Вы находитесь на странице: 1из 12

July 2012 / Bulletin 90-30

Head Pressure Control Valves


For High and Low Ambient Stability
®

OROA

ORI-6

LAC-4-DS
Page 2 – Bulletin 90-30

The design of air conditioning and refrigeration systems OPERATION


utilizing air cooled condensing units involves two main
LAC-4 – The valve designation LAC stands for Low
problems that must be solved if the system is to operate
Ambient Control. The LAC-4 is a three way modulating
reliably and economically. . . high ambient and low ambient
valve that responds to discharge pressure. As shown in Figures
operation. If the condensing unit is properly sized, it will
1 and 2, the discharge pressure bleeds around the pushrod to the
operate satisfactorily during extremely high ambient
underside of the diaphragm. The discharge pressure opposes the
temperatures. However, since most units will be required
dome pressure. When the outdoor ambient falls, the condensing
to operate at ambient temperatures below their design dry
pressure falls. This causes the discharge pressure to fall as well.
bulb temperature during most of the year, the solution to low
When the discharge pressure falls below the dome pressure,
ambient operation is more complex.
the valve modulates open to the discharge port which allows
Without good head pressure control during low ambient discharge gas to bypass the condenser. Mixing the discharge
operation, the system can experience both running cycle and gas with the liquid creates a high pressure at the condenser
off-cycle problems. Two running cycle problems are of prime outlet, reducing the flow and causing liquid to back up in the
concern: condenser. Flooding the condenser reduces the area available
1. Since the pressure differential across the thermostatic for condensing. This reduction in effective condenser surface
expansion valve port affects the rate of refrigerant flow, area results in a rise in condensing pressure. During summer
low head pressure generally causes insufficient refrig- conditions, the discharge pressure is high thus closing the
erant to be fed to the evaporator. discharge port. Hence, there is full liquid flow from the
condenser to the receiver.
2. Any system using hot gas for defrost or compressor
capacity control must have a normal head pressure to
operate properly. In either case failure to have sufficient Figure 1
head pressure will result in low suction pressure and/or LAC-4 Figure 2
iced evaporator coils. LAC-4-DS
The primary off-cycle problem is the possible inability to
get the system on-line if the refrigerant has migrated to the
condenser. The evaporator pressure may not build up to the
cut-in point of the low pressure control and the compressor Discharge
can’t start even though refrigeration is required. Even if the
evaporator pressure builds up to the cut-in setting, insufficient Receiver
flow through the TEV will cause a low suction pressure,
which results in compressor cycling.
The typical method of maintaining normal head pressure in a
refrigeration system during periods of low ambient temperature
Discharge
is to restrict liquid flow from the condenser to the receiver, Condenser
and at the same time divert hot gas to the inlet of the receiver. Receiver
This backs liquid refrigerant up into the condenser reducing its
capacity which in turn increases the condensing pressure. At
the same time the hot gas raises liquid pressure in the receiver,
allowing the system to operate normally.
Sporlan has adjustable and fixed setting direct acting head Condenser
pressure control valves for systems from 1 to 35 tons.

⚠WARNING – USER RESPONSIBILITY


Failure or improper selection or improper use of the products described herein or related items can cause death, personal injury and property damage.
This document and other information from Parker Hannifin Corporation, its subsidiaries and authorized distributors provide product or system options for further
investigation by users having technical expertise.
The user, through its own analysis and testing, is solely responsible for making the final selection of the system and components and assuring that all performance,
endurance, maintenance, safety and warning requirements of the application are met. The user must analyze all aspects of the application, follow applicable industry
standards, and follow the information concerning the product in the current product catalog and in any other materials provided from Parker or its subsidiaries or
authorized distributors.
To the extent that Parker or its subsidiaries or authorized distributors provide component or system options based upon data or specifications provided by the user,
the user is responsible for determining that such data and specifications are suitable and sufficient for all applications and reasonably foreseeable uses of the
components or systems.
For safety information see the Safety Guide at www.parker.com/safety or call 1-800-CParker.
OFFER OF SALE
The items described in this document are hereby offered for sale by Parker Hannifin Corporation, its subsidiaries or its authorized distributors. This offer and its
acceptance are governed by the provisions stated in the detailed “Offer of Sale” elsewhere in this document or available at www.parker.com.
FOR USE ON REFRIGERATION and/or AIR CONDITIONING SYSTEMS ONLY
For more information about our products visit us at www.sporlan.com.
Supersedes Bulletin 90-30, July 2006 and all prior publications.
Bulletin 90-30 – Page 3

LAC-5, LAC-10 – The LAC-5 and LAC-10 are also three- When the outdoor ambient temperature changes, the condensing
way modulating valves but they respond to receiver pressure. pressure changes. This causes the receiver pressure to fluctuate
As shown in Figure 3, the receiver pressure acts under the accordingly. As the receiver pressure decreases, the OROA
diaphragm. As the receiver pressure drops below the valve throttles the flow of liquid from the condenser. And as
setting, the seat moves away from the discharge port allowing the receiver pressure increases, the valve modulates in an
discharge gas to bypass the condenser. This discharge gas opening direction to maintain a nearly constant pressure in
warms the liquid in the receiver and raises the pressure to the the receiver. Since the ambient temperature of the element
valve setting. At the same time discharge gas is bypassing affects the valve pressure setting, the control pressure may change
the condenser, liquid flow from the condenser is restricted, slightly when the ambient temperature changes. However,
which allows liquid to back up in the condenser. Flooding the the valve and element temperature remain fairly constant.
condenser reduces the area available for condensing thus raising
the condensing pressure. During summer conditions, the seat An ORD valve is an integral part of the OROA valve. The
closes the discharge port due to high pressure in the receiver. operation of the ORD is described later.
Therefore, there is full liquid flow from the condenser to the
receiver. ORI – The ORI head pressure control valve is an inlet pressure
regulating valve and responds to changes in condensing
Figure 3 pressure only. The valve designation stands for on Rise of
Inlet pressure. As shown in Figure 5, the outlet pressure is
LAC-5
exerted on the underside of the bellows and on top of the seat
LAC-10
disc. Since the effective area of the bellows is equal to the
area of the port, the outlet pressure is cancelled and the inlet
pressure acting on the bottom of the seat disc opposes the
Discharge adjusting spring force. These two forces are the operating forces
of the ORI.
Receiver

When the outdoor ambient temperature changes, the ORI opens


or closes in response to the change in condensing pressure.
An increase in inlet pressure above the valve setting tends to
open the valve. If the ambient temperature drops, the condenser
Condenser
capacity is increased and the condensing pressure falls, causing
the ORI to modulate toward the closed position.
OROA – The OROA is a nonadjustable head pressure control
valve which performs the function of limiting the flow of liquid Figure 5
refrigerant from the condenser and at the same time regulates the ORI
flow of hot gas around the condenser to the receiver. The main
orifice of the OROA valve is controlled by the valve diaphragm Adjusting Spring
which causes the orifice to Open on Rise of Outlet pressure.
As shown in Figure 4, the inlet and outlet pressures are
exerted on the underside of the seat disc in an opening Bellows
direction. Since the area of the port is small in relationship to
the diaphragm area, the inlet pressure has little direct effect
on the operation of the valve. Therefore, the outlet or receiver
pressure is the control pressure which actuates the valve. The
force on top of the diaphragm, which opposes the control
Seat Disc
pressure, is due to the air charge in the element. These two
Seat
forces are the operating forces of the OROA valve that control
the main port.

ORD – The ORD valve is a pressure differential valve that


Figure 4 responds to changes in the pressure difference across the valve,
OROA Seat Disc Figure 6 on the next page. The valve designation stands for
Opens on Rise of Differential pressure. Therefore, the ORD
is dependent on some other control valve or action for its
operation. And in this respect, it is used with the ORI for head
Seat pressure control.

Receiver As the ORI valve starts to throttle the flow of liquid refrigerant
Discharge Seat
from the condenser, a pressure differential is created across the
Seat Disc ORD. When the differential reaches setpoint, the ORD starts
to open and bypasses hot gas to the liquid drain line. As the
Condenser differential increases, the ORD opens further until its full stroke
is reached at a differential of 10 psi above setpoint.
Page 4 – Bulletin 90-30

ORD – (cont.) Refrigerant Migration – During an off cycle there is a


Due to its function in the control of head pressure, the full stroke potential for refrigerant to migrate from the warm receiver to
can be utilized in selecting the ORD. the cold condenser. An auxiliary check valve should be used in
the liquid line between the LAC and the receiver to prevent this
Figure 6 from occurring. See Figure 7.
ORD
Figure 7
External Equalizer
Seat Disc See-All
Evaporator
TEV Solenoid
Valve
Seat Distributor

Catch-All
Condenser
The standard pressure setting for the ORD is 20 psig. For
systems where the pressure drop between the compressor and LAC
the receiver is higher than 14 psi, an ORD with a higher setting
is available. See Table 1 below. Check Valve
Compressor
Table 1
Receiver
Maximum Pressure Drop
Head Pressure
Between Compressor
Component Selection
and Receiver – psi
OROA-5-100 or -180
ORI/ORD – The operation of the ORI/ORD system is such that
Below 14 a constant receiver pressure is maintained for normal system
ORD-4-20 & ORI
*OROAB-5-100 or -180 operation. Since the ORI is adjustable over a nominal range of
15 – 19
*ORD-4-25 & ORI 65 to 225 psig, the desired pressure can be maintained for all of
*OROAC-5-100 or -180 the commonly used refrigerants.
20 – 24
*ORD-4-30 & ORI
*OROAD-5-100 or -180 As shown in Figure 8, the ORI is located in the liquid drain line
25 – 29
*ORD-4-35 & ORI between the condenser and the receiver. And the ORD is located
Bold type indicates pressure range. in a hot gas line bypassing the condenser. During periods of
*Available on Special Order ONLY.
low ambient temperature, the condensing pressure falls until it
approaches the setting of the ORI valve. The ORI then throttles,
APPLICATION restricting the flow of liquid from the condenser. This causes
LAC and OROA Pressure Settings – The LAC and OROA refrigerant to back up in the condenser thus reducing the active
valves are available with three standard settings which should condenser surface and raising the condensing pressure. Since
handle the majority of applications: 100 psig for R-134a; 180 it is really receiver pressure that needs to be maintained, the
psig for R-22, R-407C and R-502; and 210 psig for R-402A, bypass line with the ORD is required.
R-404A and R-507. The LAC valves can also be used with
other commonly used refrigerants including R-401A. Generally,
standard settings may be used for these refrigerants but special Figure 8
settings may be preferred for some applications. External Equalizer
See-All
The standard element is a non-adjustable dome element as Evaporator
TEV Solenoid
shown in Figure 3. However, there are many valves in the field Valve
Distributor
with non-adjustable remote bulbs indicated by an “R” following
the valve setting. Valves and elements with the remote bulb are
Condenser Catch-All
available on special order. The valve designation and setting are
stamped on the valve body. Many valves in the field have
ORI
special settings and should be replaced with the same valve to ORD-4-20
ensure satisfactory system performance.

The LAC-4-DS has a dual setting feature that allows a choice Compressor
between two fixed settings, see Figure 2. The DS element has Receiver
an internal spring that is set to maintain the lower setting. The
element is then charged with air to obtain the higher setting
and the capillary tube is pinched and fused. An example is an The ORD opens after the ORI has offered enough restriction to
LAC-4-DS-100/180. If the capillary tube is left intact the valve cause the differential between condensing pressure and receiver
will maintain a 180 psig setting. If the capillary tube is clipped pressure to exceed the ORD setpoint. The hot gas flowing
and fused again, the valve will maintain a 100 psig setting. It is through the ORD serves to heat the cold liquid being passed by
important to fuse the capillary tube tip after clipping to prevent the ORI. Thus the liquid reaches the receiver warm and with
moisture from entering the element. sufficient pressure to assure proper expansion valve operation.
Bulletin 90-30 – Page 5

ORI/ORD – (cont.) operate. One factor to keep in mind is that the valve setting
As long as sufficient refrigerant charge is in the system, the doesn’t make any difference if the system is short of refrigerant.
two valves modulate the flow automatically to maintain proper This is discussed below.
receiver pressure regardless of outside ambient temperature.
The ORI valves are adjustable over a nominal range of 65 to
While valve capacity ratings and basic selection procedures are 225 psig. And because of their adjustability, they can be used
given later, two other factors affect the proper selection of head with all commonly used refrigerants. The standard factory
pressure control valves . . . paralleling valves for larger systems setting is 120 psig for R-134a. If a higher adjustment range is
and pressure settings. These are discussed separately below necessary, replacement spring kits are available. KO-6-100/290
along with the other application factors that affect the operation (for ORI-6-65/225) and KO-10-100/290 (for ORI-10-65/225)
of a system. can be used to achieve the higher pressure range. See Bulletin
122. This change will result in approximately 12% less capacity
Paralleling Valves – Sporlan Head Pressure Control Valves than is stated on page 6 because of the stronger spring. Valves with
may be applied in parallel to provide higher refrigerant flow other settings and ranges are available in reasonable quantities
rates for large systems with load requirements greater than any on special order. Adjustment instructions are included in
single valve’s capacity. The ORD-4 is used with two sizes of Bulletin 90-31. Since the OROA is a non-adjustable valve,
head pressure control valves, ORI-6 and ORI-10. In those cases the desired receiver pressure setting must be specified. Three
where the ORI-10 is applied on systems with more capacity standard settings have been set up to handle the majority of
than the ORD-4 or when more than one head pressure control applications: 100 psig, 180 psig, and 210 psig. Valves with
valve is used, it is necessary to use two or more ORD-4 valves other pressure settings are available in reasonable quantities
in parallel. Since it is not harmful to oversize any of these on special order. Since the OROA controls receiver pressure,
valves, it is better to select them equal to or larger than the these settings approximate the nominal condensing pressure
system capacity to minimize pressure drop. settings of 120 psig and 200 psig for the ORI valves because of
the opening pressure differential of the ORD.
Head Pressure Control for Reclaim Systems – When
employing heat reclaim on a refrigeration system, the addition The standard setting for the ORD is 20 psig. That is, it will start
of head pressure controls is important not only to maintain to open when the pressure difference between the discharge line
liquid pressure at the expansion valve inlet, but also to assure and the receiver is 20 psig. This setting is suitable for all systems
the availability of quality hot gas at the reclaim heat exchanger. where the combined pressure drop through the condenser, the
ORI or OROA, and connecting piping is less than 14 psi.
Some precautions must be taken when installing heat reclaim on Therefore, if the ORI or OROA is selected for 2 psi ΔP, then
a system equipped with head pressure control. If reclaim coils the maximum allowable pressure drop through the condenser
are piped in a series circuit, additional pressure drop is created is 12 psi. Normally, condenser pressure drop on refrigeration
between the compressor discharge valve and the receiver inlet systems is less than 10 psi. However, many condensers on
by the added components. This additional pressure drop in two air conditioning systems may have pressure drops up to 25
condensers, three-way diverting valve, the head pressure psi. Therefore, when in doubt, consult with the equipment
control and associated piping might cause the ORD-4-20 or manufacturer or, if possible, measure it by reading the discharge
OROA-5-100 or -180 to stay in the bypass position at all times. pressure at the compressor and the receiver pressure during
full load operation. This reading should be taken with a
If this pressure drop is determined to be above 14 psi, consult normal condensing temperature at full load. For systems where
Table 1 for recommended HPC components. the condenser pressure drop is higher than normal, ORD valves
with higher settings are available. See Table l.
When heat reclaim is added to a parallel system, the only
increase in pressure drop is introduced by the diverting Piping Suggestions – Figures 7 and 8 are piping schematics
valve. This additional pressure drop must be considered when only to illustrate the general location of the head pressure control
selecting head pressure controls. See Table 1 for proper valves in the system. Sporlan recommends that recognized piping
selection. Refer to Sporlan Bulletin 30-20 for more information references be consulted for assistance in piping procedures.
on heat reclaim systems. Sporlan is not responsible for system design, any damage
arising from faulty system design, or for misapplication of its
Pressure Settings – The pressure settings of these valves products. If these valves are applied in any manner other than as
determine to a great extent how well the system will operate described in this bulletin, the Sporlan warranty is void.
once they are installed. The proper setting is a function of the
specific system on which the valves are applied. Generally, the The inlet connections on the ORI-6, ORI-10, and OROA valves
setting should be equivalent to a condensing temperature of should be sized the same as the outlet of the condenser where
approximately 90 to 100°F or a receiver pressure equivalent possible. The ORD-4 is available with 5/8” ODF connections
to a temperature of approximately 80 to 90°F. This means that only, since a 5/8” OD bypass line will handle flow capacities
when the ambient temperature falls below approximately 70°F, up to the capacity rating of this valve and on these systems
the head pressure control valve will start to throttle. Normally, the bypass line may be the same size as the discharge line.
it is not necessary or economical to operate with a higher setting Reducing couplings or bushings may be used to install the
than this. On systems with hot gas defrost, hot gas bypass for ORD-4 or the OROA-5 in systems with discharge and bypass
capacity control, or heat reclamation it is important that proper lines smaller than 5/8” ODF. The 5/8” ODF connection on the
head pressure control be utilized to ensure sufficient heat to OROA is used as the hot gas bypass line.
Page 6 – Bulletin 90-30

Piping Suggestions – (cont.) assembly. Inlet strainers are available for all head pressure
This is available in this manner for two reasons — to allow the control valves. Due to the construction of the ORD, it is only
bypassed hot gas to flow through the OROA to maintain the available with the strainer included. However, the strainer
element temperature and to eliminate the need of a separate tee is optional for the ORI and OROA valves. Just as with any
connection in the liquid drain line. Compared to the ORI and refrigerant flow control devices, the need for an inlet strainer
ORD combination, the OROA-5 installation process is simplified is a function of system cleanliness.
as the ORD-4 is included as an integral part of the OROA

HEAD PRESSURE CONTROL VALVE CAPACITIES


LOW AMBIENT (WINTER) CAPACITIES — TONS OF REFRIGERATION
Capacities are based on 0°F evaporator, 94°F condenser, 10°F subcooled liquid.
Valve Type Valve Type
Refrigerant Minimum Pressure Refrigerant Minimum Pressure
Valve Ambient Drop ORD-4 Valve Ambient Drop ORD-4
Setting Design Across OROA-5 Setting Design Across OROA-5
LAC-4 LAC-5 LAC-10 LAC-4 LAC-5 LAC-10
(psig) Temp. °F Valve (psi) ORI-6 (psig) Temp. °F Valve (psi) ORI-6
ORI-10 ORI-10
1 1.71 3.04 7.30 — 1 1.19 2.11 5.10 —
2 2.41 4.29 10.2 — 2 1.67 2.99 7.16 —
5 3.77 6.77 15.9 — 5 2.62 4.71 11.2 —
10 5.26 9.53 22.1 — 10 3.67 6.64 15.5 —
-20 -20
15 6.37 11.6 26.7 — 15 4.45 8.10 18.7 —
20 7.28 13.4 30.3 — 20 5.09 9.32 21.3 —
25 8.05 14.9 33.4 18.3 25 5.64 10.4 23.6 12.4
30 8.73 16.2 36.0 25.8 30 6.12 11.3 25.5 17.4
1 1.85 3.28 7.85 — 1 1.27 2.25 5.42 —
2 2.60 4.63 11.0 — 2 1.79 3.19 7.61 —
5 4.07 7.30 17.1 — 5 2.81 5.03 11.9 —
22 10 5.69 10.3 23.7 — 404A 10 3.92 7.08 16.5 —
0 0
(180) 15 6.88 12.5 28.6 — (210) 15 4.75 8.64 19.9 —
20 7.86 14.4 32.5 — 20 5.44 9.94 22.6 —
25 8.70 16.1 35.8 21.0 25 6.02 11.1 25.0 13.9
30 9.43 17.5 38.6 29.6 30 6.53 12.1 27.0 19.6
1 2.03 3.58 8.57 — 1 1.38 2.44 5.85 —
2 2.86 5.06 12.0 — 2 1.94 3.45 8.20 —
5 4.46 7.99 18.6 — 5 3.04 5.44 12.7 —
10 6.22 11.3 25.8 — 10 4.25 7.67 17.7 —
20 20
15 7.53 13.7 31.1 — 15 5.15 9.35 21.3 —
20 8.60 15.8 35.3 — 20 5.89 10.8 24.3 —
25 9.51 17.6 38.8 25.2 25 6.52 12.0 26.8 16.4
30 10.3 19.2 41.9 35.5 30 7.07 13.1 29.0 23.1
1 1.36 2.42 5.83 — 1 1.17 2.08 5.02 —
2 1.91 3.41 8.17 — 2 1.65 2.94 7.05 —
5 2.98 5.37 12.7 — 5 2.59 4.64 11.0 —
10 4.13 7.54 17.4 — 10 3.62 6.54 15.3 —
-20 -20
15 4.96 9.17 20.8 — 15 4.38 7.98 18.4 —
20 5.62 10.5 23.4 — 20 5.01 9.18 21.0 —
25 6.16 11.6 25.4 13.0 25 5.55 10.2 23.2 12.3
30 6.62 12.7 27.1 18.4 30 6.02 11.2 25.0 17.3
1 1.48 2.64 6.34 — 1 1.27 2.24 5.39 —
2 2.09 3.72 8.88 — 2 1.78 3.17 7.56 —
5 3.25 5.86 13.7 — 5 2.79 5.00 11.8 —
134a 10 4.51 8.23 18.9 — 507 10 3.90 7.05 16.3 —
0 0
(100) 15 5.42 10.0 22.5 — (210) 15 4.73 8.60 19.7 —
20 6.14 11.5 25.3 — 20 5.40 9.89 22.4 —
25 6.73 12.7 27.6 15.0 25 5.98 11.0 24.8 14.1
30 7.24 13.8 29.4 21.2 30 6.49 12.0 26.8 19.9
1 1.66 2.94 7.03 — 1 1.39 2.45 5.86 —
2 2.33 4.15 9.84 — 2 1.95 3.46 8.21 —
5 3.63 6.53 15.2 — 5 3.05 5.46 12.8 —
10 5.03 9.16 20.9 — 10 4.26 7.69 17.7 —
20 20
15 6.04 11.1 24.9 — 15 5.16 9.39 21.4 —
20 6.84 12.8 28.0 — 20 5.90 10.8 24.3 —
25 7.51 14.2 30.4 18.1 25 6.54 12.0 26.8 17.0
30 8.07 15.4 32.4 25.5 30 7.09 13.1 29.0 23.9
Bulletin 90-30 – Page 7

HEAD PRESSURE CONTROL VALVE CAPACITIES


HIGH AMBIENT (SUMMER) CAPACITIES — TONS OF REFRIGERATION
Capacities are based on 0°F evaporator, 110°F condenser, 10°F subcooled liquid.

Pressure Valve Type Pressure Valve Type


Drop Drop
Refrigerant Across Refrigerant Across

OROA-5

OROA-5
LAC-10

LAC-10
ORI-10

ORI-10
ORD-4

ORD-4
LAC-4

LAC-5

LAC-4

LAC-5
Valve Valve

ORI-6

ORI-6
(psi) (psi)
1 2.57 5.50 11.7 7.35 19.7 10.4 — 1 1.61 3.43 7.33 5.01 13.9 6.49 —
2 3.59 7.78 16.3 10.7 27.2 14.7 — 2 2.25 4.85 10.2 7.29 19.3 9.15 —
3 4.37 9.53 19.7 13.3 32.8 17.9 — 3 2.73 5.94 12.3 9.07 23.3 11.2 —
4 5.02 11.0 22.6 15.5 37.5 20.7 — 4 3.14 6.86 14.1 10.6 26.6 12.9 —
22 404A
5 5.60 12.3 25.1 17.5 41.6 23.1 — 5 3.50 7.67 15.7 12.0 29.5 14.4 —
6 6.11 13.5 27.3 19.4 45.3 25.3 — 6 3.82 8.40 17.1 13.2 32.1 15.8 —
8 7.02 15.6 31.3 22.6 51.8 29.2 — 8 4.39 9.70 19.6 15.4 36.7 18.2 —
10 7.82 17.4 34.8 25.5 57.5 32.6 — 10 4.89 10.8 21.8 17.4 40.7 20.3 —
1 2.30 4.92 10.5 4.90 12.2 9.31 — 1 1.57 3.36 7.17 4.94 13.7 6.36 —
2 3.22 6.96 14.5 7.13 16.8 13.1 — 2 2.20 4.75 9.96 7.19 18.9 8.96 —
3 3.91 8.53 17.6 8.88 20.3 16.1 — 3 2.67 5.82 12.1 8.95 22.9 11.0 —
4 4.49 9.85 20.2 10.4 23.2 18.5 — 4 3.07 6.72 13.8 10.4 26.2 12.6 —
134a 507
5 5.01 11.0 22.4 11.7 25.8 20.7 — 5 3.42 7.51 15.4 11.8 29.0 14.1 —
6 5.47 12.1 24.5 12.9 28.0 22.6 — 6 3.74 8.23 16.8 13.0 31.6 15.4 —
8 6.28 13.9 28.0 15.1 32.1 26.1 — 8 4.30 9.51 19.2 15.2 36.1 17.8 —
10 7.00 15.6 31.2 17.0 35.6 29.2 — 10 4.79 10.6 21.3 17.1 40.1 19.9 —

SELECTION PROCEDURES
The actual selection of Sporlan Head Pressure Control Valves mixture flowing through the valve at the minimum design
involves four basic items: ambient conditions that will determine the valve’s capacity. Once
1. System capacity in tons the valve’s capacity and pressure drop have been determined
at minimum design ambient conditions, the capacity of the
2. Refrigerant valve during high ambient conditions should be checked to
3. Minimum ambient design temperature determine the pressure drop of the valve with full liquid flow.
4. Allowable pressure drop across the valve
Example —Select a LAC valve for a 10 ton, R-22 unit with a
When selecting these valves it is necessary to consider the minimum design ambient temperature of -20°F. The LAC-10
valve’s capacity when it is controlling at the minimum ambient has a capacity of 10.2 tons at a 2 psi drop across the valve
design temperature. The minimum ambient design temperature according to the Low Ambient Capacity Table on page 6. The
is a factor because the bypassed discharge gas must heat the LAC-10 also has a capacity of 11.7 tons at a 1 psi drop across
subcooled liquid leaving the condenser to maintain the receiver the valve according to the High Ambient Capacity Table on
pressure. This subcooled liquid will approach the ambient page 7. The LAC-10 is the correct selection.
temperature. It is the flow of the discharge gas and liquid
Page 8 – Bulletin 90-30

SPECIFICATIONS
Standard Connections
Weight
Factory ODF Solder Dimensions (Inches) Replacement
Valve Type (lbs.)
Setting (Inches) Parts
(psig) Inlet(s) Outlet A B C D E F G H I Net Ship
1/4 1/4 0.77 0.85
LAC-4 3/8 3/8 1.78 1.87 3.02 2.38 4.73 0.80 0.88
Not
1/2 1/2 0.82 0.90
Available

Replacement Elements
3/8 3/8 0.87 1.02
LAC-4-DS 1.78 1.87 3.02 2.38 6.11
1/2 1/2 0.94 1.09
100, 1/2 1/2 1.65 1.60 3.77 2.99 6.10 5.59 2.50 2.65
180, Non-Adjustable
5/8 5/8 1.74 1.69 3.86 3.08 6.19 5.68 — — — — 2.55 2.70 Dome Element:
LAC-5 or
210 7/8 7/8 2.23 2.18 4.35 3.57 6.68 6.17 2.60 2.75 D3L (specify
1-1/8 1-1/8 2.38 2.33 4.50 3.72 6.83 6.32 2.75 2.90 setting) or

D3L

R3L
 1-3/8 Non-Adjustable
7/8 2.67 4.39 3.43 6.91 6.40 3.20 3.42 Remote Bulb
 7/8
LAC-10 2.82 Element: R3L
 1-3/8
1-1/8 2.56 4.83 3.87 7.35 6.84 3.28 3.50 (specify setting)
 1-1/8
5/8 5/8 825-5
1.00 1.25
ORI-6-65/225-H 120 7/8 7/8 9.85 5.04 6.37 — 825-7
1-1/8 1-1/8 1.25 1.50 825-9

Inlet Strainer
1-1/8 1-1/8 825-9
ORI-10-65/225-H 120 11.04 5.48 6.56 — 2.50 2.75
1-3/8 1-3/8 825-11
— — — — —
ORD-4-20 20 5/8 5/8 6.56 0.97 — — 0.33 0.50 825-5
100,  5/8
5/8 5.94 3.75 1.88 2.16 825-5
180,  5/8
OROA-5 2.00 2.25
or  5/8
210 7/8 6.19 4.00 2.12 2.41 825-7
 7/8
 Discharge Connection.
 Condenser Connection.

MATERIALS and CONSTRUCTION DETAILS


Port Size Element Type Connections
Valve Type Adjustable Body Material Seating Material Type of Joints
(Inches) & Material
Type Material
LAC-4 1/2
Domed Knife Edge
LAC-5 No 5/8 Solder Copper Brass Metal to Metal
Steel (Metal to Metal)
LAC-10 3/4
ORI-6 3/4 Bellows -
Yes Brass
ORI-10 1.218 Brass
Hermetic
ORD-4 1/2 — Solder Copper Copper Metal to Metal
Construction
No Diaphragm
OROA 5/8 Brass
Stainless Steel

UNDERWRITER’S LABORATORY INFORMATION


Both the ORI-6 and ORI-10 are U.L. Listed valves. They have a maximum rated pressure (MRP) of 450 psig. The LAC valves and
the OROA-5 are all U.L. Recognized components. The MRP for the LAC-4 is 500 psig, while the OROA-5, LAC-5, and LAC-10
have a MRP of 450 psig. All valves are in U.L. file SA-5460.
Bulletin 90-30 – Page 9

VALVE DESIGNATION/ORDERING INSTRUCTIONS


To eliminate shipment delays, specify complete valve designation.
3.62
LAC-4 LAC-4-DS 1.94 LAC-5 and LAC-10

1.94 3.62 R3L

D3L
Discharge Discharge
Discharge 4.00
Receiver E Receiver
Receiver
E
E
.75
C
D C C
D D
Condenser
Condenser Condenser
A B
A B A B

LAC – 4 – DS – 100/180 – 3/8 x 3/8 x 3/8 ODF


Valve Type: Dual Setting Valve Setting(s) (psig) Discharge Condenser Receiver
Valve Solder
Low Ambient (Omit for standard (Specify one setting for Connection Connection Connection
Size Connections
Control dome element) standard dome element) (Inches) (Inches) (Inches)

LAC – 5 – 180 – R – 5/8 x 5/8 x 5/8 ODF


Indicates Remote
Valve Type: Discharge Condenser Receiver
Valve Valve Setting Bulb Model Solder
Low Ambient Connection Connection Connection
Size (psig) (Delete for standard Connections
Control (Inches) (Inches) (Inches)
dome element)

ORI OROA

3.62
ORD-4

Receiver A
A
B B
C Receiver
Discharge C

Condenser
Condenser D
B A

ORI – 6 – 65/225 – 7/8” ODF – With Strainer – H


Valve Type: Port Size Nominal Designates
Solder Inlet Strainer
Open on Rise of (Eighths of Adjustment High Pressure
Connections (Optional)
Inlet Pressure an inch) Range (psig) Bellows

OROA – 5 – 180 – 5/8” ODF – With Strainer


Valve Type: Port Size Pressure
Solder Inlet Strainer
Open on Rise of (Eighths of Setting
Connections (Optional)
Outlet Pressure an inch) (psig)

ORD – 4 – 20
Valve Type: Port Size Opening
Open on Rise of (Eighths of Pressure
Differential Pressure an inch) Differential (psi)
OFFER OF SALE
The items described in this document and other documents and descriptions provided by Parker Hannifin Corporation, its subsidiaries and its authorized distributors (“Seller”)
are hereby offered for sale at prices to be established by Seller. This offer and its acceptance by any customer (“Buyer”) shall be governed by all of the following Terms and
Conditions. Buyer’s order for any item described in its document, when communicated to Seller verbally, or in writing, shall constitute acceptance of this offer. All goods,
services or work described will be referred to as “Products”.

1. Terms and Conditions. Seller’s willingness to offer application and follow applicable industry standards immediately terminate this agreement, in writing, if
Products, or accept an order for Products, to or from and Product information. If Seller provides Product or Buyer: (a) commits a breach of any provision of this
Buyer is subject to these Terms and Conditions or any system options, the user is responsible for determining agreement (b) appointments a trustee, receiver or
newer version of the terms and conditions found on-line that such data and specifications are suitable and custodian for all or any part of Buyer’s property (c)
at www.parker.com/saleterms/. Seller objects to any sufficient for all applications and reasonably files a petition for relief in bankruptcy on its own
contrary or additional terms or conditions of Buyer’s foreseeable uses of the Products or systems. behalf, or by a third party (d) makes an assignment
order or any other document issued by Buyer. 8. Loss to Buyer’s Property. Any designs, tools, for the benefit of creditors, or (e) dissolves or liquidates
2. Price Adjustments; Payments. Prices stated on patterns, materials, drawings, confidential information all or a majority of its assets.
Seller’s quote or other documentation offered by Seller or equipment furnished by Buyer or any other items 17. Governing Law. This agreement and the sale and
are valid for 30 days, and do not include any sales, which become Buyer’s property, will be considered delivery of all Products hereunder shall be deemed
use, or other taxes unless specifically stated. Unless obsolete and may be destroyed by Seller after two to have taken place in and shall be governed and
otherwise specified by Seller, all prices are F.C.A. consecutive years have elapsed without Buyer ordering construed in accordance with the laws of the State of
Seller’s facility (INCOTERMS 2010). Payment is subject the items manufactured using such property. Seller Ohio, as applicable to contracts executed and wholly
to credit approval and is due 30 days from the date of shall not be responsible for any loss or damage to such performed therein and without regard to conflicts of
invoice or such other term as required by Seller’s Credit property while it is in Seller’s possession or control. laws principles. Buyer irrevocably agrees and consents
Department, after which Buyer shall pay interest on any 9. Special Tooling. A tooling charge may be imposed to the exclusive jurisdiction and venue of the courts of
unpaid invoices at the rate of 1.5% per month or the for any special tooling, including without limitation, Cuyahoga County, Ohio with respect to any dispute,
maximum allowable rate under applicable law. dies, fixtures, molds and patterns, acquired to controversy or claim arising out of or relating to this
3. Delivery Dates; Title and Risk; Shipment. All manufacture Products. Such special tooling shall be agreement.
delivery dates are approximate and Seller shall not be and remain Seller’s property notwithstanding payment 18. Indemnity for Infringement of Intellectual
responsible for any damages resulting from any delay. of any charges by Buyer. In no event will Buyer acquire Property Rights. Seller shall have no liability for
Regardless of the manner of shipment, title to any any interest in apparatus belonging to Seller which is infringement of any patents, trademarks, copyrights,
products and risk of loss or damage shall pass to Buyer utilized in the manufacture of the Products, even if such trade dress, trade secrets or similar rights except
upon placement of the products with the shipment apparatus has been specially converted or adapted for as provided in this Section. Seller will defend and
carrier at Seller’s facility. Unless otherwise stated, Seller such manufacture and notwithstanding any charges indemnify Buyer against allegations of infringement
may exercise its judgment in choosing the carrier and paid by Buyer. Unless otherwise agreed, Seller shall of U.S. patents, U.S. trademarks, copyrights, trade
means of delivery. No deferment of shipment at Buyers’ have the right to alter, discard or otherwise dispose dress and trade secrets (“Intellectual Property Rights”).
request beyond the respective dates indicated will be of any special tooling or other property in its sole Seller will defend at its expense and will pay the cost
made except on terms that will indemnify, defend and discretion at any time. of any settlement or damages awarded in an action
hold Seller harmless against all loss and additional 10. Buyer’s Obligation; Rights of Seller. To secure brought against Buyer based on an allegation that a
expense. Buyer shall be responsible for any additional payment of all sums due or otherwise, Seller shall Product sold pursuant to this Agreement infringes the
shipping charges incurred by Seller due to Buyer’s acts retain a security interest in the goods delivered and Intellectual Property Rights of a third party. Seller’s
or omissions. this agreement shall be deemed a Security Agreement obligation to defend and indemnify Buyer is contingent
4. Warranty. Seller warrants that the Products sold under the Uniform Commercial Code. Buyer authorizes on Buyer notifying Seller within ten (10) days after
hereunder shall be free from defects in material or Seller as its attorney to execute and file on Buyer’s Buyer becomes aware of such allegations of
workmanship for a period of twelve months from the behalf all documents Seller deems necessary to perfect infringement, and Seller having sole control over the
date of delivery to Buyer or 2,000 hours of normal use, its security interest. defense of any allegations or actions including all
whichever occurs first. The prices charged for Seller’s 11. Improper use and Indemnity. Buyer shall negotiations for settlement or compromise. If a Product
products are based upon the exclusive limited indemnify, defend, and hold Seller harmless from any is subject to a claim that it infringes the Intellectual
warranty stated above, and upon the following claim, liability, damages, lawsuits, and costs (including Property Rights of a third party, Seller may, at its sole
disclaimer: DISCLAIMER OF WARRANTY: THIS attorney fees), whether for personal injury, property expense and option, procure for Buyer the right to
WARRANTY COMPRISES THE SOLE AND ENTIRE damage, patent, trademark or copyright infringement continue using the Product, replace or modify the
WARRANTY PERTAINING TO PRODUCTS or any other claim, brought by or incurred by Buyer, Product so as to make it noninfringing, or offer to
PROVIDED HEREUNDER. SELLER DISCLAIMS ALL Buyer’s employees, or any other person, arising out of: accept return of the Product and return the purchase
OTHER WARRANTIES, EXPRESS AND IMPLIED, (a) improper selection, improper application or other price less a reasonable allowance for depreciation.
INCLUDING DESIGN, MERCHANTABILITY AND misuse of Products purchased by Buyer from Seller; Notwithstanding the foregoing, Seller shall have no
FITNESS FOR A PARTICULAR PURPOSE. (b) any act or omission, negligent or otherwise, of liability for claims of infringement based on information
5. Claims; Commencement of Actions. Buyer shall Buyer; (c) Seller’s use of patterns, plans, drawings, provided by Buyer, or directed to Products delivered
promptly inspect all Products upon delivery. No claims or specifications furnished by Buyer to manufacture hereunder for which the designs are specified in whole
for shortages will be allowed unless reported to the Product; or (d) Buyer’s failure to comply with these or part by Buyer, or infringements resulting from the
Seller within 10 days of delivery. No other claims terms and conditions. Seller shall not indemnify Buyer modification, combination or use in a system of any
against Seller will be allowed unless asserted in writing under any circumstance except as otherwise provided. Product sold hereunder. The foregoing provisions of
within 30 days after delivery. Buyer shall notify Seller 12. Cancellations and Changes. Orders shall not be this Section shall constitute Seller’s sole and exclusive
of any alleged breach of warranty within 30 days after subject to cancellation or change by Buyer for any liability and Buyer’s sole and exclusive remedy for
the date the defect is or should have been discovered reason, except with Seller’s written consent and upon infringement of Intellectual Property Rights.
by Buyer. Any action based upon breach of this terms that will indemnify, defend and hold Seller 19. Entire Agreement. This agreement contains the
agreement or upon any other claim arising out of this harmless against all direct, incidental and consequential entire agreement between the Buyer and Seller and
sale (other than an action by Seller for an amount due loss or damage. Seller may change product features, constitutes the final, complete and exclusive expression
on any invoice) must be commenced within 12 months specifications, designs and availability with notice of the terms of sale. All prior or contemporaneous
from the date of the breach without regard to the date to Buyer. written or oral agreements or negotiations with respect
breach is discovered. 13. Limitation on Assignment. Buyer may not assign to the subject matter are herein merged.
6. LIMITATION OF LIABILITY. UPON its rights or obligations under this agreement without 20. Compliance with Law, U. K. Bribery Act and
NOTIFICATION, SELLER WILL, AT ITS OPTION, the prior written consent of Seller. U.S. Foreign Corrupt Practices Act. Buyer agrees
REPAIR OR REPLACE A DEFECTIVE PRODUCT, OR 14. Force Majeure. Seller does not assume the risk to comply with all applicable laws and regulations,
REFUND THE PURCHASE PRICE. IN NO EVENT and shall not be liable for delay or failure to perform including both those of the United Kingdom and
SHALL SELLER BE LIABLE TO BUYER FOR ANY any of Seller’s obligations by reason of circumstances the United States of America, and of the country or
SPECIAL, INDIRECT, INCIDENTAL OR beyond the reasonable control of Seller (hereinafter countries of the Territory in which Buyer may operate,
CONSEQUENTIAL DAMAGES ARISING OUT OF, “Events of Force Majeure”). Events of Force Majeure including without limitation the U. K. Bribery Act, the
OR AS THE RESULT OF, THE SALE, DELIVERY, shall include without limitation: accidents, strikes or U.S. Foreign Corrupt Practices Act (“FCPA”) and the
NON-DELIVERY, SERVICING, USE OR LOSS OF labor disputes, acts of any government or government U.S. Anti-Kickback Act (the “Anti-Kickback Act”), and
USE OF THE PRODUCTS OR ANY PART THEREOF, agency, acts of nature, delays or failures in delivery agrees to indemnify and hold harmless Seller from the
OR FOR ANY CHARGES OR EXPENSES OF ANY from carriers or suppliers, shortages of materials, or consequences of any violation of such provisions by
NATURE INCURRED WITHOUT SELLER’S WRITTEN any other cause beyond Seller’s reasonable control. Buyer, its employees or agents. Buyer acknowledges
CONSENT, EVEN IF SELLER HAS BEEN NEGLIGENT, 15. Waiver and Severability. Failure to enforce any that they are familiar with the provisions of the U. K.
WHETHER IN CONTRACT, TORT OR OTHER LEGAL provision of this agreement will not waive that Bribery Act, the FCPA and the Anti-Kickback Act, and
THEORY. IN NO EVENT SHALL SELLER’S LIABILITY provision nor will any such failure prejudice Seller’s certifies that Buyer will adhere to the requirements
UNDER ANY CLAIM MADE BY BUYER EXCEED THE right to enforce that provision in the future. thereof. In particular, Buyer represents and agrees that
PURCHASE PRICE OF THE PRODUCTS. Invalidation of any provision of this agreement by Buyer shall not make any payment or give anything
7. User Responsibility. The user, through its own legislation or other rule of law shall not invalidate any of value, directly or indirectly to any governmental
analysis and testing, is solely responsible for making other provision herein. The remaining provisions of official, any foreign political party or official thereof, any
the final selection of the system and Product and this agreement will remain in full force and effect. candidate for foreign political office, or any commercial
assuring that all performance, endurance, maintenance, 16. Termination. Seller may terminate this agreement entity or person, for the purpose of influencing such
safety and warning requirements of the application for any reason and at any time by giving Buyer thirty person to purchase products or otherwise benefit the
are met. The user must analyze all aspects of the (30) days written notice of termination. Seller may business of Seller.
© 2012 Parker Hannifin Corporation. Bulletin 90-30 / 072012
Parker Hannifin Corporation
Sporlan Division
206 Lange Drive • Washington, MO 63090 USA
phone 636 239 1111 • fax 636 239 9130
www.sporlan.com

Вам также может понравиться