SINAMICS G150
Operating Instructions 6-35
Operation 03/06
NOTE
The advantages of Totally Integrated Automation (TIA) can only be utilized when
selecting "0".
General information
Selecting a telegram via CU parameter p0922 determines which process data is
transferred between the master and slave.
From the perspective of the slave (SINAMICS G150), the received process data
comprises the receive words and the process data to be sent the send words.
The receive and send words comprise the following elements:
• Receive words: Control words and setpoints
• Send words: Status words and actual values
CTW 1 N_SETP
SINAMICS G150
6-36 Operating Instructions
03/06 Operation
SINAMICS G150
Operating Instructions 6-37
Operation 03/06
Telegr. PZD 1 PZD 2 PZD 3 PZD 4 PZD 5 PZD 6 PZD 7 PZD 8 PZD 9 PZD 10
1 CTW 1 N_setp_A
STW 1 N_act_A
2 CTW 1 N_setp_B CTW2
STW 1 N_act_B STW2
3 CTW 1 N_setp_B CTW2 G1_CTW
STW 1 N_act_B STW2 G1_STW G1_XACT1 G1_XACT2
4 CTW 1 N_setp_B CTW2 G1_CTW
STW 1 N_act_B STW2 G1_STW Further allocation: see FP2420
20 CTW 1 N_setp_A
STW 1 N_act_GLATT Ia_act_GLATT M_act_GLATT P_act_GLATT MELD_NAMUR
352 CTW 1 N_setp_A PCS7_3 PCS7_4 PCS7_5 PCS7_6
STW 1 N_act_GLATT Ia_act_GLATT M_act_GLATT WARN_CODE FAULT_CODE
999 CTW 1 free free free free free free free free free
STW 1 free free free free free free free free free
Overview
SINAMICS G150
6-38 Operating Instructions
03/06 Operation
1 = ON
0: Pulse block, main contactor (if fitted) is
0 = Coast to stop (OFF2) BI: p0844
opened 1
1 BI: p0845
1 = Do not coast to stop
Note: Control signal OFF2 is generated by ANDing BI: p0844 and BI: p0845.
0: Deceleration on the rapid-stop ramp
0 = Fast stop (OFF3) (p1115), then pulse block, main contactor (if
fitted) is opened. 1 BI: p0848
2
1 = No emergency stop
Note: Control signal OFF3 is generated by ANDing BI: p0848 and BI: p0849.
1: Enable inverter, pulse enable, ramp-up
0 = Disable operation with active setpoint
3 1 BI: p0852
1 = Enable operation 0: Pulse inhibit. The motor coasts down.
The "Ready To Run" status remains set.
0 = Set ramp generator to 0: The ramp generator output is set to
zero setpoint "0".
4 1 BI: p1140
1 = Enable ramp-function
generator
0: The current setpoint is frozen at the ramp
0 = Freeze ramp generator
5 generator output. 1 BI: p1141
1 = Restart ramp generator
SINAMICS G150
Operating Instructions 6-39
Operation 03/06
1 = ON
0: Pulse block, main contactor (if fitted) is
0 = Coast to stop (OFF2) BI: p0844
opened 1
1 BI: p0845
1 = Do not coast to stop
Note: Control signal OFF2 is generated by ANDing BI: p0844 and BI: p0845.
0: Deceleration on the rapid-stop ramp
0 = Fast stop (OFF3) (p1115), then pulse block, main contactor (if
fitted) is opened. 1 BI: p0848
2
1 = No emergency stop
Note: Control signal OFF3 is generated by ANDing BI: p0848 and BI: p0849.
1: Enable inverter, pulse enable, ramp-up
0 = Disable operation with active setpoint
3 1 BI: p0852
1 = Enable operation 0: Pulse inhibit. The motor coasts down.
The "Ready To Run" status remains set.
0 = Set ramp generator to 0: The ramp generator output is set to
zero setpoint "0".
4 1 BI: p1140
1 = Enable ramp-function
generator
0: The current setpoint is frozen at the ramp
5 0 = Freeze ramp generator 1 BI: p1141
generator output.
SINAMICS G150
6-40 Operating Instructions
03/06 Operation
SINAMICS G150
Operating Instructions 6-41
Operation 03/06
SINAMICS G150
6-42 Operating Instructions
03/06 Operation
Overview
SINAMICS G150
Operating Instructions 6-43
Operation 03/06
SINAMICS G150
6-44 Operating Instructions
03/06 Operation
12 Reserved
SINAMICS G150
Operating Instructions 6-45
Operation 03/06
12 Reserved
15 Reserved
SINAMICS G150
6-46 Operating Instructions
03/06 Operation
SINAMICS G150
Operating Instructions 6-47
Operation 03/06
SINAMICS G150
6-48 Operating Instructions