NEC/CEC: NEC/CEC:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB
Class I, Zone 2 Group IIC Simultaneous Exposure
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY
Class III Wet Locations
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67
Applications
• Enclosed and gasketed fixtures suitable for use in:
— A wide range of industrial, chemical processing and other
areas where flammable gases and vapors are present, for
example
— Oil and Gas Refineries
— Petrochemical Plants
— Foundries
— Drilling Rigs
— Pulp and Paper Mills
— Food and Beverage Processing Facilities
— Loading Docks
— Power Plants
— Water and Wastewater Treatment Facilities
— Other areas where corrosive, wet, dirty and tough
environments are a problem
• IP66/IP67, Type 4X, marine and wet locations
• Locations requiring dependable, consistent lighting in extreme
hot/cold temperature environments. -40 °C to +65 °C
(-40 °F to +149 °F) ambient temperature range Floodlight
Features
• Three lumen outputs provide up to 19,500 lumens.
Nominal Wattage Efficacy HID Model
Lumens (W) (lpw) Equivalent Number Standard Materials
9,500 70 136 175W-250W AMLGL6 • Housing and lens door: copperfree (4/10 of 1% max.) aluminum
Order using catalog numbering guides below or select catalog number from tables on following pages.
AMLG L7 C G 7 BU S
LED/Floodlights: NEC/CEC Enclosed and Gasketed
3000K CCT (warm) is not available with NEMA 7x7 light pattern
Frosted Glass is only available with NEMA 7x7 light pattern
Use of fuse voids Marine rating.
All lumen values are typical (tolerance +/-10%).
Electrical Ratings
Input Current Total Harmonic
Voltage Suffix Voltage (V) Input Power (Watts) (Amps) Power Factor (PF) Distortion (THD) Model Number
120 Vac 73 0.62
>.9 <20%
277 Vac 71 0.27
BU
170 Vdc 69 0.41
N/A N/A AMLGL6
300 Vdc 68 0.23
347 Vac 71 0.21
BH >.9 <20%
480 Vac 71 0.16
120 Vac 111 0.94
>.9 <20%
277 Vac 106 0.43
BU
170 Vdc 113 0.67
N/A N/A AMLGL7
300 Vdc 111 0.37
347 Vac 115 0.33
BH >.9 <20%
480 Vac 115 0.25
120 Vac 154 1.30
>.9 <20%
277 Vac 146 0.56
BU
170 Vdc 156 0.92
90° to Ground-Worst
1.52 1.20 1.82
Case Mounting
Wind Direction
45° to Ground-Standard
1.07 1.2 1.28
Mounting
Wind Direction
Surge Protection: Integral 6KV surge protection. Option for up to 10KV surge protection. (cCSAus only).
All ratings are typical.
NEC/CEC: NEC/CEC:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB
Class I, Zone 2 Group IIC Simultaneous Exposure
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY
Class III Wet Locations
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67
Temperature Codes
Lamp Gas Dust
“T” Numbers Represent the Maximum Internal Temperature or Maximum Surface Temperature
NEC/CEC
“T” # T1 350 325 T2 T2A T2B T2C T2D T3 T3A T3B T3C T4 T4A T5 T6
Temp. 351- 326- 301- 281- 261- 231- 216- 201- 181- 166- 161- 136- 121- 101- 86-
85
450 350 325 300 280 260 230 215 200 180 165 160 135 120 100
Range
(664- (619- (574- (538- (502- (448- (421- (394- (358- (331- (322- (277- (250- (214- (187-
ºC (˚ºF) (185)
842) 662) 617) 572) 536) 500) 446) 419) 392) 356) 329) 320) 275) 248) 212)
ATEX/IECEx
“T” # T1 T2 T3 T4 T5 T6
Temp. 86-
301-450 201-300 136-200 101-135 85
100
Range
(187-
ºC (˚ºF) (547-842) (394-572) (277-392) (214-275) (185)
212)
T numbers represent the maximum internal temperature for Class I, Division 2 and Class I, Zone 2 locations designated by the NEC.
T numbers represent the maximum surface temperature under a dust blanket for Class II, Division 1 and 2 as designated by the NEC.
NEC/CEC: NEC/CEC:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB
Class I, Zone 2 Group IIC Simultaneous Exposure
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY
Class III Wet Locations
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67
For Fusing option, add suffix F to end of part number, example AMLGL8CG6BUF.
For 10KV surge protection, add suffix S to end of part number, example AMLGL7CG7BUS.
For both Fusing and 10KV surge, add suffix FS to end of part number, example AMLGL8CG7BUFS.
NEC/CEC: NEC/CEC:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB
Class I, Zone 2 Group IIC Simultaneous Exposure
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY
Class III Wet Locations
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67
Crossarm Mounting Bracket (G-AM-8-CA) used with Pipe or Wall Mount Bracket (G-AM-8-WB).
Poletop Slip-Fitter
Poletop Slip-Fitter
NEC/CEC: NEC/CEC:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB
Class I, Zone 2 Group IIC Simultaneous Exposure
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY
Class III Wet Locations
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67
Wire Guard
Safety Cable
Visor
NEC/CEC: NEC/CEC:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB
Class I, Zone 2 Group IIC Simultaneous Exposure
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY
Class III Wet Locations
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67
Replacement Covers
AMLGCLEAR
AMLGFROST
Driver Constant
Voltage Wattage Current Setting Luminaire Model CCT Catalog Number
Replacement Drivers
BU AMLGL6C, APMS100C105UD41
100 watt 410mA 5K and 3K
BH AMLGL6W APMS100C105HD41
BU APMS150C105UD65
150 watt 650mA AMLGL7W 3K
BH APMS150C105HD65
BU APMS150C105UD68
150 watt 680mA AMLGL7C 5k
BH APMS150C105HD68
BU APMS150C105UD89
150 watt 890mA AMLGL8W 3K
LED/Floodlights: NEC/CEC Enclosed and Gasketed
BH APMS150C105HD89
BU APMS150C105HD93
150 watt 930mA AMLGL8C 5k
BH APMS150C105HD93
NEC/CEC: NEC/CEC:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB
Class I, Zone 2 Group IIC Simultaneous Exposure
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY
Class III Wet Locations
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67
156.5 mm
(6.16 in) 351.5 mm
413.5 mm Square (13.84 in)
(16.28 in)
(4) Yoke
Bolts
152.4 mm
Conduit Entry Yoke (6.00 in)
57.2 mm
44.5 mm
(1.75 in) (3) Mounting Holes 152.4 mm (6.00 in) Turning Radius
Ø 14 mm (0.56 in) 180° Rotation
88.9 mm
(3.5 in)
NEC/CEC: NEC/CEC:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB
Class I, Zone 2 Group IIC Simultaneous Exposure
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY
Class III Wet Locations
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67
110°
1,133
0 Tilt Angle- 45 Degree LLF-0.9
567 100°
1 Mounting Maximum
0 90° Height Point Forward Throw Distance (ft)
2
567 80° 0.5 Fc 1 Fc 2Fc 5Fc
1,133
3 20 1.51 45 35 24 11
70°
1,700 4
30 0.68 47 36 21 N/A
60° 40 0.38 50 35 N/A N/A
2,267
20 fc 1fc
10 fc 0.5 fc
2,833 50°
5 fc 0.2 fc Tilt Angle- 45 Degree LLF-0.9
2.5 fc 0.1 fc
3,400 Mounting
LED/Floodlights: NEC/CEC Enclosed and Gasketed
NEC/CEC: NEC/CEC:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB
Class I, Zone 2 Group IIC Simultaneous Exposure
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY
Class III Wet Locations
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67
Mounting Maximum
817 100° 0
Height Point Forward Throw Distance (ft)
0 90° 1
0.5 Fc 1 Fc 2Fc 5Fc
817 80° 2 20 4.42 50 39 29 16
1,633
30 1.97 55 43 25 N/A
70° 3
40 1.11 57 40 19 N/A
2,450
4
60°
3,267 Tilt Angle- 45 Degree LLF-0.9
20 fc 1fc
4,083 50° 10 fc 0.5 fc Mounting
5 fc 0.2 fc Height Side-to-Side Distance (ft)
4,900 2 fc 0.1 fc
0° 10° 20° 30° 40° 0.5 Fc 1 Fc 2Fc 5Fc
20 70 56 40 20
-0° H -22.5° H
-90° H -45° H 30 80 58 38 N/A
-67.5° H 40 80 50 16 N/A
NEC/CEC: NEC/CEC:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB
Class I, Zone 2 Group IIC Simultaneous Exposure
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY
Class III Wet Locations
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67
10 fc 0.5 fc
6,900
5 fc 0.2 fc Height Side-to-Side Distance (ft)
0° 10° 20° 30° 40°
2.5 fc 0.1 fc 0.5 Fc 1 Fc 2Fc 5Fc
Point of Max FC: 10.02
-0° H -22.5° H 20 84 70 52 32
-90° H -45° H 30 96 72 54 15
-67.5° H
40 104 72 48 N/A
1,067 100°
Mounting Maximum
0
Height Point Forward Throw Distance (ft)
0 90° 1
0.5 Fc 1 Fc 2Fc 5Fc
1,067 80°
2 20 5.76 55 43 32 20
2,133
70° 30 2.56 31 45 31 N/A
3
3,200 40 1.43 62 49 29 N/A
60° 4
4,267
Tilt Angle- 45 Degree LLF-0.9
5,333 50° 20 fc 1fc
10 fc 0.5 fc Mounting
6,400
0° 10° 20° 30° 40°
5 fc 0.2 fc Height Side-to-Side Distance (ft)
2 fc 0.1 fc
0.5 Fc 1 Fc 2Fc 5Fc
-0° H -22.5° H 20 78 60 44 22
-90° H -45° H
-67.5° H
30 88 62 34 N/A
40 98 58 38 N/A
NEC/CEC: NEC/CEC:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB
Class I, Zone 2 Group IIC Simultaneous Exposure
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY
Class III Wet Locations
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67
-0° H -22.5° H 20 84 64 44 16
-90° H -45° H 30 90 66 36 N/A
-67.5° H
40 96 56 N/A N/A
NEMA 7x6, Clear Glass
REPORT NUMBER: AMLGL6WG7BU
2,500
40 0.73 56 36 N/A N/A
60° 20 fc 1fc
3,333 10 fc 0.5 fc Tilt Angle- 45 Degree LLF-0.9
5 fc 0.2 fc
2 fc 0.1 fc
4,167 50° Mounting Point of Max FC: 10.02
5,000 Height Side-to-Side Distance (ft)
0° 10° 20° 30° 40°
0.5 Fc 1 Fc 2Fc 5Fc
-0° H -22.5° H 20 80 64 44 16
-90° H -45° H 30 84 60 36 N/A
-67.5° H
40 88 48 N/A N/A
NEC/CEC: NEC/CEC:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB
Class I, Zone 2 Group IIC Simultaneous Exposure
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY
Class III Wet Locations
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67
3,650
40 1.07 64 50 N/A N/A
60° 20 fc 1fc
4,867 10 fc
5 fc
0.5 fc
0.2 fc
Tilt Angle- 45 Degree LLF-0.9
6,083 2 fc 0.1 fc
50° Mounting
Point of Max FC: 10.02
7,300 Height Side-to-Side Distance (ft)
0° 10° 20° 30° 40°
0.5 Fc 1 Fc 2Fc 5Fc
-0° H -22.5° H 20 90 72 52 30
-90° H -45° H 30 108 78 48 N/A
-67.5° H
40 112 72 N/A N/A
NEC/CEC: NEC/CEC:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB
Class I, Zone 2 Group IIC Simultaneous Exposure
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY
Class III Wet Locations
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67