Вы находитесь на странице: 1из 13

Ain Shams Engineering Journal (2014) 5, 775–787

Ain Shams University

Ain Shams Engineering Journal


www.elsevier.com/locate/asej
www.sciencedirect.com

ELECTRICAL ENGINEERING

UPFC with series and shunt FACTS controllers


for the economic operation of a power
system
Biplab Bhattacharyya *, Vikash Kumar Gupta, Sanjay Kumar

Department of Electrical Engineering, Indian School of Mines, Dhanbad 826004, India

Received 1 February 2014; revised 14 March 2014; accepted 31 March 2014


Available online 15 May 2014

KEYWORDS Abstract This paper presents the application of Genetic Algorithm (GA) and Differential Evolu-
FACTS devices; tion (DE) technique for the minimization of transmission loss and simultaneous reduction in the
Operating cost; operating cost of the system using Flexible AC Transmission System (FACTS) devices. Three types
Optimal power flow; of FACTS devices, Thyristor Controlled Series Compensator (TCSC), Static VAR Compensator
Transmission loss; (SVC) and Unified Power Flow Controller (UPFC) are considered for this purpose. Optimal place-
Genetic Algorithm; ment of FACTS devices in the heavily loaded power system reduces transmission loss, control reac-
Differential Evolution tive power flow, improves voltage profile of all nodes and also reduces operating cost. The system is
reactively loaded starting from base to 200% of base reactive load and the system performance is
observed without and with FACTS devices. The proposed technique is applied on IEEE 30-bus sys-
tem for the optimal setting of FACTS devices. Finally, how system performance is improved with
the use of UPFC along with other series and shunt FACTS controller is illustrated.
 2014 Production and hosting by Elsevier B.V. on behalf of Ain Shams University.

1. Introduction be continuously expanded and upgraded to cater the ever


growing power demand. Increase in power demand, restriction
Modern power systems are prone to widespread failures due to on the construction of new lines, unscheduled power flow in
increase in power demand, so power system engineers are cur- lines create congestion in the transmission network and
rently facing challenges to improve power transfer capability increase in transmission loss. Power flow through an ac trans-
of the existing transmission system. Power systems need to mission line is a function of line impedance, the magnitude and
the phase angle between the sending end and the receiving end
voltages. Optimal power flow problem is of nonlinear and
* Corresponding author. Tel.: +91 9431711085.
nonconvex in nature and used widely for power system
E-mail addresses: biplabrec@yahoo.com (B. Bhattacharyya),
vikash1146@gmail.com (V.K. Gupta), sanjayism2012@gmail.com
planning and operation. Effective control of reactive power
(S. Kumar). compensation on weak nodes improves voltage profile, reduces
Peer review under responsibility of Ain Shams University. power loss and improves both steady state and dynamic
performance of the system. With the development of power
electronics it is possible to design power electronic equipment
of higher rating for high voltage systems. This actually led to
Production and hosting by Elsevier
the introduction of Flexible AC Transmission System
2090-4479  2014 Production and hosting by Elsevier B.V. on behalf of Ain Shams University.
http://dx.doi.org/10.1016/j.asej.2014.03.013
776 B. Bhattacharyya et al.

Nomenclature

i, j node i & node j Qgi existing nodal reactive capacity at node i


Xij reactance of the transmission line Vi, Vj voltage of ith and jth bus
Xij(new) reactance of transmission line with TCSC Pij, Qij active and reactive power flow between ith & jth
XTCSC reactance of the TCSC bus.
CF(TCSC) cost function of TCSC in $/kVar Pji, Qji active and reactive power flow between jth & ith
CF(SVC) cost function of SVC in $/kVar bus
CF(UPFC) cost function of UPFC in $/kVar N number of lines
TCSCvalue, SVCvalue & UPFCvalue operating value of G0ij , B0ij real and imaginary components of bus admit-
FACTS devices tance matrix
CTotalCost total operating cost of the system dij phase angle between ith & jth bus.
CEnergy cost due to energy loss Si, Sj total power injected at bus i & bus j by UPFC
CFacts investment cost of the FACTS devices Pi, Qi active and reactive power injected by UPFC at
Pmin
ni ; Pmax
ni minimum and maximum limit of nodal active ith bus
power in the ith bus Pj, Qj active and reactive power injected by UPFC at
Qmin max
ni ; Qni minimum and maximum limit of nodal reactive jth bus
power in the ith bus Vs supply voltage by UPFC
Pni ; Qni nodal active and reactive power output of the øs phase angle of supply voltage Vs
ith bus hi, hj phase angle of voltages Vi and Vj
Vmin
i ; Vi
max
minimum and maximum limit of voltage magni- Iq reactive component of current
tude at ith bus
Vi voltage magnitude at bus i
Qmin max
gi ; Qgi minimum and maximum limit of existing nodal
reactive capacity in the ith bus

(FACTS) controllers such as Thyristor Controlled Series Com- voltage stability improvement. An improved evolutionary
pensators (TCSC), Unified Power Flow Controllers (UPFC) programming (IEP) technique to solve the optimal reactive
and Static Var Compensator (SVC). The concept of FACTS power dispatch (ORPD) problem is discussed in [12,13]. In
was first introduced by Hingorani in [1]. These devices not only [14] author has presented enhanced Genetic Algorithm for
have the capability in controlling active and reactive power the solution of optimal power flow with both continuous and
flow in an electrical network but also can redistribute power discrete control variables. FACTS devices are used in [15]
flow even under highly loaded condition that ultimately have for the improvement of available transfer capacity (ATC) dur-
the effect in reducing overall congestion. Hence FACTS con- ing normal as well as contingency situations using real-coded
trollers can be used to increase system loadability as situation GA. Jerbex et al. [16] provide an idea for the optimal alloca-
demands. Steady state and transient stability is also improved tions of FACTS devices, without considering the investment
with the help of FACTS controller. TCSC is a series connected cost of FACTS device. Das et al. [17] applied GA for the opti-
devices used in power systems to control the reactance of a mum value of fixed and switched shunt capacitors in minimiz-
transmission line thereby controls line power flow in one ing energy loss and in maintaining acceptable voltage profile at
way. SVC is a shunt connected device which regulates the volt- load buses under different loading conditions on a radial dis-
age of transmission system at a selected terminal by controlling tribution network. In [18] GA is used for the optimal power
reactive injections. UPFC is a combination of a static synchro- flow solution for a six bus system. Graphical user interface
nous compensator (STATCOM) and a static synchronous (GUI) based on GA is used in [19] for the determination of
series compensator (SSSC) coupled via a common DC voltage optimal positions and magnitudes of multi-type FACTS
link used for controlling active and reactive power flow devices in large power systems in minimizing active power loss
through the lines. It also has direct impact in controlling volt- of the system. Multi-objective problem of a power system is
age. Reactive power flow control by FACTS devices to solved by proper allocation of series and shunt FACTS con-
increase transmission capacity is discussed in [2]. Optimal troller in [20]. Basu et al. [21] proposed DE algorithm for the
placement of FACTS devices increases the power transfer limit minimization of generator fuel cost using FACTS devices.
in the system as discussed in [3–5]. Minimization of transmis- Verma et al. [22] used UPFC at the suitable locations of a
sion loss and improvement of voltage profile with the help of connected power network for congestion management.
FACTS controller is presented in [6]. Linear programming Determination of optimal position and sizing of UPFC for
(LP) optimization methodology is discussed in [7] for the reac- congestion management of transmission network is presented
tive power control in hybrid power system. Optimal power in [23]. Optimal setting of UPFC devices to minimize the total
flow along with the power injection model of FACTS devices operating cost is discussed in [24]. Determination of optimal
is the main issues of [8,9]. Linear programming approach is locations of UPFC for enhancing the security of an intercon-
used in [10] for optimum reactive power dispatch. An algo- nected power system under single line contingency by using
rithm that includes reactive power pricing concept is presented evolutionary algorithmic approach was the main motto of
in [11] for the minimization of active power loss as well as [25,26]. Performance analysis of different FACTS devices for
UPFC with series and shunt FACTS controllers for the economic operation of a power system 777

the static voltage stability enhancement is the main theme of


[27]. In [28] author has used Optimal Unified Power Flow Con-
troller (OUPFC) for minimization of real power loss as well as
total fuel cost. In [29] author has discussed system loading dis-
tribution factors and the effect after placement of UPFC in the
system load ability and operating cost.
In this paper three types of FACTS devices have been dis-
cussed namely, Thyristor Controlled Series Capacitor (TCSC),
Static Var Compensator (SVC) and Unified Power Flow Con-
troller (UPFC). It has been a rare research work where UPFC
along with both the series and shunt FACTS controllers is
used in minimizing the transmission loss problem in power sys-
tem. The main purpose of this present work is to determine the
optimal positions of the interconnected power system network Figure 2 Static model of SVC.
where the FACTS devices can be placed in such a way so that
over all transfer capacity of the system increases that ulti-
mately results minimum operating cost under different loading where Xij(new) is the reactance after the placement of TCSC; Xij
conditions. System performance is greatly affected by the type, the reactance of the transmission line and XTCSC the reactance
capacity of the FACTS controller and also the location where of the TCSC.
they are placed. TCSCs are ideal for the placement in lines
where reactive power flows are very high and the SVCs are
installed at the receiving end buses of the other lines where 2.2. Static Var Compensator (SVC)
major reactive power flows take place. Voltage magnitude
and the phase angle of the sending end buses of the lines where SVC is a shunt connected devices used to absorb reactive
major active power flow takes place are controlled by UPFC.
power from the bus or to inject reactive power to the bus where
Finally, GA and DE based algorithm is presented with
it is connected. SVC is parallel combination of capacitor and
FACTS devices and effectiveness of this technique is clearly
inductor and static model of SVC is shown in Fig. 2.
evident from the result obtained. A comparative study is made
between GA and DE approach to minimize the overall operat-
ing cost, which includes the cost, resulted due to transmission 2.3. Unified Power Flow Controller (UPFC)
loss and the investment costs of FACTS devices under differ-
ent loading conditions. The UPFC concept was proposed by Gyugyi in 1991. It is able
to control, simultaneously or selectively all the parameters
2. Static modeling of FACTS devices affecting power flow in the transmission line (i.e., voltage,
impedance and phase angle). UPFC consists of two switching
FACTS devices are composed of static equipment used to converters operated from a common DC link, as shown in
increase power transfer capability of the network. It is also Fig. 3 and power injection model of UPFC is shown in
used to minimize transmission loss and to improve the voltage Fig. 4. The working range of the UPFC angle is between
profile of the system. Static model of TCSC, SVC and UPFC is 180 and +180.
discussed below:
3. Cost functions of FACTS devices
2.1. Thyristor Controlled Series Capacitors (TCSC)
Cost functions for installation of TCSC, SVC and UPFC are
TCSC consists of series compensating capacitor shunted by taken from [30]:
thyristor controlled reactor. It is modeled as a controllable TCSC:
reactance, inserted in series with the transmission line to adjust
the line impedance and thereby control the power flow as CFðTCSCÞ ¼ 0:0015ðTCSCvalue Þ2  0:7130ðTCSCvalue Þ
shown in Fig. 1.
þ 153:75 ðUS$=kVarÞ ð2Þ
XijðnewÞ ¼ Xij  XTCSC ð1Þ
SVC:

CFðSVCÞ ¼ 0:0003ðSVCvalueÞ2 :  0:3051ðSVCvalueÞ


þ 127:38 ðUS$=kVarÞ ð3Þ
UPFC:

CFðUPFCÞ ¼ 0:0003ðUPFCvalueÞ2  0:2691ðUPFCvalueÞ


þ 188:22 ðUS$=kVarÞ ð4Þ

where TCSCvalue, SVCvalue and UPFCvalues are the operat-


Figure 1 Static model of TCSC. ing values of the FACTS devices.
778 B. Bhattacharyya et al.

Figure 3 Static model of UPFC.

system performance. The SVCs are placed at buses those are


at the finishing end of the lines carrying high reactive power.
In case II, three types of FACTS controllers namely TCSC,
SVC and UPFC are used and three positions are selected for
the optimal placement of each of these devices. UPFC’s posi-
tions are determined by identifying the lines carrying high
active power. It is observed that active power flow is very high
Figure 4 Power injection model of UPFC. in lines 6th, 7th and 4th. These lines are again connected
between buses (2, 6), (4, 6) & (3, 4) respectively. Here the volt-
age magnitude and the phase angle of the 2nd, 4th and 3rd
4. Optimal placement of FACTS devices buses are to be controlled as these are at the starting end of
the lines 6th, 7th and 4th respectively. Then TCSC’s positions
The main objective of this paper is to minimize the total oper- are selected by choosing the lines carrying high reactive power.
ating cost under different loading conditions by the installation The series reactance of the lines 15, 20 and 28 is controlled by
of FACTS devices at the optimal location in the transmission placing TCSCs in these lines. SVC s are planned to be placed in
systems. The decision where they are to be placed is largely buses 7, 17 and 21 as these buses are the weak buses where suit-
dependent on the desired effect and the characteristics of the able reactive injection can improve system performance. It can
specific system. SVCs are mainly used to provide the voltage be observed that the total number of FACTS controllers in
support at a particular bus and to inject reactive power flow case II is not same as that of number of FACTS controllers
in the adjacent lines. Power flow through the lines can also in case I. In case I, the TCSCs are placed in four lines where
be changed by modifying the line reactance with the help of as in case II, TCSCs are placed in three lines. Similarly three
TCSC. UPFCs are placed at the buses to improve the bus volt- weak buses are chosen for the placement of SVCs in case II
age of the system along with improvement in the power trans- where as four buses are considered for the placement of SVC
fer capacity of the lines. For increasing the system ability to in case I. This is done to show the clarity of advantages in
transmit power, FACTS devices are placed in such a way that using UPFC in case II.
it can also utilize the existing generating units. The reason for Finally, GA and DE based optimization algorithms are
the placement of FACTS devices in the heavily loaded line is used to minimize the objective functions with FACTS devices
that it results decrease in reactive power flow through these for both the cases along with reactive generation of generators
lines. It has an indirect effect of redistributing of additional and transformer tap positions.
power in the other sections of lines of the system in such a
manner that these lines are also not overloaded. 5. Problem formulation with FACTS devices
In the proposed method the decision for the placement of
FACTS devices in a line or at the remote end of a line is made The main objective is to find the optimal location of FACTS
on the basis of power flow in each line. We have restricted devices along with network constraints so as to minimize the
about the choice of number of FACTS devices. Here two cases total operational cost at different loading conditions. The
are considered for the optimal location and types of FACTS objective function which is to be minimized is twofold as it
devices using evolutionary techniques. In case I, only two types includes cost of energy loss and the investment cost of FACTS
of FACTS controller namely TCSCs and SVCs are used and devices. Without FACTS devices, controlling existing reactive
four locations are selected for the optimal placement of each capacities such as optimal setting of transformer tap positions,
type of these devices. TCSC’s positions are selected by choos- reactive generations of generators and proper placement of
ing the lines carrying largest reactive power. Lines 25th, 41st, Shunt Var sources at weak nodes active power loss can be min-
28th and 5th are found as the lines for TCSC placement and imized to a certain extent. But if FACTS controllers are used
simultaneously series reactance of these lines are controlled. in addition of controlling existing reactive Sources, active
Bus numbers 21st, 7th, 17th and 15th are found as the buses power loss can be reduced to a large extent. As Var generations
where suitable reactive injection by SVC can improve the of the generators and controlling transformer tap settings
UPFC with series and shunt FACTS controllers for the economic operation of a power system 779

within their defined limits do not contribute any cost to the generation in the cases of Genetic Algorithm and Differential
operating cost of the system, here in the proposed approach Evolution techniques.
setting of transformer tap positions and reactive generations
of generators are included as controlling parameters along 6. Proposed approach
with the FACTS devices.
The objective function is combinatorial. It consists of two In the present problem, Genetic Algorithm (GA) and Differen-
parts; first is the cost due to the energy loss and second is tial Evolution (DE) techniques are used to determine the
the investment cost of FACTS devices. So the optimization optimal value of the FACTS devices to be connected with
of the objective function becomes combinatorial where invest- the existing reactive power sources to maximize the system per-
ment cost of FACTS devices is to be considered while minimiz- formance whereas the location of FACTS devices is already
ing transmission loss. In other words, the objective of the determined by power flow analysis.
proposed technique is to determine the optimum operating Multi-types of FACTS devices are discussed here. TCSCs
cost under different cases of loading. are to modify reactances of some selected lines, SVCs control
So, the objective function can be written as: the reactive injection at weak buses and UPFC is connected
CTotal Cost ¼ CEnergy þ CFACTS ð5Þ at some specified buses to control Voltage, phase angle associ-
ated with these buses and impedances of the lines nearby to the
where CEnergy is the cost due to energy loss component and buses connected with UPFC. In addition transformer tap
CFACTS is the investment cost of the FACTS devices. positions along with reactive generations of the generators
The following equality and in equality constraints are to be are controlled. As a whole all these variables are to be opti-
satisfied: mized by evolutionary optimization methods. It is to be men-
The active and reactive nodal power should be within the tioned that, during evaluation of objective function with the
limits as parameters inside a string which contains FACTS devices
along with Var generation by generators and transformer tap
Pmin max
ni 6 Pni 6 Pni
setting arrangements, the modified power flow Eqs. (6)–(13)
has to be included in the load flow program.
Qmin max
ni 6 Qni 6 Qni

Again, these active and reactive nodal powers have to satisfy 6.1. Genetic algorithm in brief
voltages magnitude constraints: Vi min 6 Vi 6 Vi max .
As well as the existing nodal reactive capacity constraints: Genetic Algorithms (GAs) is an optimization algorithms based
Qmin max
gi 6 Qgi 6 Qgi . on the mechanics of natural selection and genetics. GA con-
Superscripts min, max are the minimum and maximum lim- sists of main three operators, namely, reproduction, crossover
its of the variables. and mutation. The description of GA in brief is explained
The power flow equations between the nodes i-j after incor- below:
porating TCSC and SVC would appear as Initially populations of N strings are randomly created in
such a way so that the parameter values should be within
Pij ¼ V2i G0ij  Vi Vj ðG0ij cos dij þ B0ij sin dij Þ ð6Þ their limits. Then the objective function is computed for every
individual of the population. A biased roulette wheel is cre-
Qij ¼ V2i B0ij  Vi Vj ðG0ij sin dij  B0ij cos dij Þ ð7Þ ated from the values obtained after computing the objective
function for all the individuals of the current population.
Pji ¼ V2j G0ij  Vi Vj ðG0ij cos dij  B0ij sin dij Þ ð8Þ Thereafter the usual genetic operation such as reproduction,
crossover and mutation takes place. Two individuals are ran-
Qji ¼ V2j B0ij þ Vi Vj ðG0ij sin dij þ B0ij cos dij Þ ð9Þ domly selected from the current population for reproduction.
Then Cross-over takes place with a probability close to one
If an UPFC connected between bus ith & jth, the injected (here 0.8). The crossover between two strings takes place in
power at bus ith (Si = Pi + jQi) and bus jth (Sj = Pj + jQj) such a manner that the particular type of elements (e.g.,
can be written as: TCSC, SVC, UPFC, Transformer tap setting or Reactive gen-
eration of generators) of one string cross over with the same
Pi þ V2s G0ij þ 2Vi Vs G0ij cosð/s  hi Þ  Vj Vs ½G0ij cosð/s  hj Þ type of elements of another string as shown in Fig. 5, and a
 B0ij sinð/s  hj Þ ¼ 0 ð10Þ new set of strings are produced. Then mutation operation
with specific probability (very low) takes place. After comple-
Qi  Vi Iq  Vi Vs ½G0ij sinð/s  hi Þ  B0ij cosð/s  hi Þ ¼ 0 ð11Þ tion of all genetic operations, the first generation is com-
pleted, and the second generation is about to start. In this
way, the GA is continued in order to reduce the cost of oper-
Pj  Vj Vs ½G0ij cosð/s  hj Þ þ B0ij sinð/s  hj Þ ¼ 0 ð12Þ
ation in each generation until the optimum solution is
obtained.
Qj þ Vj Vs ½G0ij sinð/s  hj Þ  B0ij cosð/s  hj Þ ¼ 0 ð13Þ

Si and Sj are the total power injection by UPFC at bus ith and 6.2. Differential evolution in brief
jth respectively. These changes in the power flow equations are
taken into consideration by appropriately modifying the Differential Evolution (DE) is a population based algorithm
admittance bus matrix for the execution of load flow in evalu- was proposed by Storn and Price (1995) to solve real-parame-
ating the objective function for each individual population of ter optimization problems. The optimization process in DE is
780 B. Bhattacharyya et al.

Figure 5 Crossover operation in GA.

Figure 6a String variables for IEEE-30 bus system with TCSC & SVC.

Figure 6b String variables for IEEE-30 bus system with TCSC, SVC & UPFC.

carried out using three basic operators: crossover, mutation the transmission network while Table 1b shows the locations
and selection. of TCSCs, SVCs and UPFCs in the transmission network.
Initial populations are created randomly that are repre- Limits of FACTS devices and other controlling parameters
sented by strings where the variables inside string are same such as transformer tap positions and reactive generation of
as that of GA. In DE each vector in the population becomes generators are shown in Table 2. Reactive power flow without
a target vector. The term vector is used for a total length of and with FACTS devices in lines considering only TCSC and
a string. Cost of a vector is determined by evaluating objective SVC is shown in Table 3 using GA and DE based approach
function with the variables inside a vector and the process is whereas Table 4 shows reactive power flow without and with
similar as that of DE technique. Each target vector is com- FACTS devices in lines considering TCSC, SVC and UPFC
bined with a donor vector and a random vector differential using GA & DE based approach for different loading condi-
in order to produce a trial vector. If the cost of the trial vector tions. Bus voltages for 200% of base reactive loading with
is less than the target, the trial vector replaces the target in the FACTS and without FACTS are shown in Table 5. Magnitude
next generation. The donor vector is selected such that its cost of control variables such as TCSCs and SVCs, along with reac-
is either less than or equal to the target vector. Mutation in DE tive generation of generators and transformer tap positions
is generally performed by generating a random value utilizing using GA and DE based algorithmic approaches are shown
a predefined probability density function. In DE the differen- in Table 6a whereas magnitude of control variables such as
tial vector, where the contributors are the target, the donor TCSCs, SVCs and UPFC, along with reactive generation of
and two other randomly selected vectors perform the muta- generators and transformer tap positions using GA and DE
tion. The objective function is calculated for all the individual based algorithmic approaches are shown in Table 6b and
of the new generation and the procedure is repeated till the Table 7 shows the comparative analysis of active power loss
final goal is achieved. and operating cost of the system without and with FACTS
String representing control variables using GA and DE is devices using GA and DE technique under different loading
shown in Figs. 6a and 6b. Flowchart of the proposed approach conditions. Here two cases are considered for the selection
is shown in Fig. 7. and optimal allocation of FACTS devices, in case I only two
type of FACTS devices (TCSC and SVC) are placed at the
locations defined as shown in Table 1a whereas in case II three
7. Results and discussions types of FACTS devices (TCSC, SVC and UPFC) are placed
as shown in Table 1b. After placement of FACTS devices reac-
The proposed GA and DE based evolutionary technique is tive power flow reduces significantly in both cases in lines using
implemented on IEEE-30 bus test system under different load- evolutionary techniques.
ing conditions. FACTS devices are placed at the optimal loca- From Table 1a, it is clear that TCSCs are placed in line
tions as discussed above and comparative analysis of the number 25, 41, 28 and 5 as at these lines reactive power flows
system performance with and without FACTS controller is are very high while SVCs are placed at buses 21, 7, 17 and 15.
made. Table 1a shows the locations of TCSCs and SVCs in After installation of FACTS devices to these lines reactive
UPFC with series and shunt FACTS controllers for the economic operation of a power system 781

Figure 7 Flowchart of the proposed approach.

Table 1a Locations of TCSC & SVC in the transmission


power flow has been reduced considerably which is observed
network.
from Table 3. In IEEE-30 bus system, previously the lines
27, 26, 9 and 18 which were carrying very high reactive power
TCSC in lines SVC in buses now carry lesser amount of reactive power for all cases of load-
25, 41, 28, 5 21, 7, 17, 15 ings after placement of SVCs at 21, 7, 17 and 15 buses. These
buses are at the finishing end of the lines 27, 26, 9 and 18
respectively. Similarly it happened for the lines where TCSCs
are placed except in line 5 for IEEE-30 bus system as observed
Table 1b Locations of TCSC, SVC & UPFC in the trans- from Table 3. There are more or less no change in reactive
mission network. power flow for 150% and 200% of base reactive loading in
both GA and DE based approach in case of line 5. But as a
TCSC in lines SVC in buses UPFC in buses
whole, there is significant reduction in reactive power flow as
28, 20, 15 17, 7, 21 2, 4, 3 observed from Table 3.

Table 2 Limits of FACTS devices and other controlling parameters.


TCSC (pu) SVC (pu) UPFC Transformer Tap Reactive generation Qg
positions (pu)
0.025 (min) 0 (min) 0.1Vmax and angle 0.9 (min) Within the minimum and maximum
0.6 (max) 0.5 (max) lies between 180 to +180 1.1 (max) value of reactive generations of the
generators of the IEEE-30 bus system
782
Table 3 Reactive power flows in lines without and with FACTS devices (TCSC & SVC) using GA & DE based techniques.
Line no. Base reactive load 150% Base reactive load 200% Base reactive load
Reactive power Reactive power Reactive power Reactive power Reactive power Reactive power Reactive power Reactive power Reactive power
flow without flow with FACTS flow with FACTS flow without flow with FACTS flow with FACTS flow without flow with FACTS flow with FACTS
FACTS (pu) using GA (pu) using DE (pu) FACTS (pu) using GA (pu) using DE (pu) FACTS (pu) using GA (pu) using DE (pu)
27 0.0939 0.0656 0.0690 0.1430 0.0613 0.0559 0.1925 0.0630 0.0638
26 0.0608 0.0380 0.0542 0.0735 0.0251 0.0058 0.0860 0.0173 0.0350
9 0.0731 0.0055 0.0038 0.0884 0.0064 0.0102 0.1032 0.0141 0.0119
18 0.0507 0.0527 0.0518 0.0930 0.0524 0.0481 0.1365 0.0608 0.0618
25 0.0441 0.0440 0.0537 0.0553 0.0494 0.0265 0.0664 0.0649 0.0512
41 0.0421 0.0217 0.0311 0.0581 0.0186 0.0174 0.0751 0.0248 0.0248
28 0.0419 0.0371 0.0400 0.0650 0.0376 0.0356 0.0883 0.0432 0.0434
5 0.0390 0.0384 0.0471 0.0387 0.0383 0.0383 0.0384 0.0381 0.0382

Table 4 Reactive power flows in lines without and with FACTS devices (TCSC, SVC & UPFC) using GA & DE based techniques.
Line no. Base reactive load 150% Base reactive load 200% Base reactive load
Reactive power Reactive power Reactive power Reactive power Reactive power Reactive power Reactive power Reactive power Reactive power
flow without flow using GA flow using DE flow without flow using GA flow using DE flow without flow using GA (TCSC, flow using DE
FACTS (pu) (TCSC, SVC & (TCSC, SVC & FACTS (pu) (TCSC, SVC & (TCSC, SVC & FACTS (pu) SVC & UPFC) (pu) (TCSC, SVC &
UPFC) (pu) UPFC) (pu) UPFC) (pu) UPFC) (pu) UPFC) (pu)
4 0.0277 0.0573 0.0754 0.0153 0.0638 0.0650 0.0025 0.0291 0.0422
6 0.0510 0.0033 0.0084 0.0312 0.0082 0.0088 0.0107 0.0123 0.0048
7 0.0240 0.2205 0.2667 0.0165 0.2329 0.2364 0.0086 0.1634 0.2012
9 0.0731 0.0001 0.0095 0.0884 0.0003 0.0190 0.1032 0.0033 0.0338

B. Bhattacharyya et al.
15 0.0685 0.0741 0.0682 0.0341 0.0459 0.0378 0.0016 0.0421 0.0352
20 0.0024 0.0125 0.0138 0.0089 0.0023 0.0024 0.0155 0.0042 0.0075
21 0.0020 0.0798 0.0872 0.0145 0.0440 0.0439 0.0313 0.0804 0.1000
27 0.0939 0.0617 0.0634 0.1430 0.0673 0.0721 0.1925 0.0492 0.0299
28 0.0419 0.0350 0.0361 0.0650 0.0379 0.0398 0.0883 0.0382 0.0314
UPFC with series and shunt FACTS controllers for the economic operation of a power system 783

Table 5 Bus voltages without and with FACTS devices for 200% reactive loading using GA & DE approach in IEEE-30 bus system.
Bus no. Bus voltage without Bus voltages with Bus voltages with Bus voltages with Bus voltages with
FACTS (pu) FACTS using GA FACTS using GA FACTS using DE FACTS using DE
(TCSC & SVC) (TCSC, SVC & UPFC) (TCSC & SVC) (TCSC, SVC &
(pu) Case I (pu) Case II (pu) Case I UPFC) (pu) Case II
1 1.0500 1.0500 1.0500 1.0500 1.0500
2 1.0338 1.0338 1.0338 1.0338 1.0338
3 1.0284 1.0140 1.0211 1.0138 1.0187
4 1.0231 1.0058 1.0144 1.0056 1.0115
5 1.0058 1.0058 1.0058 1.0058 1.0058
6 1.0182 1.0122 1.0165 1.0122 1.0152
7 1.0014 1.0043 1.0072 1.0042 1.0034
8 1.0230 1.0230 1.0230 1.0230 1.0230
9 1.0302 1.0532 1.0483 1.0514 1.0488
10 1.0135 1.0490 1.0510 1.0493 1.0534
11 1.0913 1.0913 1.0913 1.0913 1.0913
12 1.0295 1.0144 1.0274 1.0151 1.0227
13 1.0883 1.0883 1.0883 1.0883 1.0883
14 1.0096 1.0061 1.0113 1.0070 1.0075
15 1.0036 1.0113 1.0096 1.0122 1.0067
16 1.0122 1.0212 1.0300 1.0219 1.0292
17 1.0050 1.0383 1.0429 1.0389 1.0459
18 0.9906 1.0072 1.0068 1.0079 1.0057
19 0.9871 1.0091 1.0094 1.0097 1.0095
20 0.9926 1.0179 1.0186 1.0184 1.0193
21 0.9956 1.0389 1.0418 1.0391 1.0456
22 0.9965 1.0370 1.0397 1.0373 1.0431
23 0.9892 1.0037 1.0035 1.0044 1.0024
24 0.9819 1.0064 1.0082 1.0068 1.0096
25 0.9901 1.0018 1.0043 1.0021 1.0048
26 0.9651 0.9748 0.9773 0.9750 0.9778
27 1.0079 1.0127 1.0155 1.0129 1.0155
28 1.0121 1.0086 1.0119 1.0087 1.0110
29 0.9832 0.9866 0.9894 0.9867 0.9894
30 0.9696 0.9724 0.9753 0.9726 0.9753

Table 6a Magnitudes of control variables in the network with FACTS devices (TCSC & SVC) using GA & DE based techniques.
Loading SVC amount (pu) TCSC amount (pu) Reactive generation Qg (pu) Transformer tap position (pu)
GA DE GA DE GA DE GA DE
100% 0.0754 0.0767 0 0 0.3669 0.38 0.9478 0.9516
0.05 0.0472 0.0419 0.0419 0.2138 0.625 0.9012 0.9
0.0335 0.0359 0 0 0.3381 0 0.9005 0.9
0.0660 0.0654 0.0503 0.0506 0.2304 0.4 0.9282 0.9284
0.0827 0.0878
200% 0.2291 0.2273 0 0 0.3202 0.6 0.9873 0.9945
0.1610 0.1578 0 0 0.2790 0 0.9066 0.9
0.1044 0.1077 0 0 0.2963 0 0.9130 0.9109
0.1564 0.1593 0.0490 0.0485 0.2638 0 0.9 0.9
0.1718 0.3596

From Table 1b, it is clear that TCSCs are placed in line FACTS devices are connected for all cases of loading, only
number 28, 20 and 15 as at these lines reactive power flows there is slight increase in reactive power flow in lines 4 and 6
were very high while SVCs are placed at buses 17, 7 and 21, as seen from Table 4.
the finishing end of the lines 21, 9 and 27. 2nd, 3rd and 4th Even at 200% of base reactive loading with FACTS devices
bus is selected for UPFC connection as there is large amount voltage profile of all the buses are within the desired limit with
of flow of active power in the lines 6, 4 and 7 respectively those both GA and DE methods. Magnitudes of control variables
are at the starting end of the 2nd, 3rd and 4th bus. After instal- consists of FACTS devices such as TCSCs, SVCs and UPFCs,
lation of FACTS devices to these lines reactive power flow has reactive generation of generators and transformer tap
been reduced considerably which is observed from Table 4. positions are within the operating limits for different loading
Reactive power flow reduces significantly in lines where conditions as shown in Tables 6a and 6b. Active power loss
784 B. Bhattacharyya et al.

Table 6b Magnitudes of control variables in the network with FACTS devices (TCSC, SVC & UPFC) using GA & DE based
techniques.
Loading SVC amount (pu) TCSC amount (pu) UPFC amount Reactive generation Qg Transformer tap position
(pu) (pu) (pu)
GA DE GA DE GA DE GA DE GA DE
100% 0.0310 0.0385 0.0417 0.0339 0.0051 0.0038 0.1102 0.1145 0.9778 0.9506
0.0520 0.0509 0 0.0115 0.0129 0.0203 0.2321 0.0875 0.9132 0.9461
0.0804 0.0804 0 0.0090 0.0099 0.0190 0.1504 0.2436 0.9148 0.9
0.0960 0.0849 0.9201 0.9068
0.2385 0.2634
200% 0.1124 0.1371 0.0226 0.0164 0.0045 0.0053 0.0446 0.6 1.0142 1.0155
0.1664 0.1057 0 0.0056 0.0193 0.0186 0.2141 0.2345 0.9 0.9
0.2509 0.2832 0 0.0032 0.0134 0.0199 0.1712 0.5 0.9464 0.9342
0.2390 0 0.9464 0.9314
0.2467 0.0499

Table 7 Operating cost & active power loss analysis without and with FACTS devices with GA & DE based approach in IEEE-30
bus.
Reactive Active power loss Operating cost Evolutionary methods Active power Operating cost Cost of fACTS Net saving
loading without FACTS due to energy with FACTS devices loss with FACTS (in $) (B) devices (in $) (in $) (A–B)
devices (pu) loss (in $) (A) devices (pu)
100% 0.0711 3737016 GA (TCSC & SVC) 0.0405 2.1741 · 106 45,420 1,562,916
GA (TCSC, SVC & UPFC) 0.0385 2.0519 · 106 28,340 1,685,116
DE (TCSC & SVC) 0.0405 2.1740 · 106 45,320 1,563,016
DE (TCSC, SVC & UPFC) 0.0385 2.0634 · 106 39,840 1,673,616
150% 0.0742 3899952 GA (TCSC & SVC) 0.0432 2.3391 · 106 68,508 1,560,852
GA (TCSC, SVC & UPFC) 0.0428 2.2832 · 106 33,632 1,616,752
DE (TCSC & SVC) 0.0432 2.3390 · 106 68,408 1,560,952
DE (TCSC, SVC & UPFC) 0.0427 2.2910 · 106 46,688 1,608,952
200% 0.0795 4178520 GA (TCSC & SVC) 0.0572 3.0969 · 106 90,468 1,081,620
GA (TCSC, SVC & UPFC) 0.0540 2.9047 · 106 66,460 1,273,820
DE (TCSC & SVC) 0.0572 3.0967 · 106 90,268 1,081,820
DE (TCSC, SVC & UPFC) 0.0540 2.9202 · 106 81,960 1,258,320

and operating cost reduce significantly with FACTS devices


using GA and DE under different loading cases. In Case I,
where only TCSCs and SVCs are used as FACTS devices,
active power loss and operating costs are nearly same for both
GA and DE approach. But in case II, where TCSCs, SVCs and
UPFCs are used as FACTS devices, active power loss is con-
siderably reduced in each cases of loading if compared with
case I, though the magnitudes of active power loss is same with
GA and DE. Also there is significant difference in the operat-
ing cost when UPFCs along with TCSCs and SVCs are used
compared to the situation where TCSCs and SVCs are used
as FACTS devices. In all cases of loading, a large economic
benefit in terms of savings is observed by using GA and DE
based approach for the placement of FACTS controller. Again
it is to be mentioned that introduction of UPFC with other
FACTS devices results further decrease in active power loss
and operating cost compared to the operation with FACTS
devices excluding UPFC.
GA and DE based algorithms are run for 500 generations
and the number of populations is taken as 80 for IEEE-30
bus system. Figs. 8–10 show variation in operating cost with
generation using GA and DE technique for case I. Similarly, Figure 8 Variation in Operating Cost with generation for base
Figs. 11–13 show variation in operating cost with generation loading using GA & DE with TCSC & SVC in IEEE-30 bus
using GA and DE technique for case II. system.
UPFC with series and shunt FACTS controllers for the economic operation of a power system 785

Figure 9 Variation in Operating Cost with generation for 150% Figure 12 Variation in Operating Cost with generation for
of base loading using GA & DE with TCSC & SVC in IEEE-30 150% of base loading using GA & DE with TCSC, SVC & UPFC
bus system. in IEEE-30 bus system.

Figure 13 Variation in Operating Cost with generation for


Figure 10 Variation in Operating Cost with generation for 200% of base loading using GA & DE with TCSC, SVC & UPFC
200% of base loading using GA & DE with TCSC & SVC in in IEEE-30 bus system.
IEEE-30 bus system.

Cost of energy for per kW h is 0.06 $/kW h.

8. Conclusion

In this paper Genetic Algorithm (GA) and Differential Evolu-


tion (DE) approach are used for the optimal allocation and
setting of FACTS devices along with reactive generation of
generators and transformer tap positions. Two cases are con-
sidered for the optimal location and types of FACTS devices.
In the first case, TCSC as a series controller and SVC as a
shunt FACTS controller is used along with the existing power
system variables for obtaining economic operation of the
power system. In case II, UPFC is used with the series and
shunt FACTS controllers as mentioned along with the existing
power system variables in minimizing active power loss and
Figure 11 Variation in Operating Cost with generation for base system operating cost as case I. It is observed that use of
loading using GA & DE with TCSC, SVC & UPFC in IEEE-30 UPFC along with series and shunt FACTS controller gives
bus system. better result than without UPFC. Active power loss and
786 B. Bhattacharyya et al.

operating cost reduced significantly and huge economic gain generic graphical user interface. IEEE Trans Power Syst
are achieved with the placement of UPFC along with other 2013;28(2):764–78.
FACTS controller by both the GA and DE based optimization [20] Lashkar Ara A, Kazemi A, Nabavi Niaki SA. Multiobjective
techniques. optimal location of FACTS shunt-series controllers for power
system operation planning. IEEE TRANS Power Del
2012;27(2):481–90.
References [21] Basu M. Optimal power flow with FACTS devices using
differential evolution. Int J Electr Power Energy Syst
[1] Hingorani NG. High power electronics and flexible AC transmis- 2008;30:150–6.
sion system. IEEE Power Eng Rev 1998, July. [22] Verma KS, Singh SN, Gupta HO. Location of unified power flow
[2] Hingorani N. Flexible AC transmission. IEEE Spectrum controller for congestion management. Electr Power Syst Res
1993;30(4):40–5. 2001;58:89–96.
[3] Ramey D, Nelson R, Bian J, Lemak T. Use of FACTS power flow [23] Chong B, Zhang XP, Godfrey KR, Yao L, Bazargan M. Optimal
controllers to enhance transmission transfer limits. In: Proceed- location of unified power flow controller for congestion manage-
ings American power conference, vol. 56, Part 1; April 1994. p. ment. Europ Trans Electr Power 2010;20(5):600–10.
712–8. [24] Venkatesh B, Gooi HB. Optimal siting of united power flow
[4] Rajaraman R, Alvarado F, Maniaci A, Camfield R, Jalali S. controllers. Electr Power Compon Syst 2006;34:271–84.
Determination of location and amount of series compensation to [25] Shaheen HI, Rashed GI, Cheng SJ. Application and comparison
increase power transfer capability. IEEE Trans Power Syst of computational intelligence techniques for optimal location and
1998;13(2):294–9. parameter setting of UPFC. Eng Appl Artif Intell. Elsevier, vol.
[5] Orfanogianni T, Bacher R. Steady-state optimization in power 23; 2010. p. 203–16.
systems with series FACTS devices. IEEE Trans Power Syst [26] Shaheen HI, Rashed GI, Cheng SJ. Application of differential
2003;18(1):19–26, February. evolution algorithm for optimal location and parameters setting
[6] Domınguez-Navarro JA, Bernal-Agustın JL, Dıaz A, Requena D, of UPFC considering power system security. Europ Trans Electr
Vargas EP. Optimal parameters of FACTS devices in electric Power 2009;19(7):911–32.
power systems applying evolutionary strategies. Int J Electr Power [27] Sode-Yome A, Mithulananthan N, Lee KY. Comprehensive
Energy Syst 2007;29:83–90. comparison of FACTS devices for exclusive loadability enhance-
[7] Taghavi R, Seifi A. Optimal reactive power control in hybrid ment. IEEJ Trans Electr Electron Eng 2013;8(1):7–18.
power systems. Electr Power Compon Syst 2012;40:741–58. [28] Lashkar Ara A, Kazemi A, Nabavi Niaki SA. Modelling of
[8] Xiao Y, Song YH, Sun YZ. Power flow control approach to Optimal Unified Power Flow Controller (OUPFC) for optimal
power systems with embedded FACTS devices. IEEE Trans steady-state performance of power systems. Energy Conver
Power Syst 2000;17(4):943–50. Manage. Elsevier, vol. 52; 2011. p. 1325–33.
[9] Xiao Y, Song YH, Chen-Ching Liu, Sun YZ. Available transfer [29] Singh JG, Singh SN, Srivastava SC. Optimal placement of unified
capability enhancement using FACTS devices. IEEE Trans Power power flow controller based on system loading distribution
Syst 2009;18(1):305–12. factors. Electr Power Compon Syst 2009;37:441–63.
[10] Jabr RA. Optimization of reactive power expansion planning. [30] Cai LJ, Erlich I. Optimal choice and allocation of FACTS
Elect Power Compon Syst 2011;39:1285–301. devices using genetic algorithms. In: Proceedings on twelfth
[11] Yousefi GR, Seifi H, Shirmohammadi D. A new algorithm for intelligent systems application to power systems conference;
reactive power management and pricing in an open access 2003. p. 1–6.
environment. Europ Trans Electr Power 2008;18(2):109–26.
[12] Yan W, Lu S, David CYu. A novel optimal reactive power
dispatch method based on an improved hybrid evolutionary Biplab Bhattacharyya born in 9th January,
programming technique. IEEE Trans Power Syst 1970. He is currently working as Associate
2004;19(2):913–8. Professor of Electrical Engineering in the
[13] Ongsakul W, Tantimaporn T. Optimal power flow by improved Indian School of Mines University, Dhanbad,
evolutionary programming. Electr Power Compon Syst India. He has joined in the Electrical Engi-
2006;34:79–95. neering department as Assistant Professor in
[14] Bakirtzis AG, Biskas PN, Zoumas CE, Petridis V. Optimal power the year of 2007. Then he promoted to the
flow by enhanced genetic algorithm. IEEE Trans Power Syst post of Associate Professor on 2010. He had
2002;17(2). served department of Electrical Engineering of
[15] Nireekshana T, Rao GK, Raju SSN. Enhancement of ATC with National In-stitute of Technology, Durgapur,
FACTS devices using real-code genetic algorithm. Int J Electr India for six years as senior Lecturer. He was
Power Energy Syst 2012;43:1276–84. in the position of Lecturer in the Electrical Engineering department of
[16] Gerbex S, Cherkaoui R, Germond AJ. Optimal location of multi- BITS, Pilani, Rajasthan, India for nearly one year. He worked as
type FACTS devices in a power system by means of genetic Assistant Engineer (Electrical Test), in a reputed cable industry for
algorithm. IEEE Trans Power Syst 2001;16:537–44. nearly three years. He obtained B.Sc (Hons) in Physics from Calcutta
[17] Das D. Reactive power compensation for radial distribution University, India in 1990. He obtained his B-Tech and M-Tech degree
network using genetic algorithm. Electr Power Energy Syst in the field of Electrical machines and Power system from Calcutta
2002;24:573–81. University in 1993 and 1995 respectively. He obtained his Phd degree
[18] Osman MS, Abo-Sinna MA, Mousa AA. A solution to the in Engineering from the department of Electrical Engineering, Jadav-
optimal power flow using genetic algorithm. Appl Math Comput pur University, India in 2006. He has published several technical
2004;155:391–405. papers in international/national journals and conference proceedings.
[19] Ghahremani E, Kamwa I. Optimal placement of multiple-type His research area mainly includes Evolutionary approaches, Power
FACTS devices to maximize power system loadability using a system optimization, Planning, Dispatch, FACTS devices.
UPFC with series and shunt FACTS controllers for the economic operation of a power system 787
Vikash Kumar Gupta born in 9th January Sanjay Kumar born in 5th June 1980. He
1984. He received B. E. degree Anna Univer- received B.Tech degree from N.I.T Jamshed-
sity, Chennai in 2009, and the M.Tech degree pur in 2006, M.Tech from N.I.T Patna in
from B.I.T. Sindri, Dhnabad, Jharkhand in 2010. He has having two years of teaching
2011. Currently, he is the Research Scholar in experience and currently, he is the Research
the Electrical Engineering Department, Indian Scholar in the Electrical Engineering Depart-
School of Mines, Dhanbad, Jhark-hand. His ment, Indian School of Mines, Dhanbad,
area of interest is Power System. Jharkhand.

Вам также может понравиться