Wind Data :
Basic Wind speed = 47 m/s
Terrain category = 1
Class of structure = C
Design wind speed, Vz
Vb = 47
K1 (considering mean probable design life of wall as 25 years) = 0.9
K2 (terrain category 1 and class of structure, C) = 0.99
K3 (ground is almost flat) = 1
Vz = Vb. K1. K2. K3 = 41.877 m/s
Wind Force, F
F = Cf Ae Pz
A) Force on wall, F1
Here, b =136 metre(approx), h= 2.5 m, b/h = 54.4
Since, wall is on ground and b/h = 54.4
Cf Drag coefficient 1.6
Ae effective frontal strip area 1 m2
2
Pz Design wind pressure 1052.21 N/m
Therefore, F1 = 1683.5358 N/m2
B) Force on Barbed wire, F2
Solidity ratio = 10%
Corressponding value of Cf = 1.9
(for single frame having flat
sided members)
Ae effective frontal strip area 0.1 m2
2
Pz Design wind pressure 1052.21 N/m
Therefore, F2 = 199.92 N
Wind moment due to Wall and Barbed wire
=199.92x(2.5+0.6/2) + 1683.536x2.5x (2.5/2) = 5820.8254 Nm
= 5.82 kNm
Tensile stress at the base of the wall is very much less. Moreover, Base of the
wall is supported by R.C.C beam . Therefore, no vertical bending will occur
due to wind load on wall. Ok.
Design of Plinth Beam (Normal condition)
Data:
Size of the Beam : 250 x 400 x 6000 mm
Ht. Of Brick wall above beam : 2500 mm
Effective depth, d = 400 - 50 - 16/2 = 342 mm
Dead load of beam = 0.4 x 0.25 x 1.0 x 25 = 2.5 kN/m
Imposed load (Bk wall)=
(i) .125 x 1.5 x 1.0 x 19.2 3.6
(ii) .25 x 1.0 x 1.0 x 19.2 4.8 = 8.4 kN/m
+ ve Bending moment (at support) Staad calculation 38.67 kNm
-ve Bending moment (at centre) 9.728 kNm
Moment due to Earth pressure (1.0m ht.)
2
= 1/2x16x(1.0) x 0.25 @ 1.0/3 m 0.67 kNm
Mu = 1.5 (38.67 + 0.67) = 59.01 kNm
A) Design for maximum Bending moment at support :
The limiting moment of resistance,
2
Mulim = 0.138 fck bd
2
= 0.138 x 20 x 250 x 342 = 80.71 kNm
Mu = = 59.01 kNm
Mulim > Mu Hence , it is under reinforced beam
Percentage of steel,
4.6 Mu
1- 1- 2
f ck bd
Pt = 50
fy /fck
6
Mu 59.01 x 10
= 2.02
2 2
bd 250 x 342
4.6 x 2.02
1- 1-
20
Pt = 50 = 0.54
500
20
2
Provide , 2/16 F + 2/12 F bar = 628 mm
Moments:
(i) Wind moment due to Wall and Barbed wire = 5.82 kNm
(ii) Moment due to Earth pressure (1.0m ht.) = 0.67 kNm
(iii) Moment due to vertical loads (staad) = 38.67 kNm
Total 45.16 kN/m
4.6 x 1.74
1- 1-
20
Pt = 50 = 0.45
500
20
6
2 1.005 x 10
Mu / f ck bD = 2
0.002
20 x 300 x 300
2
Pu / f ck bD and Mu/ fck bD is very much less,
To ensure proper composite action minimum area of longitudinal steel is required.
Transverse reinforcement :
Diametre (f t) and spacing (Sv) of lateral ties are determined as follows :
ft < 5 mm
< larger diametre of 16 mm of longitudinal bars / 4 = 4 mm
Consider, f t = 8 mm
and Sv < minimum dimension of column section = 300 mm
< 16 x smaller diametre of 16mm of longitudinal bar = 256 mm
< 48 x diametre of 8 mm of lateral ties = 384 mm
Hence provide 8 mm f lateral ties at spacing 250 mm c/c
Design of Column ( wind condition)
vertical Load on Column: = 72.6 kN
Moments:
(i) Wind moment due to Wall and Barbed wire = 5.82 kNm
(ii) Moment due to Earth pressure (1.0m ht.) = 0.67 kNm
Total 6.49 kNm
6
2 6.49 x 10
Mu / f ck bD = 2
0.01
20 x 300 x 300 x 1.33
2
Pu / f ck bD and Mu/ fck bD is very much less,
To ensure proper composite action 0.89% steel is provided.
which is more than minimum area of steel required in column. Hence, Ok.
Design of Foundation (Eccentric consideration)
Loads :
Total Column Load = 72.6 kN
Assuming weight of footing = 14.52 kN
(20% of column load) Total = 87.12 kN
= 87120 N
Moments:
(i) Wind moment due to Wall and Barbed wire = 5.82 kNm
(ii) Moment due to Earth pressure (1.0m ht.) = 0.67 kNm
Total = 6.49 kNm
= 6490 Nm
Eccentricity :
6490
= = 0.07 m = 70 mm
87120
Area of footing :
Total load
=
Safe bearing capacity
87120
= 0.87 m2
100000
Therefore, side of footing = √ 0.87 0.93 m
72.6x 10 3 2
Net upward pressure intensity = = 50417 N/m
1.2 x 1.2
Depth of footing :
(1) Punching shear consideration :
Punching load = Column load - Reaction on column area.
= 72600 - 50417 x 0.30 2 = 68062 N
Factored punching load = 1.5 x 68062 = 102093 N
Area of Steel :
Mu 12270 x 1000
2 2
= 1.09
bd 300 x 194
4.6 x 1.09
1- 1-
20
Pt = 50 = 0.27
500
20
2
Therefore, Ast = 0.27%x 300 x 194 = 157.14 mm