor HUD-1 (12x60) 23/8 1/2 7/16 3/8 128 185
external finish layer surrounding
the hole should be removed to Fisher(1)
allow the anchor to fully penetrate Anchor GB10 (5) 2 3/8 3/8 1/4 126 ---
into the AAC element. 1/2 1/4 --- 104
Anchor GB14 3 5/8 5/8 3/8 165 225
Anchor S10H80R 31/8 3/8 3/8 5/16 123 150
Hebel AAC Nail:
Hebel galvanized AAC nails are Notes: (1) Available at Xella AAC Texas, Inc. (2) Available at Hilti Shops, Home Depot, Lowe’s, etc.
designed specifically to provide a (3) Available at www.demandproducts.com (4) For AAC-6 (Block & Panel) use 1/4” drill bit. (5) For

definitive anchorage in the AAC. AAC-6 (Block & Panel) use 1/2” drill bit. *Safety Factor [SF]=5. Use masonry drill bits. Anchors
do not include screws (except TOX anchors).
Hebel AAC nails are directly
hammered-into the AAC element Table 9: Anchoring to Hebel AAC.
– no drilling is required.

Screws:
Precautions:
Always use screws of the diameter
Load values (pull-out strength)
recommended on table 9.
shown in chart shall be used only
as a reference guide; field testing
Minimum length of screw is
is suggested according to project
defined by the anchor length plus
requirements.
the thickness of the finish layer
and the thickness of the element
The load values (lb) shown in chart
to be fixed.
are for direct pull-out and a safety
factor of 5 is included in them. Full
penetration of screws into the
anchor is assumed to obtain such
load values.

Fig. 31: Recommended nails & anchors.

Fig. 30: Minimum screw length.

Hebel Aerated Concrete 11


November 2009. Printed and Made in Mexico.
Xella Mexicana, S.A. de C.V.
Río Amacuzac 1201 Ote.
Col. Valle Oriente
Garza García, NL 66269
México

Tels +52 (81) 8399 2424, 64 y 62


Fax +52 (81) 8399 2420 y 30

01 800 00 XELLA (93552)


ventasmexico@xella.com

Manufacturing Facility:
Carretera a Dulces Nombres Km 9.1
Pesquería, NL 66650
México

Tel +52 (81) 8369 1515


Fax +52 (81) 8369 1520

Xella AAC Texas, Inc.

San Antonio Office:


900 Schneider Dr.
Cibolo, TX 78108
USA

Tel (210) 402 3223


Fax (210) 402 6390

1 888 SA XELLA (72 93552)


xellatexas@xella.com

Xella and Hebel are registered trademarks of Xella Group.


Rio Grande Valley Office:
700 East Expressway 83
San Juan, TX 78589
USA

Tel (956) 782 9065


Fax (956) 782 9068

xellatexas-rgv@xella.com

www.hebel.mx
www.xellamexicana.com
www.xellatexas.com

Вам также может понравиться