Вы находитесь на странице: 1из 40

INSTRUMENT TRANSFORMERS.

LOW VOLTAGE.
INSULATORS AND WALL BUSHINGS.
This document may be subject to changes.
Contact ARTECHE to confirm the characteristics and
availability of the products described here.

Moving together
CONTENTS
1. Instrument transformers. Low voltage. 2. Insulators and wall bushings
Current transformers › Support insulators. Indoor
• AR | 27
› Metering. Indoor
• IFG-5 | 6 › Signal insulators. Indoor
• IFP-0 | 6 • ARC | 28
• IFW-4 / IFW-5 | 7
• IFX | 7 › Signalling box
• LAF-1 | 28
› Metering and protection. Indoor
• IFE | 8 › Wall bushings. Indoor
• IFG-7 / IFG-8 | 9 • PRU / PRP | 30
• IFH-6 | 10 • PBD | 31
• IFP-1 | 11 • PBE | 31
• IFW-0-DS / IFW-4-DS | 11 • PPL | 32

› Metering and protection. Indoor / Outdoor › Wall bushings. Indoor


• IFH-0 | 12 • PPE-36 | 33
• IFH-1 | 13
• IFH-3 | 14
• IFH-4 | 15
• IFH-5 | 16 3. Manufacturing and technology | 34
• IFH-7 | 17
• IFH-10 | 18


• IFH-12 | 19
Protection. Split-core
4. Quality and environment | 36
• BAT | 20
• BAR | 20
• BAS | 21 5. Service | 38
› Homopolar. Indoor / Outdoor
• BAR | 22
• IFH-3 | 23
• ICO-3 | 23
› Window type for bushings
• BUSHING CT | 24
› Auxiliary
• IRM | 24

Voltage Transformers
› Metering and protection. Indoor
• URC | 25

Instrument transformers | Low voltage


1. INSTRUMENT TRANSFORMERS.
LOW VOLTAGE
Current Transformers
Voltage Transformers

4 Instrument transformers | Low voltage


CURRENT TRANSFORMERS
>> WINDOW TYPE >> SQUARE WINDOW TYPE
Current transformers without primary winding Current transformers for installation in low
intended to be used in low voltage bars or voltage panel bars where available space is
isolated cables. critical.

RANGE RANGE

› Primary nominal currents up to 10,000 A. › Primary nominal currents up to 3,000 A.


› Secondary currents 1 and 5 A. › Secondary currents 1 and 5 A.
› Frequencies 50 Hz and 60 Hz. › Frequencies 50 Hz and 60 Hz.

APPLICATIONS APPLICATIONS

› Low voltage panels. › Low voltage panels.


› Motor control.
› Primary distribution switchgear. ADVANTAGES
› Secondary distribution switchgear.
› Capacitor banks.
› Variety of models with different window
sizes available.
› Power generation.
› Sealable cover for secondary terminals.
› Dead tank circuit breaker.
› Railway.

ADVANTAGES

› Wide range of models with different >> WITH PRIMARY BAR


window sizes available.
Transformers for installation in low voltage
› Multi-ratio transformer for different
measuring panels.
transformation ratios available.
› Sealable cover for secondary terminals.
RANGE
› Stainless steel screws available.
› Designs for outdoor service available. › Primary nominal currents up to 1,000 A.
› Transformer can be assembled in any › Secondary currents 1 and 5 A.
position. › Frequencies 50 Hz and 60 Hz.
› Split core current transformers to install
without handling the primary bars or
APPLICATIONS
cables.
› Low voltage panels.

ADVANTAGES

› Mechanism for fastening the transformer


onto the bar.
› Sealable cover for secondary terminals.
› Connection for voltage tap.

Instrument transformers | Low voltage 5


1. CURRENT TRANSFORMERS > Metering > Indoor

IFG-5
Sealable cover
CHARACTERISTICS
Primary Secondary terminals M4
current CL0.2 VA CL0.5 VA CL1 VA
A
50
75 4
100 7.5 0
ø7

101
93.5
125 10 ø2
2
150 15
200 15 30
250 20 40
300 30 50
400 30 35
500 15 35 40 60
600 20 50 60

62
73
85

IFP-0
CHARACTERISTICS

Primary Marks Mark


current A and B C
A Cl 0.5 Fs5 VA
5
Secondary terminals M4 Sealable cover
10
20 80 90
30 43 85
40 10 and 15
50
75
100
150
106
90

200
E

300
40

400 10 and 15
500
600
145
Thermal Current: 60xIn
110 a 115
= = With passing-through hole
6.5 MARK C - From 200 to 600 A
2.26

DIMENSIONS 102
3.5

Mark Current E
A Up to 300 A 5 P1 P2
63.5
30
33

B From 200 to 600 A 10 K L


10.25
3.5

S1 S2
k l
2.26

145
110 a 115 30.25

6 Instrument transformers | Low voltage


1. CURRENT TRANSFORMERS > Metering > Indoor

IFW-4 • IFW-5
CHARACTERISTICS Secondary terminals M4 Sealable cover

Primary
CL0.5 CL1 H
Type current
VA VA G
A
3,000
IFW-4 3,500
4,000
15 30
3,500
IFW-5 4,000
5,000

65
D
B

A F
C E

DIMENSIONS Screws to fix
transformer on busbar
Type A B C D E F G H
IFW-4 62 105 150 193 75 50 78 85.5
IFW-5 95 105 190 200 75 50 78 85.5

IFX
Secondary terminals M4 Sealable cover
CHARACTERISTICS
F G
Primary CL0.5
Type current FS 5
A VA
400*
500*
600*
10
750*
IFX-0 800*
D
B

1,000*
1,200*
10 and
1,250*
15
1,500*
750*
800*
1,000*
IFX-1
1,200*
A Screws to fix
1,500* 10 C E
transformer on
2,000* busbar
2,000*
IFX-2 2,500*
3,000*

*Extended current rating up: 150%


Thermal Current: 60xIn

DIMENSIONS

Type A B C D E F G
IFX-0 22 82 85 135 80 48 58
IFX-1 22 102 88 168 74.5 50 55
IFX-2 32 102 102 172 64 56 50

Instrument transformers | Low voltage 7


1. CURRENT TRANSFORMERS > Metering and protection > Indoor

IFE
CHARACTERISTICS
SINGLE PRIMARY RATIO AND ONE SECONDARY
Inner diameter Inner diameter
Ø D= 60 mm Ø D= 80 mm
Primary Class and burden Class and burden Class and burden Class and burden
Type
current A METERING PROTECTION METERING PROTECTION
200 5 VA CL1 2.5 VA 5P10
250 12.5 VA CL1 2.5 VA 5P10
300 5 VA CL0.5 2.5 VA 5P10
400 12.5 VA CL0.5 5 VA 5P10
5 VA CL0.2 5 VA 5P10
500
25 VA CL0.5 2.5 VA 5P15
IFE-1 10 VA CL0.2 5 VA 5P10
600
50 VA CL0.5 2.5 VA 5P20
20 VA CL0.2 7.5 VA 5P10
800
80 VA CL0.5 2.5 VA 5P15
40 VA CL0.2 10 VA 5P10
1000
100 VA CL0.5 2.5 VA 5P15
70 VA CL0.2 10 VA 5P10
1200
120 VA CL0.5 5 VA 5P15
150 35 VA CL3 2.5 VA 5P10 25 VA CL3 2.5 VA 5P10
2.5 VA CL0.5 5 VA 5P10 5 VA CL1 2.5 VA 5P10
200
10 VA CL1 5 VA 5P10 30 VA CL3 2.5 VA 5P15
5 VA CL0.5 7.5 VA 5P10 2.5 VA CL0.5 5 VA 5P10
250
20 VA CL1 2.5 VA 5P20 10 VA CL1 2.5 VA 5P15
7.5 VA CL0.5 7.5 VA 5P10 5 VA CL0.5 5 VA 5P10
300
35 VA CL1 2.5 VA 5P20 20 VA CL1 2.5 VA 5P20

C
5 VA CL0.2 10 VA 5P10 10 VA CL0.5 7.5 VA 5P10 F
400 Ø
20 VA CL0.5 5 VA 5P20 45 VA CL1 2.5 VA 5P20
10 VA CL0.2 15 VA 5P10 5 VA CL0.2 10 VA 5P10
500
40 VA CL0.5 5 VA 5P20 25 VA CL0.5 2.5 VA 5P20

H
IFE-3 15 VA CL0.2 15 VA 5P10 10 VA CL0.2 12.5 VA 5P10 Ø
D
600
75 VA CL0.5 7.5 VA 5P20 40 VA CL0.5 5 VA 5P20
40 VA CL0.2 20 VA 5P10 20 VA CL0.2 15 VA 5P10
800
175 VA CL0.5 10 VA 5P20 100 VA CL0.5 5 VA 5P20

B
75 VA CL0.2 30 VA 5P10 45 VA CL0.2 20 VA 5P10
1000
200 VA CL0.5 12.5 VA 5P20 150 VA CL0.5 7.5 VA 5P20
30 VA 5P10 70 VA CL0.2 25 VA 5P10

1,5
1200 100 VA CL0.2
12.5 VA 5P20 175 VA CL0.5 10 VA 5P20
25 VA 5P10 A
1500 125 VA CL0.2
10 VA 5P20
Ø7

35 VA 5P10
2000 200 VA CL0.2
10 VA 5P20
= =
25

DIMENSIONS

D = =
Type Mark A B C E F G H
(±1.5) 105
IFE-1 120 81 83.5 60 40 145 50 164.5 G
A 60
IFE-3 120 103 106 35 190 55 209
B 80

8 Instrument transformers | Low voltage


1. CURRENT TRANSFORMERS > Metering and protection > Indoor

IFG-7 • IFG-8
CHARACTERISTICS

SINGLE PRIMARY RATIO AND ONE SECONDARY


Primary Class and burden Class and burden
Type
current A METERING PROTECTION
200 2.5 VA CL0.5 2.5 VA 5P10
250 5 VA CL0.5 2.5 VA 5P10
300 7.5 VA CL0.5 2.5 VA 5P15
2.5 VA CL0.2 5 VA 5P10
400
20 VA CL0.5 2.5 VA 5P15
7.5 VA CL0.2 5 VA 5P10
IFG-7 500
40 VA CL0.5 2.5 VA 5P20
15 VA CL0.2 7.5 VA 5P10
600
60 VA CL0.5 2.5 VA 5P20
35 VA CL0.2 7.5 VA 5P10
800
90 VA CL0.5 2.5 VA 5P15
60 VA CL0.2 12.5 VA 5P10
1000
120 VA CL0.5 2.5 VA 5P20
100 25 VA CL3 2.5 VA 5P10
150 7.5 VA CL1 2.5 VA 5P15
200 5 VA CL0.5 2.5 VA 5P10
5 VA CL0.5 5 VA 5P10
250
20 VA CL1 2.5 VA 5P15 › IFG-7
2.5 VA CL0.2 10 VA 5P10
300
15 VA CL0.5 2.5 VA 5P20
7.5 VA CL0.2 12.5 VA 5P10
400
IFG-8 40 VA CL0.5 5 VA 5P20
15 VA CL0.2 15 VA 5P10
500
75 VA CL0.5 5 VA 5P20
30 VA CL0.2 15 VA 5P10
600
125 VA CL0.5 7.5 VA 5P20 Ø 125
A
70 VA CL0.2 20 VA 5P10
800
180 VA CL0.5 7.5 VA 5P20
125 VA CL0.2 30 VA 5P10
1000
240 VA CL0.5 10 VA 5P20

DIMENSIONS P2

Type A
IFG-7 55
50
160

IFG-8 85 Ø
147
1.5

2.5 90 2.5
= =
2.25
3.5
=

=
80

59
33
=
=

3.5
2.25

6.5
= =
110

Instrument transformers | Low voltage 9


1. CURRENT TRANSFORMERS > Metering and protection > Indoor

IFH-6
DIMENSIONS & CHARACTERISTICS
Primary
D L Mark current METERING PROTECTION METERING + PROTECTION
A
100 5 VA CL1 5 VA 5P20
200 10 VA CL0.5 12.5 VA 5P20 5 VA CL1 + 7.5 VA 5P20
130 I 400 15 VA CL0.2 25 VA 5P20 10 VA CL0.5 + 15 VA 5P20
600 15 VA CL0.2S 40 VA 5P20 15 VA CL0.2 + 15 VA 5P20
1,000 70 VA CL0.2S 70 VA 5P20 15 VA CL0.2S + 30 VA 5P20
100 7.5 VA 5P20 5 VA CL3 + 5 VA 5P20
200 20 VA 5P20 5 VA CL1 + 15 VA 5P20
60 180 B 400 40 VA 5P20 15 VA CL0.5 + 25 VA 5P20
600 60 VA 5P20 15 VA CL0.2S + 35 VA 5P20
1,000 100 VA 5P20 15 VA CL0.2S + 60 VA 5P20
100 10 VA 5P20 5 VA CL3 + 7.5 VA 5P20
200 25 VA 5P20 10 VA CL1 + 20 VA 5P20
225 E 400 55 VA 5P20 20 VA CL0.5 + 40 VA 5P20
600 85 VA 5P20 15 VA CL0.2 + 60 VA 5P20
1,000 140 VA 5P20 15 VA CL0.2S + 90 VA 5P20
100 15 VA CL3 5 VA 5P20
200 5 VA CL0.5 12.5 VA 5P20 2.5 VA CL0.5 + 5 VA 5P20
400 10 VA CL0.2 25 VA 5P20 12.5 VA CL0.5 + 12.5 VA 5P20
130 J
600 35 VA CL0.2 40 VA 5P20 15 VA CL0.2 + 15 VA 5P20
1,000 40 VA CL0.2S 70 VA 5P20 15 VA CL0.2S + 20 VA 5P20
2,000 300 VA CL0.2S 135 VA 5P20 15 VA CL0.2S + 65 VA 5P20

D
100 7.5 VA 5P20
60

Ø
325
200 20 VA 5P20 2.5 VA CL0.5 + 12.5 VA 5P20 290 Ø2
80 400 40 VA 5P20 12.5 VA CL0.5 + 25 VA 5P20
180 C
600 65 VA 5P20 15 VA CL0.2 + 35 VA 5P20
1,000 100 VA 5P20 15 VA CL0.2S + 60 VA 5P20
2,000 200 VA 5P20

141
100 10 VA 5P20
200 25 VA 5P20 10 VA CL1 + 20 VA 5P20
225 F 400 55 VA 5P20 20 VA CL0.5 + 40 VA 5P20
600 85 VA 5P20 12.5 VA CL0.2 + 60 VA 5P20
1,000 140 VA 5P20 15 VA CL0.2S + 90 VA 5P20
100 15 VA CL3 5 VA 5P20

9
200 5 VA CL0.5 12.5 VA 5P20 2.5 VA CL0.5 + 5 VA 5P20
110 130 L 400 7.5 VA CL0.2 25 VA 5P20 12.5 VA CL0.5 + 12.5 VA 5P20 Ø
600 35 VA CL0.2 40 VA 5P20 15 VA CL0.2 + 15 VA 5P20
1,000 40 VA CL0.2S 70 VA 5P20 15 VA CL0.2S + 20 VA 5P20 =

118
200 15 VA CL1 10 VA 5P20 5 VA CL1 + 5 VA 5P20 98
400 30 VA CL0.5 20 VA 5P20 5 VA CL0.5 + 10 VA 5P20
=

600 20 VA CL0.2 30 VA 5P20 7.5 VA CL0.2 + 15 VA 5P20


130 A
1,000 25 VA CL0.2S 50 VA 5P20 20 VA CL0.2 + 25 VA 5P20
1,500 85 VA CL0.2S 75 VA 5P20 20 VA CL0.2 S + 25 VA 5P20
2,000 200 VA CL0.2S 100 VA 5P20 25 VA CL0.2S + 50 VA 5P20
200 15 VA 5P20 7.5 VA CL1 + 7.5 VA 5P20 = =
130
400 30 VA 5P20 15 VA CL0.5 + 15 VA 5P20 195
180 D
600 45 VA 5P20 10 VA CL0.2 + 25 VA 5P20 220
1,000 80 VA 5P20 10 VA CL0.2 S + 45 VA 5P20
L
200 20 VA 5P20 7.5 VA CL1 + 12.5 VA 5P20
400 45 VA 5P20 15 VA CL0.5 + 25 VA 5P20
225 G
600 65 VA 5P20 7.5 VA CL0.2 + 45 VA 5P20
1,000 115 VA 5P20 7.5 VA CL0.2 S + 70 VA 5P20
200 7.5 VA CL1 10 VA 5P20
400 15 VA CL0.5 20 VA 5P20 7.5 VA CL0.5 + 10 VA 5P20
160 225 K 600 12.5 VA CL0.2 25 VA 5P20 20 VA CL0.5 + 15 VA 5P20
1,000 10 VA CL0.2S 50 VA 5P20 25 VA CL0.2 + 25 VA 5P20
1,500 50 VA CL0.2S 55 VA 5P20 15 VA CL0.2 S + 40 VA 5P20
1,000 15 VA CL0.5 15 VA 5P10 10 VA CL0.5 + 10 VA 5P10
205 180 H 1,200 20 VA CL0.5 20 VA 5P10 15 VA CL0.5 + 15 VA 5P10
1,600 25 VA CL0.5 25 VA 5P10 10 VA CL0.5 + 10 VA 5P10
100 10 VA 5P20 5 VA CL3 + 7.5 VA 5P20
200 25 VA 5P20 10 VA CL1 + 20 VA 5P20
70 225 M 400 55 VA 5P20 20 VA CL0.5 + 40 VA 5P20
600 85 VA 5P20 15 VA CL0.2 + 60 VA 5P20
1,000 140 VA 5P20 15 VA CL0.2S + 90 VA 5P20

10 Instrument transformers | Low voltage


1. CURRENT TRANSFORMERS > Metering and protection > Indoor

IFP-1
MARK A - Up to 1,000 A
225
125 175
= =

5
25 25 6.
Ø

=
10

166
145

120
145
50
72.5

=
M12
= =

6
145
CHARACTERISTICS

Primary CL0,2 SP10


Mark With passing - Through hole
current A VA VA
MARK B - From 250 to 1000 A
5 to 250 30 20
147
300 15 15
400 20
A 600 30

10.25
800 30 35
900 40
1,000 45 50.25
300 15 15
400 20
500 25
B 600 30
30
800 35
900 40
1,000 45

Thermal Current: 60xIn

IFW-O/DS • IFW-4/DS
CHARACTERISTICS

Ratio Burden VA Ratio Class and burden


Type
(A) PROTECTION (A) METERING + PROTECTION
250/5 7.5 VA 10P5
300/5 10 VA 10P5
350/5 12.5 VA 10P5
15 VA 10P5 or
400/5
5 VA 5P10
15 VA 10P5 or 10 VA CL1 + 5 VA 5P10
500/5 500/5-5
7.5 VA 5P10 5 VA 10P10
IFW-O/DS 20 VA 10P5 or 10 VA CL1 + 7.5 VA 5P10
600/5 600/5-5
10 VA 5P10 7.5 VA 10P10
30 VA 10P5 or 15 VA CL0.5 + 10 VA 5P10
1,000/5 1,000/5-5
15 VA 5P10 10 VA 10P10
30 VA 10P5 or 15 VA CL0.5 + 10 VA 5P10
1,250/5 1,250/5-5
15 VA 5P10 12.5 VA 10P10
40 VA 10P5 or 15 VA CL0.5 + 15 VA 5P10
1,500/5 1,500/5-5
20 VA 5P10 15 VA 10P10 Sealable cover Secondary terminals M4
45 VA 10P5 15 VA CL0.5 + 15 VA 5P10
2,000/5 2,000/5-5 E
20 VA 5P10 20 VA 10P10
40 VA 10P5 15 VA CL0.5 + 20 VA 5P10
2,500/5 2,500/5-5
30 VA 5P10 25 VA 10P10
40 VA 10P5 15 VA CL0.5 + 25 VA 5P10
IFW-4/DS 3,000/5 3,000/5-5
30 VA 5P10 30 VA 10P10
40 VA 10P5 15 VA CL0.5 + 25 VA 5P10
3,500/5 3,500/5-5
30 VA 5P10 30 VA 10P10
35
D
B

45 VA 10P5 15 VA CL0.5 + 30 VA 5P10


4,000/5 4,000/5-5
40 VA 5P10 35 VA 10P10

DIMENSIONS
A F
Type A B C D E F G C G
IFW-0/DS 20 62 84 126 126 80 105 Screws to fix transformer
IFW-4/DS 62 105 150 193 136 90 115 on busbar

Instrument transformers | Low voltage 11


1. CURRENT TRANSFORMERS > Metering and protection > Indoor / Outdoor

IFH-0
Secondary terminals M6 (max. 6)

Indoor service
45

Mark A

PG 16

Secondary terminals
M6 (max. 6)

PG 16
57.5

Outdoor service
Mark B
Ø1
60
89.5

65
Ø
260

226.5 170
= =

13
Ø
=
=
113

60

90
M8
=

=
= =
106 200

CHARACTERISTICS
ONE SECONDARY TWO SECONDARIES
Primary
METERING PROTECTION METERING + PROTECTION
current A
100 5 VA 5P10
150 10 VA CL1 10 VA 5P10
200 25 VA CL1 10 VA 5P10 5 VA CL1 + 10 VA 5P5
250 25 VA CL1 15 VA 5P10 15 VA CL1 + 5 VA 5P10
300 20 VA CL0.5 15 VA 5P10 20 VA CL1 + 5 VA 5P10
400 40 VA CL0.5 20 VA 5P10 15 VA CL0.5 + 10 VA 5P10
500 50 VA CL0.5 30 VA 5P10 15 VA CL0.5 + 15 VA 5P10
600 50 VA CL0.5 15 VA 5P20 20 VA CL0.5 + 20 VA 5P10
750 65 VA CL0.5 20 VA 5P20 30 VA CL0.5 + 25 VA 5P10
800 40 VA CL0.5 + 30 VA 5P10
1,000 30 VA CL0.2 25 VA 5P20 50 VA CL0.5 + 35 VA 5P10
1,200 30 VA CL0.2 30 VA 5P20 50 VA CL0.5 + 45 VA 5P10

12 Instrument transformers | Low voltage


1. CURRENT TRANSFORMERS > Metering and protection > Indoor / Outdoor

IFH-1
Secondary terminals M6 (max. 6)

Indoor
45

service

PG 16

Secondary terminals M6 (max. 6)


Outdoor
service
57.5

45

PG 16
Ø

P1
107.5

Ø 120
290

D
Ø

257
Ø1
90
125

M8

67.5 67.5
20 135
170
= =
11
Ø
=
=
60

90
=

= =
200

CHARACTERISTICS
INNER DIAMETER (ØD= 60 mm) INNER DIAMETER (ØD= 80 mm)
ONE SECONDARY TWO SECONDARIES ONE SECONDARY TWO SECONDARIES
Primary
current METERING PROTECTION METERING + PROTECTION METERING PROTECTION METERING + PROTECTION
A
75 15 VA CL3 7.5 VA 10P10 10 VA CL3 10 VA 10P5
100 50 VA CL3 12.5 VA 5P10 40 VA CL3 7.5 VA 10P10
150 20 VA CL1 15 VA 5P10 30 VA CL3 + 10 VA 5P10 10 VA CL1 12.5 VA 5P10 20 VA CL3 + 5 VA 5P10
200 10 VA CL0.5 20 VA 5P10 10 VA CL1 + 12.5 VA 5P10 25 VA CL1 7.5 VA 5P20 5 VA CL1 + 7.5 VA 5P10
250 20 VA CL0.5 25 VA 5P10 20 VA CL1 + 15 VA 5P10 12.5 VA CL0.5 10 VA 5P20 10 VA CL1 + 10 VA 5P10
300 40 VA CL0.5 15 VA 5P20 10 VA CL0.5 + 20 VA 5P10 20 VA CL0.5 12.5 VA 5P20 15 VA CL1 + 12.5 VA 5P10
400 90 VA CL0.5 25 VA 5P20 10 VA CL0.5 + 15 VA 5P20 50 VA CL0.5 15 VA 5P20 10 VA CL0.5 + 15 VA 5P10
500 50 VA CL0.2 30 VA 5P20 20 VA CL0.5 + 25 VA 5P20 25 VA CL0.2 20 VA 5P20 12.5 VA CL0.5 + 5 VA 5P20
600 75 VA CL0.2 35 VA 5P20 30 VA CL0.5 + 25 VA 5P20 40 VA CL0.2 20 VA 5P20 20 VA CL0.5 + 15 VA 5P20
800 100 VA CL0.2 50 VA 5P20 15 VA CL0.2 + 35 VA 5P20 100 VA CL0.2 30 VA 5P20 40 VA CL0.5 + 20 VA 5P20
1,000 100 VA CL0.2 60 VA 5P20 30 VA CL0.2 + 45 VA 5P20 100 VA CL0.2 35 VA 5P20 20 VA CL0.2 + 25 VA 5P20
1,200 100 VA CL0.2 60 VA 5P20 50 VA CL0.2 + 50 VA 5P20 100 VA CL0.2 45 VA 5P20 30 VA CL0.2 + 30 VA 5P20
1,500 100 VA CL0.2 50 VA 5P20 50 VA CL0.2 + 40 VA 5P20
2,000 100 VA CL0.2 75 VA 5P20 100 VA CL0.2 + 40 VA 5P20

DIMENSIONS

Mark Ø D (±1.5) Service


A 60
Outdoor
B 80
C 60
Indoor
D 80

Instrument transformers | Low voltage 13


1. CURRENT TRANSFORMERS > Metering and protection > Indoor / Outdoor

IFH-3
Secondary terminals M6 (max. 6)

Indoor service
45

Mark A
PG 16

Secondary terminals M6 (max. 6)

Outdoor service
PG 16
57.5

Mark B

M8 (on request)
P1
121.5
323

0
110 Ø 22
Ø

290
Ø 90°

Ø1
50
144

Ø 45
° M8

= =
20 115
170
= =
11
Ø
=
=
60

90
=

= =
200

CHARACTERISTICS

ONE SECONDARY TWO SECONDARIES

Primary
current METERING PROTECTION METERING + PROTECTION
A
150 5 VA CL1 5 VA 5P20
200 15 VA CL1 5 VA 5P20
250 5 VA CL0.5 10 VA 5P20
300 12.5 VA CL0.5 10 VA 5P20 5 VA CL1 + 5 VA 5P20
350 20 VA CL0.5 12.5 VA 5P20 5 VA CL0.5 + 5 VA 5P20
400 20 VA CL0.5 15 VA 5P20 5 VA CL0.5 + 7.5 VA 5P20
500 25 VA CL0.5 20 VA 5P20 10 VA CL0.5 + 10 VA 5P20
600 50 VA CL0.5 20 VA 5P20 12.5 VA CL0.5 + 12.5 VA 5P20
1,000 50 VA CL0.5 20 VA 5P20
1,500 50 VA CL0.5 20 VA 5P20 30 VA CL0.5 + 30 VA 5P20
2,000 50 VA CL0.5 20 VA 5P20
3,000 50 VA CL0.5 20 VA 5P20 30 VA CL0.5 + 30 VA 5P20

14 Instrument transformers | Low voltage


1. CURRENT TRANSFORMERS > Metering and protection > Indoor / Outdoor

IFH-4
Secondary terminals M5 (max. 9)
Secondary terminals M6

Indoor service
Mark A

Secondary terminals M5 (max. 9)


Secondary terminals M6
131 Outdoor service
Mark B

PG 16
107

Ø1
90
289

5
Ø8
125

M8
= =
171
205
170
= = 11
Ø
=
=

90
60
=

= =
200

CHARACTERISTICS

ONE SECONDARY TWO SECONDARIES

Primary
current METERING PROTECTION METERING + PROTECTION
A
100 5 VA CL1 5 VA 5P20
150 15 VA CL1 10 VA 5P20 5 VA CL1 + 5 VA 5P20
200 7.5 VA CL0.5 12.5 VA 5P20 15 VA CL1 + 7.5 VA 5P20
300 30 VA CL0.5 20 VA 5P20 15 VA CL0.5 + 10 VA 5P20
400 15 VA CL0.2 25 VA 5P20 7.5 VA CL0.2 + 10 VA 5P20
500 30 VA CL0.2 30 VA 5P20 15 VA CL0.2 + 15 VA 5P20
700 20 VA CL0.2 45 VA 5P20 10 VA CL0.2S + 20 VA 5P20
1,000 60 VA CL0.2 65 VA 5P20 25 VA CL0.2S + 25 VA 5P20
2,000 400 VA CL0.2 100 VA 5P20 100 VA CL0.2S + 50 VA 5P20

Instrument transformers | Low voltage 15


1. CURRENT TRANSFORMERS > Metering and protection > Indoor / Outdoor

IFH-5
Secondary terminals M6 (max. 6)

Indoor
45

service
PG 16

Secondary terminals M6 (max. 6)


Outdoor
service
57.5

PG 16
Ø 15
137.5
352

Ø 250
D

257
Ø
157

M8
On request = =
170

170
= =
11
Ø

› IFH-5. Side mounting


=
= =

on request installation
90
60

horizontal or vertical.
=

= =
200

CHARACTERISTICS
ONE SECONDARY TWO SECONDARIES
Inner diameter Inner diameter Inner diameter Inner diameter Inner diameter
(ØD= 100 mm) (ØD= 130 mm) (ØD= 145 mm) (ØD= 100 mm) (ØD= 130 mm)

Primary
PROTECTION METERING + PROTECTION
current A
200 20 VA 5P20 12.5 VA 5P20 5 VA 5P20 10 VA CL3 + 1 ÷ 10 VA 5P20 7.5 VA CL1 + 7.5 VA 5P20
250 25 VA 5P20 15 VA 5P20 7.5 VA 5P20 15 VA CL1 + 15 VA 5P20 15 VA CL1 + 10 VA 5P20
300 30 VA 10P20 20 VA 5P20 10 VA 5P20 10 VA CL0.5 + 15 VA 5P20 5 VA CL0.5 + 10 VA 5P20
500 45 VA 10P20 30 VA 5P20 15 VA 5P20 25 VA CL0.5 + 25 VA 5P20 20 VA CL0.5 + 20 VA 5P20
750 50 VA 10P20 50 VA 5P20 25 VA 5P20 30 VA CL0.5 + 30 VA 5P20 25 VA CL0.5 + 30 VA 5P20
1,000 50 VA 10P20 50 VA 5P20 30 VA 5P20 30 VA CL0.5 + 40 VA 5P20 30 VA CL0.5 + 40 VA 5P20
2,000 50 VA 10P20 50 VA 5P20 50 VA 5P20 30 VA CL0.5 + 40 VA 5P20 30 VA CL0.5 + 40 VA 5P20
3,000 50 VA 10P20 50 VA 5P20 50 VA 5P20 30 VA CL0.5 + 40 VA 5P20 30 VA CL0.5 + 40 VA 5P20
6,000 45 VA 5P20

DIMENSIONS

Mark D (±1.5) Service


A 100
Outdoor
B 130
C 100
Indoor
D 130
E 145 Outdoor
F 145 Indoor

16 Instrument transformers | Low voltage


1. CURRENT TRANSFORMERS > Metering and protection > Indoor / Outdoor

IFH-7
5
Ø1

70
ØD Ø2
220

200
H

Secondary terminals
M6 (max. 6)

PG 21
15

PG 21
(on request)

CHARACTERISTICS DIMENSIONS

Primary Weight
Mark PROTECTION PROTECTION Mark H D
current A (kg)
100 15 VA 5P10 7.5 VA 5P20 1 166 40
200 30 VA 5P10 15 VA 5P20 2 231 55
100
1 300 50 VA 5P10 20 VA 5P20 3 296 75
400 60 VA 5P10 30 VA 5P20 4 361 90
500 75 VA 5P10 40 VA 5P20
50 7.5 VA 5P10 2.5 VA 5P20
75 15 VA 5P10 5 VA 5P20
100 25 VA 5P10 10 VA 5P20
150 40 VA 5P10 15 VA 5P20
2
250 60 VA 5P10 30 VA 5P20
300 70 VA 5P10 35 VA 5P20
600 100 VA 5P10 60 VA 5P20
1,000 100 VA 5P10 100 VA 5P20
50 10 VA 5P10 5 VA 5P20
100 30 VA 5P10 15 VA 5P20
3
200 60 VA 5P10 30 VA 5P20
300 100 VA 5P10 50 VA 5P20
50 15 VA 5P10 7.5 VA 5P20
4 100 40 VA 5P10 20 VA 5P20
150 60 VA 5P10 30 VA 5P20

Instrument transformers | Low voltage 17


1. CURRENT TRANSFORMERS > Metering and protection > Indoor / Outdoor

IFH-10
Secondary terminals M6 (max. 6)
115

PG 16
0
29

0
Ø 45
562
Ø

255

M8
5
9
Ø
=

110
90

CHARACTERISTICS
=

ONE SECONDARY TWO SECONDARIES


= =
195 Primary
220 current METERING PROTECTION METERING + PROTECTION
A
4,000
5,000
6,000 30 VA CL0.5 30 VA 5P20 30 VA CL0.5 + 30 VA 5P20
8,000
10,000

18 Instrument transformers | Low voltage


1. CURRENT TRANSFORMERS > Metering and protection > Indoor / Outdoor

IFH-12
Outdoor service
Mark A 168
Ø
53

Z 1:5
4

0
30
Ø

626
572
294

M8 8

Indoor service
Mark B

Outdoor service
Mark C

20
168
617

10

564 45

M8
Indoor service
Mark D

M6
14
Ø
=

10 45
564
188

218
=

719

669
= =

470

500
600
650

CHARACTERISTICS
ONE SECONDARY TWO SECONDARIES
Primary
METERING PROTECTION METERING + PROTECTION
current A
4,000
5,000
6,,000 50 VA CL0.5 50 VA 5P20 50 VA CL0.5 + 50 VA 5P20
8000
10,000

Instrument transformers | Low voltage 19


1. CURRENT TRANSFORMERS > Protection. Split-core > Indoor / Outdoor

BAT Secondary
terminals M6 Metallic cover

S1 S2

0 PG 16
156

27
Ø

DIMENSIONS
Mark D
Ø A 130
D
B 180
155

P1 CHARACTERISTICS
4

Mark A Mark B
200
Primary
170 METERING PROTECTION METERING PROTECTION
= = current A

200 5 VA 10P10 2.5 VA 10P10


R7 300 2.5 VA CL1 12,5 VA 10P10 2 VA 10P20
TORQUE
PAR DE APRIETE

95
0.5 Kg.m

400 5 VA CL1 5 VA 5P20 2 VA CL1 2 VA 5P20


600 5 VA CL0,5 15 VA 5P20 5 VA CL1 5 VA 5P20
800 7,5 VA CL0.5 25 VA 5P20 2.5 VA CL0.5 7 VA 5P20
1,000 15 VA CL0.5 30 VA 5P20 5 VA CL0.5 7.5 VA 5P20
318
1,200 25 VA CL0.5 35 VA 5P20 7.5 VA CL0.5 10 VA 5P20
1,500 45 VA CL0.5 45 VA 5P20 12.5 VA CL0.5 12.5 VA 5P20
1,800 75 VA CL0.5 55 VA 5P20 25 VA CL0.5 15 VA 5P20
2,000 100 VA CL0.5 65 VA 5P20 50 VA CL0.5 15 VA 5P20

BAR
Secondary terminals M6

Metalic cover
112

0
19
Ø

PG 16

Ø
10
5
110

P1
4

200
CHARACTERISTICS
230
Primary
170 METERING PROTECTION
current A
200 4 VA 10P10
300 2 VA 10P20
R7 400 2 VA CL1 2 VA 5P20
TORQUE
PAR DE APRIETE

500 5 VA CL1 4 VA 5P20


80
50

95
0.5 Kg.m

600 7.5 VA CL1 5 VA 5P20


800 3 VA CL0.5 7 VA 5P20
1,000 7.5 VA CL0.5 7.5 VA 5P20

20 Instrument transformers | Low voltage


1. CURRENT TRANSFORMERS > Protection. Split-core > Indoor / Outdoor

BAS
Secondary terminals M6

Metalic cover

S1 S2

0
19
Ø
113

DIMENSIONS
D
111

P1 Mark D
A 70
B 105
4

200
170
85 85 CHARACTERISTICS
= =
Mark A Mark B
Primary
METERING PROTECTION METERING PROTECTION
current A
TORQUE
PAR DE APRIETE

150 5 VA 10P10
0.5 Kg.m

R7

200 7.5 VA 10P20 3 VA 10P20


150
80
50

300 10 VA CL1 12.5 VA 10P20 5 VA 10P20


400 5 VA CL0.5 15 VA 5P20 4 VA CL1 7.5 VA 5P20
500 12.5 VA CL0.5 20 VA 5P20 12.5 VA CL1 8 VA 5P20
600 20 VA CL0.5 30 VA 5P20 15 VA CL1 10 VA 5P20
800 7.5 VA CL0.5 12.5 VA 5P20
230 1,000 25 VA CL0.5 15 VA 5P20

Instrument transformers | Low voltage 21


1. CURRENT TRANSFORMERS > Homopolar > Indoor / Outdoor

BAR
Secondary terminals M6

Metalic cover
112

0
19
Ø
PG 16

Ø
10
5
110

P1
4

200

230
170 CHARACTERISTICS

Ratio A Characteristics
Burden: 0.1 Oh. Error: at 0.05 In ±15%
20/1 at In ±10%
TORQUE
PAR DE APRIETE

at 10 In ±15%
80
50

95
0.5 Kg.m

Burden: 0.3 Oh. Error: at 0.05 In ±15%


20/1 at In ±10%
at 5 In ±15%
Burden: 0.1 Oh. Error: at 0.05 In ±15%
30/1 at In ±10%
at 10 In ±15%
Burden: 0.3 Oh. Error: at 0.05 In ±15%
30/1 at In ±10%
at 5 In ±15%
Burden: 0.2 Oh. Error: at 0.05 In ±15%
50/1 at In ±10%
at 10 In ±15%
Burden: 1 and 1.5 Oh. Error: at 0.05 In ±15%
50/1 at In ±10%
at 10 In ±15%

Customized solutions for


any requirement.

22 Instrument transformers | Low voltage


1. CURRENT TRANSFORMERS > Homopolar > Indoor / Outdoor

IFH-3
Secondary terminals M6 (max. 6)

Indoor service
45

Mark A
PG 16

Secondary terminals M6 (max. 6)

Outdoor service
PG 16
57.5

Mark B

M8 (on request)
P1
121.5
323

0
110 Ø 22
Ø

290
Ø 90°

Ø1
50
144

Ø 45
° M8 CHARACTERISTICS

Ratio A Characteristics
Burden: 0.1 Oh. Error: at 0.05 In ±15%
= = 10/1 at In ±10%
20 115 at 10 In ±15%
170
= = Burden: 0.1 and 0.3 Oh. Error: at 0.05 In ±15%
11

20/1 at In ±10%
Ø

at 10 In ±15%
=

Burden: 0.1 Oh. Error: at 0.05 In ±15%


=
60

90

30/1 at In ±10%
=

at 5 In ±15%
=

Burden: 1 Oh. Error: at 0.05 In ±15%


= = 50/1 at In ±10%
200 at 10 In ±15%
Burden: 1 Oh. Error: at 0.05 In ±15%
60/1 at In ±10%

ICO-3 at 10 In ±15%
57

TRANSFORMADOR DE INTENSIDAD
TIPO $01____ N° $02______ $03_
42

I.pn $05___________________
Kn=
I.sn $06__ $07__ $08__
BORN. $10__ $11__ $12__
VA $14__ $15__ $16__ KV $32____
CL $18__ $19__ $20__ Hz $33____
MADE EXT.% $22__ $23__ $24__ I.ter. $34 KA$35 S
IN
SPAIN Fs $26__ $27__ $28__ I.din. $36__ KA

180
150
= =
20

P1
R9

CHARACTERISTICS
R4
5

Ratio A Characteristics
Burden: 0.1 Oh. Error: at 0.01 In ±15%
20/1 at In ±10%
at 10 In ±15%
Burden: 0.1 Oh. Error: at 0.05 In ±15%
165

30/1 at In ±10%
at 5 In ±15%
470
510

310

Burden: 0.1 Oh. Error: at 0.05 In ±15%


50/1 at In ±10%
at 10 In ±15%
Burden: 0.1 Oh. Error: at 0.05 In ±15%
60/1 at In ±10%
145

at 10 In ±15%
Burden: 0.1 Oh. Error: at 0.05 In ±15%
100/1 at In ±10%
at 10 In ±15%
R4
5

0
R9
1
Ø1
20

Instrument transformers | Low voltage 23


1. CURRENT TRANSFORMERS > Bushing CT > Indoor

BUSHING CT
Window type current transformers, bushing type, for installation
in power transformers, dead tank circuit breakers or Gas Insulated
Switchgears (GIS). They are custom made designed based on the
each project requirements.

1. CURRENT TRANSFORMERS > Auxiliary > Indoor

IRM
B
A

C
6

M
F
G
D
N
H

Secondary terminals max.


2 of M10 or 5 of M4
K
E

Secondary terminals
max. 5 of M4

CHARACTERISTICS

Maximum
Type METERING PROTECTION A B C D E F G H I J M N
current (A)
Up to 15 A 30 VA CL0.5 10 VA 10P20 143 10 135
IRM-2 80 102 112 108 5 90 72 90 M4
From 15 to 100 A 60 VA CL1 10 VA 5P20 163 30 155

Up to 15 A 45 VA CL0.5 25 VA 10P20 157 10 150


IRM-3 95 119 135 126 105 83 104
From 15 to 100 A 90 VA CL1 20 VA 5P20 177 30 170

Up to 15 A 75 VA CL0.5 45 VA 1OP30 197 10 190


IRM-4 7 M6
From 15 to 100 A 150 VA CL1 45 VA 5P20 217 30 210
120 136 152 150 125 100 125
Up to 15 A 100 VA CL0.5 60 VA 5P20 217 10 210
IRM-5
From 15 to 100 A 100 VA CL0.5 60 VA 5P20 237 30 230

24 Instrument transformers | Low voltage


VOLTAGE TRANSFORMERS
Resin-cast low voltage transformers for ADVANTAGES
measuring and protection.
› Transformer can be assembled in any
RANGE position.
› Auxiliary services can be supplied.
› Insulation level 0.72 kV.
› Frequencies: 50 Hz, 60 Hz.

APPLICATIONS

› Low voltage panel.

1. VOLTAGE TRANSFORMERS > Metering and protection > Indoor

URC
R Terminals M4
G
C

M
F

A
D
H
B
E

DIMENSIONS
Burden VA Weight
Primary
A B C D E F G H I J M
current A Class 0.5 Class 1 Thermal (kg)
URC-52 15 45 200 108 90 111 80 102 117 5 90 72
112
URC-71 25 60 300 113 120
104 M4
URC-72 30 70 450 126 95 127 105 83
120 119 135
URC-80 10 20 6.2 105 128
URC-91 75 150 600 131 138 7
URC-92 150 300 900 161 168
150 125 120 136 152 125 100 M6
URC-93 200 400 1,300 181 188
URC-100 30 70 13.5 161 169

Instrument transformers | Low voltage 25


2. INSULATORS & WALL BUSHINGS
Support insulators
Signal insulators
Signalling box
Wall bushings

26 Instrument transformers | Low voltage


2. INSULATORS AND WALL BUSHINGS > Support insulators > Indoor

AR
70 View from X
X
M10
46
M16
Pe
15
24

f
H

t1 8 6.5
10

d2
d1
D

CHARACTERISTICS AND DIMENSIONS

Highest Rated insulation level Minimum


Weight Ø
system breaking No Creepage H
Type Lightning Máx. d1 d2 t1 f
voltage Power stress sheeds (kg) distance (±0.5)
Impulse P (kg) D
kV (BIL) kV frequency kV

AR-8-60 7.2 60 80 3 0.7 200 95 56 M16


26 35
AR-8-75 12 75 4 0.98 272 130 64 M16
38
AR-8-95 17.5 95 800 6 1.37 340 175 100 69 M20 35
45
AR-8-125 24 125 50 7 1.65 397 210 74 M20 45
AR-8-170 36 170 70 11 2.57 555 300 84 M24 51 60

Instrument transformers | Low voltage 27


2. INSULATORS AND WALL BUSHINGS > Signal insulators > Indoor

ARC
B Ø 70 36
View from B
M12
M6
Minimum failing load:
4000 Newton
24
B
24
H

f
View from A
A

M16
10

C d1
M4
Ø 100
A

CHARACTERISTICS AND DIMENSIONS

Highest system Lightning Power


kV kV Height Creepage H
Type voltage Impulse frequency d1 f A B ØC
min. max. (kg) distance (±0.5)
kV (BIL) kV kV
ARC-8-40 3.6 40 10 1.2 3.6
ARC-8-60 7.2 60 20 2.4 7.2 0.98 272 130 64 23 26 12
ARC-8-75 12 75 28 4 12
16
ARC-8-95 17.5 95 38 5.8 17.5
1.65 397 210 74
ARC-8-125 24 125 50 8 24 28 28 10
ARC-8-170 36 170 70 12 36 2.60 555 300 84

2. INSULATORS AND WALL BUSHINGS > Signalling box > Indoor

LAF-1
110
2 1 100

Pe
41

.5
Ø4
Die-cast
74
82
41

120 58 12
110
70

LAF-1 Application

R S T 1 - Test light
2 - Fixed warning block
3
3 - Insulators

LAF-1

Assembly sketch

28 Instrument transformers | Low voltage


ARTECHE transformers
are installed in over 150
countries.

Instrument transformers | Low voltage 29


2. INSULATORS AND WALL BUSHINGS > Bushings > Indoor

PRU - PRP

› PRU › PRP
Ød
ØC
B

B
H

H
A
10

ØJ A
10

ØK
ØJ

ØD

ØC
ØD

50
G

E
F

Detail (striped) E
Useful zone to place F
conductor elements Detail (striped)
Useful zone to place
conductor elements

ØS
Ø 180
120

CHARACTERISTICS AND DIMENSIONS

Highest Lightning
system Impulse Bars Current Weight
Type A B C D d E F G H J K S T
voltage (BIL) max. max. (kg)
kV kV

PRU-12/75 60 2.3 115 115 68 160 200 160 120 65 20


12 75 255 110 15 M10
1,000
PRU-12/115 100 3.5 160 160 110 205 250 200 165 105 40

PRU-24/115 24 125 100 9 425 200 185 185 110 230 280 210 24 M12 190 105 40
2,500
PRP-36 36 170 120 32.5 560 275 220 220 120 250 300 300 25 20 257

30 Instrument transformers | Low voltage


2. INSULATORS AND WALL BUSHINGS > Bushings > Indoor

PBD
PBD-17 PBD-24

Ø 275

192
115
34

360
215
230

8
115

Ø 352
380
325
162.5 162.5
355
310
5.5
28

105

R 191
Ø

M8
ØD
276
210
P1

0
15

355
310
120
Ø
P1
105

DIMENSIONS
M8
Weight
Type Mark ØD
(kg)
210 190
400 181 A 100
14

Screw at screen PBD-17 25


Screw at screen 256
potential
B 130
potential PBD-24 45

PBE
8
B
A

405
360

ØC

ØD
360
405
140
P1

22
Ø4

DIMENSIONS
M8
Type A B C D
14

PBE-12 255 550 227 275


290.5 Screw at screen potential PBE-24 230 500 225 200

Instrument transformers | Low voltage 31


2. INSULATORS AND WALL BUSHINGS > Bushings > Indoor

PPL
A
230
B B 0
= =
M12 26
Ø

155

=
260
365

=
210
P1
C

Ø
16
12 25 280
E F G H
D

Mark D Mark E Mark G


(Option) Only PPL-72 (On request)
(Option)
20 40 40 130
Ø 50

120 120
30
16
40
Ø 50

1510

20 40 40 DIMENSIONS

Type A B C D E F G H I
30

120 PPL-12 706 353 442 38.5 38.5 706


157.5 207.5
16
40
Ø 50

130 PPL-36 34 716 175.5 175.5 975


Ø

I I PPL-72 1,270 451 159 209 451 1,530

The innovation undertaken


by ARTECHE in instrument
transformers during the
late years have made
them more efficient, with
compact designs for an
easiier transport, store, and
d
installation and to minimize
their visual impact.

32 Instrument transformers | Low voltage


2. INSULATORS AND WALL BUSHINGS > Bushings > Outdoor

PPE-36
DIMENSIONS

Type Mark ØD E max L


With primary A 320 1,412
terminal B 400 1,492
A 320 1,125
125
Without primary B 400 1,205
terminal C 320 1,125
210
D 400 1, 205

With primary terminal Without primary terminal


L L
460 E max
605 E max
50

Ø 363
Ø 363
ØInt. 210

ØInt. 210

Ø 530 Ø 530

Ø 500 Ø 500

Ø 14 Ø 14

ØD

N° TIPO/TYPE

AÑO/YEAR
PESO/WEIGHT

$16___

25 44,5
Ø
14
,25
100
44,5

128

Aluminium

Instrument transformers | Low voltage 33


3. MANUFACTURING AND
TECHNOLOGY
With 65 years of experience, ARTECHE
guarantees the performance of its
transformers regardless of altitude,
weather, seismic or environmental
conditions.

34 Instrument transformers | Low voltage


MANUFACTURING AND TECHNOLOGY
› Equipment undergoing a continuous
innovation process including:
computerized systems for transformer
calculation, analysis of the distribution
of the electric field by FEM, automatic
winding machines, casting in epoxy
resin or polyurethane by gravity in
vacuum tanks or pressurized gelification,
controlled polymerization in large ovens.
› Own laboratories with modern equipment,
approved for any routine or type test,
either for new developments or for specific
requirements from our customers in power
generation, transmission, distribution or
industry.
› Approved in laboratories belonging to the
International Metrology Committee: PTB
(Germany), L.C.O.E (Spain), GOST (Russia),
BEV (Austria), GUM (Poland) etc.
› Large production capacity of more than
50,000 units per year in medium voltage
and an almost unlimited number of
devices in low voltage, insulators and wall
bushings. This capacity allows us to give a
quick answer to any requirement.
ARTECHE Group makes
› Flexible designs, adapted to any a strong commitment to
specification, as a result of our strong
engineering team located in all our
innovation (R+D+i) with an
production facilities. investment of 3,3% from
› M a x i m u m s a f e t y w i t h re s i n - c a s t
2013 turnover.
transformers in which the core and the
winding form a compact block. The resin
acts as a dielectric support, protective
casing and thermal conductor for the
transformer.
› Equipment compliant to any international
or domestic standard: IEC, IEEE, UNE, BS,
VDE, SS, CAN, AS, UL, NBR, JIS, GOST,
NF, etc.

› Physical and chemical


laboratories conduct
over 130 tests to certify
the quality of raw
materials.

Instrument transformers | Low voltage 35


4. QUALITY & ENVIRONMENT

Exceeding environmental regulations,


ARTECHE has been able to minimize
the use off hazardous materials, energy
consumption and waste generation.

36 Instrument transformers | Low voltage


QUALITY & ENVIRONMENT
Everyone in the ARTECHE Group works under
the criteria set out in our environmental and
quality policy.

A sum of regulated procedures based on


communication, teamwork, prevention
analysis and continuous improvement,
common to the whole organization.

› Advanced sustainability criteria in


production and in the creation and
development of new products.
› Compact designs, manufactured with
minimal energy consumption and
enviromental-friendly materials.
› Internal and external skill motivation
programs.
› Advanced development of knowledge
management.
› Quality agreements with utilities.
› Physico-chemical and electrical
laboratories for testing under any
International Standard.
› Type test reports issued by KEMA, CESI, ARTECHE’s financial and
LAPEM, RENARDIÈRES, etc. technological independence
› Final testing according to specific
customer requirements. gives a privileged position
› Approvals in more than 100 electricity ahead of the challenges in
companies.
› ISO 14001:2004.
the sector.
› ISO 9001:2008.
› OHSAS 18001:2007.

Instrument transformers | Low voltage 37


5. SERVICE

Over 70 technical/sales service


centers with real knowledge about
each customer provide fast and
close service.

38 Instrument transformers | Low voltage


SERVICE
› ARTECHE’s service is based on a close
relationship with the customers, reflected
in the integrated post-sale assistance plan
and structured client opinion system.
› In addition to ensuring rapid response,
ARTECHE developed a continuous service
improvement plan, which sustains an
extensive training program with courses,
publications, conferences, etc.
› ARTECHE’s focus on service, with a
broad experience leading us to be
an active participant in the electrical
organizations such as: IEC, IEEE, CIGRE,
CIRED, ASINEL, etc.
› ARTECHE has production facilities on four
continents (North America, South America,
Europe, Asia and Australia) and more than
70 technical/commercial offices. Thus
ARTECHE provides effective responses
to the requirements of any customer and
situation, based on the global knowledge
acquired.
ARTECHE has the
technology and capabilities
of instrument transformers.
Thus we provide the best
solution available in the
market.

› The solutions
ARTECHE has
developed and
expanded upon have
made it a major player
participating in the
most significant events
and workgroups in the
electricity sector.

Instrument transformers | Low voltage 39


ARTECHE_CT_trfLV_EN
Version: B0
www.arteche.com ©ARTECHE

Вам также может понравиться