Вы находитесь на странице: 1из 4

SAFE FILL DIA OF

TRANS MIX DIA OF DYKE


HSD TANK HSD ID TRANSMI TRANS TYPE OF TRANSMIX CAPCITY OF HEIGHT OF FOUNDATION DYKE
TANK HEIGHT HSD NO TYPE OF HSD TANK FOUNDATION WIDTH Dyke Area
HEIGHT (m) (m) X ID (m) MIX NO. TANK LARGEST HSD FOUNDATION (m) (m) HEIGHT
(m) (m) HSD (m)
TANK TRANSMIX

HSD 20 9 34 12 3 2 FIXED CONE ROOF FLOATING ROOF 15900 1 34.5 12.5 61.646 11901.41 0
1 Area of Dyke 50000.00
2 Height of Dyke Assumed ‘H’ = 1.6
3 Dia of MS tanks 'd1' 28
4 Dia of MS tanks 'd2' 28
5 height of MS tanks 20
6 Height of Foundation ‘h’= 1
7 Diameter of MS Foundations ‘D1’ = 25
8 Diameter of MS Foundations ‘D2’ = 25
9 Number of Tanks ‘MS n1’ 1
10 Number of Tanks MS n2’ 3
11 Fire wall dimensions (Height x Width) : .3m X.6m
12 Length of Fire Wall Dimension 41
13 No of Fire Wall Dimension 4
A) Dyke enclosure volume = Area of Dyke X Dyke Height 80000
B) Working capacityof Largest tank = 7897
1.1 MS Tank foundation volume:
Volume of a tank foundation = Σπ/4 D2 X h X n
D1 : Fdn MS Dia tanks = 25
n1 : Number of MS tank fdns = 1
Volume of MS tank foundations = Σπ/4 D12 X h X n1 490.625
1.2 MS Tank foundation volume:
Volume of a tank foundation = Σπ/4 D2 X h X n
D1 : Fdn MS Dia tanks = 25
n1 : Number of MS tank fdns = 3
Volume of MS tank foundations = Σπ/4 D12 X h X n1 1471.875
Total Tank Foundation Volume 1962.5
2) Liquid volume of tanks (other than the Largest Tank) above Fdn upto Dyke Ht:
Liquid volume of tank above Fdn upto Dyke Ht. =( Σπ/4 d1 2 X (H-h) X (n1-1))+( Σπ/4
d2^2 X (H-h) X (n2) 1107.792

3) Volume of Fire wall = 29.52

C) Dead volume = (1) + (2) + (3) 3099.812

B+C = 10996.812
A = 80000
A > B + C (means A-C > B) and Dyke height is b/w 1 and 2 m
So Dyke height (1.72 M) assumed is OK.
dyke wall height = dyke height calculated + 200mm( free board )
m2 6722057920
m
m INPUTS
m
m
m
m
m
nos.
nos.

m
nos.
m3
m3

m
m
m3

m
m
m3
…………………….(1)

m3 ….…….…………..(2)

m3 …………………….(3)

m3

m3
m3

m
6722.05792