Air System Design Load Summary for EQ ONCOLOGICOS

Project Name: HMUA 09/18/2010


Prepared by: O.K. CLIMA LTDA 08:02a.m.

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 84,0 °F / 70,0 °F HEATING OA DB / WB 50,0 °F / 40,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 464 W 1583 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 619 W 2111 - 0 0 -
People 4 1180 1820 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4875 1820 - 0 0
Zone Conditioning - 4923 1820 - -22 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 832 CFM 0 - 832 CFM 0 -
Ventilation Load 250 CFM 3667 5357 250 CFM 1277 0
Supply Fan Load 832 CFM 1234 - 832 CFM -1234 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 9824 7177 - 21 0
Central Cooling Coil - 14319 7177 - 0 0
Central Heating Coil - -4495 - - 0 -
>> Total Conditioning - 9824 7177 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4,3 Page 1 of 1