EARTH FAULT PROTECTION
By
R Makesh Kandan
D
TOPICS TO BE COVERED

T
 GENERAL BASIS

AF
 RESIDUALLY CONNECTED RELAY
 CORE BALANCE
 SBEF
 REF
R
High Impedance REF
Low Impedance REF
D
Makesh Kandan.P
GO THROUGH SOME BASIS

T
Short Circuit:

AF
As per IEC 60909,Accidental or Intentional Conductive path b/w two or more conductive parts
forcing the electric potential differences b/w these conductive parts to be equal or close to zero.
Types:
Symm. & Unsymm. Faults
Bolted Fault - Conductor Solidly Connected,
Fault Impedance equal to zero.
R
Ground Faults - Phase get direct contact with earth
- Phase get direct contact to metallic part i.e. Grounded.
D
Arcing Faults - b/w two close conductor but are not in direct contact.

Makesh Kandan.P
EARTH FAULT – ORIGIN & CONSEQUENCES

T
ORIGIN:

AF
 Reduced Insulation
 Physical Damage to Insulation
 Excessive Transient or Steady State Voltage Stresses on Insulation
 Moisture, Atmospheric Contamination, Mechanical Stresses etc.

CONSEQUENCE:
R
 Shutdown if there is proper shutdown, if proper protection system is there.
 Destroy the equipment due to the arc blast or fire.
D
 Burning of Electrical Shock to the Personnel.

Makesh Kandan.P
EARTH FAULT CURRENT FLOW

T
AF
R
D
Makesh Kandan. P
EARTH FAULT – DETECTION METHOD

T
RESIDUALLY CONNECTION METHOD

AF
 The sum (IR+IY+IB) is called Residual Current.
 In absence of earth-fault, Residual Current is Zero (i.e. IR+IY+IB=0).
 During earth fault the conditions is disturbed &
(IR+IY+IB) is no more zero.
R
 Commonly used method.
 Instantaneous Trip is not used.
 Less Selectivity.
D
 Unrestricted Earth Fault Protection.
Makesh Kandan. P
EARTH FAULT – DETECTION METHOD

T
CORE BALANCE SCHEME (ZSCT)

AF
 Based on Flux Summation.
 Better Sensitivity
 Use Only One Transformer.
 Setting down to 10% of circuit current rating.
R
D
Makesh Kandan.P
EARTH FAULT – DETECTION METHOD

T
GROUND RETURN

AF
 Mostly used in solidly grounded 480V, 3 phase 3 wire or 3 phase 4 wire.
 CT Placed in Neutral to Ground Connection.
 Known as Standby Earth Fault (SBEF).
 Last Line of Defense.
R
 1st Stage Trips LV Incomer & 2nd Stage Trips Upstream.
 Unrestricted Earth Fault Protection.
D
Makesh Kandan.P
EARTH FAULT – DETECTION METHOD

T
RESTRICTED EARTH FAULT (REF) PROTECTION

AF
 Biased Differential Protection is less sensitive for single phase to earth faults close to earth
points.
 Unit Earth Fault Protection.
 Usually Applied for Start Winding of Transformer.
 Two Types
R
High Impedance REF Protection.
Low Impedance RFE Protection.
D
Makesh Kandan.P