Академический Документы
Профессиональный Документы
Культура Документы
1
All Rights Reserved © 2012 IJSETR
International Journal of Science, Engineering and Technology Research (IJSETR)
Volume 1, Issue 1, July 2012
(2) Conductor sizing depends on fault current and C. Earth Grid Design Formulae
conductivity as well as mechanical strength of material The conductor size for substation earth grid is
used.
(3) Resistivity of soil and surface layer determines the step
and touch potentials, which determine safe values of t c α r ρ r 10 4
operation as described in reference [1, 4-6]. Also the
multilayer resistivity has been a subject of continuous Ac If TCAP (1)
attention by the researchers [7-8]. Tm Ta
(4) A good grounding system provides a low resistance in ln1
order to minimize GPR (ground potential rise)[9]. K T
0 a
(5) Grid geometry is a major factor in determining the
step, touch and mesh potential contours and current The grid potential rise is GPR=IgRg [5]
distribution in grid. The limitations on the physical (2)
parameters of a ground grid are based on economics ρK s K is I g
and the physical limitations of the installation of the Es (3)
L g 1.15L r N r
grid.
The substation contains many voltages such as 1 1 1 1 n 2
- Transient enclosure voltage (TEV) Ks 1 0.5 s (4)
π 2h D h D
- Fast transient (VFT)
- Metal-to-metal touch voltage K is = 0.656 + 0.172 n s (5)
- Step voltage ρK m K im I g
Em (6)
- Touch voltage L g 1.15L r N r
- Mesh voltage
- Transferred voltage [3] 1 D 2 (D 2h) 2 h K ii 8
Km ln ln
2π 16hd 8Dd 4d K h π(2n m 1)
Kim = 0.656 + 0.172n m (8)
The step voltage limits are
0.116
E step(50kg) 1000 6 Cs ρ s (9)
t f
0.157
E step(70kg) 1000 6 Cs ρ s (10)
t f
The touch voltage limits are
0.116
E touch(50kg) 1000 1.5 Cs ρ s (11)
t f
0.157
Figure1. Illustration of the grounding system E touch(70kg) 1000 1.5 Cs ρ s (12)
t f
B. Advantages for Earth Grid
In the substation earth grids, the basic ideas and concepts FFၤၤၤ
for the following points serve such as For Substation Earthing Resistance, the formulae is
(1) A continuous conductor loop not only surrounds the
perimeters to enclose as much area as practical but also
1 1 1
helps to avoid very high current concentration and very R g ρ 1 (13)
L
t 20A 20
high gradient both in the grid area and near the 1 h
projecting cable ends. Enclosing more area also A
reduces the resistance of the earthing grid. Where,
(2) Within the loop, conductors are in parallel lines and Ac =Conductor size in sq-mm
along the structures and rows of equipments to provide If =Maximum fault current in kA
for short earth connection. tc =Duration of fault in sec
(3) Earth rods may be at the grid corners and at each α r =Thermal coefficient of resistivity at reference
temperature
second junction points along the perimeter. Earth rods
ρr =Resistivity of earth electrode at reference temperature
must also be installed at major equipments. µΩ/cm3
(4) This grid system extents over the entire substation TCAP=Thermal capacity factor
switchyard and often beyond the fence line. Tm =Maximum allowable temperature of conductor in ˚C
Nowadays, the earthing grid is used to reduce ground Ta =Ambient temperature in ˚C
potential rise and maintain the safe value of the substation K0 =Reversed value of thermal coefficient of resistivity at
earthing resistance [10]. 0 ˚C
Es = Calculating step voltage
Ρ = Soil resistivity in Ωm
Ks = Spacing factor for step voltage
2
All Rights Reserved © 2012 IJSETR
International Journal of Science, Engineering and Technology Research (IJSETR)
Volume 1, Issue 1, July 2012
3
All Rights Reserved © 2012 IJSETR
International Journal of Science, Engineering and Technology Research (IJSETR)
Volume 1, Issue 1, July 2012
0.58
Specifications Symbols Values
System voltage V 230 kV 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1
Total power P 100 MW Depth of burial grid conductor in m
Total area A 25× 15= 375 m2
300
Normal rated current I 251.022 A 6m space
7m space
40
Figure9. Various results for Step voltage according to the depths of
35 burial grid conductor (Primary side)
30
The values of the step voltage are steadily decreasing
because the depths of burial grid conductor and the earth
M e sh V o lta g e in V
25
6m space
rod spacing increase.
Substation Earthing Resistance in ohm
20 7m space
8m space
2.9 6m space
15
7m space
2.8 8m space
10
2.7
5
0
2.6
0.55 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 1.05
Dept h of burial grid conduct or in m
2.5
0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1
Figure7. Results for Mesh voltage by using the different depths Dept h of burial grid conduct or in m
of burial grid conductor (Primary side)
This figure describes that the more the depths of burial 720 6m space
Grid Potential Rise in V
7m space
grid conductor are plenty, the less the mesh voltage 700 8m space
640
0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1
Dept h of burial grid conduct or in m
4
All Rights Reserved © 2012 IJSETR
International Journal of Science, Engineering and Technology Research (IJSETR)
Volume 1, Issue 1, July 2012
VI. CONCLUSION
200
This paper aims to show the design and analysis of 230
150
kV substation earthing grid (Myauk Pyin) in Myanmar and
Mesh Voltage in V
40
ACKNOWLEDGMENT
6m space
20 7m space The author is deeply gratitude to Dr. Myint Thein,
0
8m space
Rector, Mandalay Technological University, for his
0.55 0.6 0.65 0.7 0.75 0.8 0.85
Depth of burial grid conductor in m
0.9 0.95 1 1.05
guidance and advice. The author wishes to express grateful
thanks to her chairman Dr. Khin Thu Zar Soe, Associate
Figure11. Comparison with the values of Mesh voltage and Step voltage due
to the depths of burial grid conductor (Transformer) Professor and Head Department of Electrical Power
The results of the mesh voltage are rising with the Engineering, Mandalay Technological University,
increasing of the depth of burial grid conductor. The values supervisor U Kyaw San Lwin, Lecturer, Department of
of the step voltage are inversely proportional to that of the Electrical Power Engineering, for his guidance and moral
mesh voltage. support provided during this research effort and to her all
teachers from Electrical Power Department, Mandalay
Substation Earthing Resistance in ohm
1260 0.7m depth [3] IEEE 142,"IEEE recommended practice for grounding industrial and
0.8m depth commercial power systems"
1250 0.9m depth [4] "IEEE guide for safety in AC Substation Grounding,” IEEE 80-2000,
1m depth
pp.1-192.
1240 [5] Kosztaluk, R.: Experimental Study of Transient Ground Impedances,
IEEE Transactions on Power Apparatus and Systems, Vol. PAS 100, No.
1230
6 6.2 6.4 6.6 6.8 7 7.2 7.4 7.6 7.8 8 11, pp. 4653-4660,(1981).
Eart h rod spacing in m [6] Brian Allport, ―Practical considerations (substation earthing)‖, VA
TECH Reyrolle Transmission
Figure12. Comparison results for Substation Earthing Resistance and [7] H.B. Dwight, "Calculations of Resistances to Ground", AIEE
Grid Potential Rise by varying the earth rod spacing (Secondary side) Transactions, December 1936, pp.1319-1328
The above figure12 shows the decreasing values for the [8] R. J. Heppe, ―Computation of potential at surface above an energized
substation earthing resistance and the grid potential rise by grid or other electrode, allowing for non-uniform current distribution,‖
changing the earth rod spacing and the depth of burial grid IEEE Trans. on PAS, vol. 98, no. 6, pp. 1978–1989, Nov.–Dec. 1979.
[9] Marlar Thein Oo, Ei Ei Cho, “Design of earthing system for new
conductor. substation project” , Myanmar
200
[10] Garrett, D. L. Guidelines for the Design, Installation, Testing and
Maintenance of Main Earthing Systems in Substations, Electricity
M esh Vo ltag e in V
150
Step Vo ltag e in V
100
50
0
6 7 8
Eart h rod spacing in m
5
All Rights Reserved © 2012 IJSETR