Академический Документы
Профессиональный Документы
Культура Документы
ABSTRACT
The paper aims at a detailed analysis of the current know-how in the construction of tunnel
cabling systems and shows the impact of fire and heat and the respective measures to be
taken. Therefore the results of the test projects EUREKA Firetun and MEMORIAL are
scrutinized and evaluated in view of the today's boundary conditions in typical cross sections.
It will clearly be shown how the heat distribution is dependant on the cross section and the
ventilation system.
Further it will be shown how concrete will protect cables from heat and damage even if the
coverage is low and how far open mounted installation channels are endangered.
For typical cabling systems it shall be outlined which requirements and specifications
regarding fire and heat resistance are reasonable and required. A short discussion of the
applicable norms and standards shall provide further information and decision guidance. It
shall be clarified that high safety standards re isolation and fire resistance are not generally
required.
fresh air
wall ascent
signal
wall ascent
fire emergency
lighting
tubing block
tubing block
d
c
Temperature [°C]
c e
d
e
f
The most common standard fire curve is the ISO standard 834. It forms the basis for the
examination of buildings and construction units. The examination of cable systems (cables
inclusive fittings and laying systems) is described in the DIN 4102-12 and led to the well-
known inspection certificates like e.g. "E30" (function during 30 minutes). However, the ISO
standard was developed for above ground structures - not for tunnels -, and has therefore only
limited relevance for this special field. Therefore, also the curve of the Netherlands authorities
(Rijkswaterstaat) is used, the so-called RWS-curve. The temperatures reach in accordance
with this fire curve over 1300 degrees after approximately 50 minutes. However, this curve is
internationally not recognized.
4. FIRE TESTS
Some time ago two series of fire tests in tunnels were executed. The results thereof are often
consulted for the evaluation of fire risks.
c Truck
d Bus
e Car
Temperature [°C]
d
e
The tests showed very high roof temperatures over the fire source, which were reached after a
short time of only 20 minutes. However, the tunnels had a cross-section area of 30 m2 only.
This corresponds with about the half of a modern road tunnel with two driving lanes.
Fig. 4: Memorial Tunnel Fire Ventilation Test Program: 10 minutes after fire start,
20 MW-fire
Fig. 5: Memorial Tunnel Fire Ventilation Test Program: 10 minutes after fire start,
50 MW-fire
The comparison with EUREKA shows that with attention of the flow effect and the cross
section many lower temperatures are measured. Further, the higher temperatures were
measured with relatively high fire loads only.
no temperature change ≤ 50 °C
For the active characteristics of cables the following standards are relevant. They define the
requirements during fire.
The system circuit integrity of cable systems is mostly the most important issue. Thus the
system function can be guaranteed during fires for a certain period. In the extensive
standardization work DIN 4102 the system circuit integrity is treated for electrical cable
systems in the part 12. The standard comprises the entire cabling system, i.e. cable inclusive
carrying system. However, it is applicable only to low-voltage cables (< 1 kV), thus not to
high-voltage cables and also not to fibre optic cables. System circuit integrity classes are
defined (in minutes): E30, E60, E90.
Furthermore, the requirements can be divided in three groups:
Halogen free
Require- Circuit Circuit
and flame
ments Requirements IEC-Standard integrity integrity
retardant
Group (≥ FE 5) (E30 - E90)
cables (FE 0)
Function Circuit integrity DIN 4102-12 -- -- X
Isolation Circuit integrity IEC 60331-11 -- -- X
Material flame retardant IEC 60332-1 X X X
halogen free IEC 60754-1 X X X
no corrosive gases IEC 60754-2 X X X
low smoke emission IEC 61034 X X X
low flame propagation IEC 60332-3-24 -- X X
9. CONCLUDING REMARK
Fire accidents in road tunnels result often in high temperatures due to the limited cross
section. The temperatures indicated in the standards always describe the values maximally
arising during a fire event; however, these values have to be expected only within the upper
tunnel area. At the lower level the temperatures are significantly lower. Due to safety
considerations, the general demand for system circuit integrity cannot be justified for cable
systems in accordance with DIN 4101-12, since the risk reduction is only marginal in many
cases. However, each project must separately be regarded due to the object-specific
conditions.