Committee Statement
1 of 11 3/6/2014 9:29 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Committee Statement
Committee The sentences proposed to be deleted in the definitions are not part of the definition but are an
Statement: explanation which should be placed either in the annex (as recommended in public comments # 3
through 6) or in a separate part of the standard. Definitions are not enforceable and requirements or
additional information should be placed out side the definitions area.A list of discharge devices was
added to the revised single sentence definition.
2 of 11 3/6/2014 9:29 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Response
Message:
Public Comment No. 2-NFPA 16-2013 [Section No. 3.3.6]
3 of 11 3/6/2014 9:29 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Committee Statement
4 of 11 3/6/2014 9:29 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
5.11.2
Unless required by other standards or product listings, strainers shall be required only where there are
discharge orifices that are 3 ⁄8 in. (10 mm) or smaller.
Committee Statement
Committee This section was addressing the protection of the concentrate pump. In reviewing this section,
Statement: the TC realized the pump is not within the scope of this TC, therefore this section is being
deleted.
Response
Message:
Public Comment No. 8-NFPA 16-2013 [Section No. 5.11.2]
5 of 11 3/6/2014 9:29 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Committee Statement
Committee The sentences proposed to be deleted from the definitions in public comment # 2 are not part of
Statement: the definition but are an explanation which should be placed either in the annex (as recommended
in public comment # 3) or in a separate part of the standard. Definitions are not enforceable and
requirements or additional information should be placed out side the definitions area.
Response
Message:
Public Comment No. 3-NFPA 16-2013 [Section No. A.3.3.6]
6 of 11 3/6/2014 9:29 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
The normal direction of discharge from foam-water sprinklers is downward. To provide a choice in
installation design, foam-water sprinklers are produced for installation in the upright position and in the
pendent position with the pattern of discharge in either case in the downward direction. Sprinkler
deflectors are formed to produce the required discharge pattern, which could mean differing shapes of
deflectors for each of the two positions of installation. The variation in the shape of deflectors is illustrated
in Figure A.3.3.6.1 .
When the valve in a foam-water deluge system opens, water flows into the piping system and discharges
from all discharge devices attached thereto.
Figure A.3.3.6.1 Variations in Deflector Shape.
7 of 11 3/6/2014 9:29 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
City:
State:
Zip:
Submittal Date: Tue Mar 04 12:00:14 EST 2014
Committee Statement
Committee The sentences proposed to be deleted from the definitions in public comment # 2 are not part of
Statement: the definition but are an explanation which should be placed either in the annex (as recommended
in public comment # 4) or in a separate part of the standard. Definitions are not enforceable and
requirements or additional information should be placed out side the definitions area.
Response
Message:
Public Comment No. 4-NFPA 16-2013 [Section No. A.3.3.6.1]
8 of 11 3/6/2014 9:29 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Committee Statement
Committee The sentences proposed to be deleted from the definitions in public comment # 2 are not part of
Statement: the definition but are an explanation which should be placed either in the annex (as recommended
in public comment # 5) or in a separate part of the standard. Definitions are not enforceable and
requirements or additional information should be placed out side the definitions area.
Response
Message:
Public Comment No. 5-NFPA 16-2013 [Section No. A.3.3.6.2]
9 of 11 3/6/2014 9:29 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Committee Statement
Committee The sentences proposed to be deleted from the definitions in public comment # 2 are not part of
Statement: the definition but are an explanation which should be placed either in the annex (as recommended
in public comment # 6) or in a separate part of the standard. Definitions are not enforceable and
requirements or additional information should be placed out side the definitions area.
Response
Message:
Public Comment No. 6-NFPA 16-2013 [Section No. A.3.3.6.3]
10 of 11 3/6/2014 9:29 AM
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Committee Statement
11 of 11 3/6/2014 9:29 AM