MID SPAN CLEARANCE BETWEEN TOP PHASE CONDUCTOR AND OPGW
As per SEC Standard TES‐P‐122.09 Table 9‐13
Midspan clearance required for 244 m Span 7.30 m
Midspan clearance required for 305 m Span 9.70 m
By linear interpolation
Midspan clearance required at 250.00 m Ruling Span: ( 250 ‐ 244 ) / ( 305 ‐ 244 ) x ( 9.70 ‐ 7.30 )+ 7.30
(AF) = 7.54 m
Final Sag of AAAC Conductor at every day temperature 30 ºC, No wind &
250.00 m Ruling Span: 6200 mm (Sag without Conductor Lights)
Final Condition (AB)
Final Sag of OPGW at every day temperature 30ºC, No wind & Final
250.00 m Ruling Span: 4170 mm (Sag without Warning Spheres)
Condition (HF)
Length of V‐suspension string for top phase top conductor: (tower cleat+4720‐646.29)‐conductor radius:
4209.16 mm
(150+4720‐646.29)‐(29.1/2) (BC)
Vertical length of OPGW suspension assembly: 129+(16.2/2)+tower cleat(65) ‐ (DH) 202.10 mm
Horizontal distance from center of tower to top right conductor (top cross arm): (2085/2)+(12232/2) 6958.5 mm
Horizontal distance from center of tower to OPGW attachment point: (1900/2)+5200 6150 mm
Horizontal distance between OPGW attachment point and conductor attachment
(6958.5 ‐ 6150) 808.5 mm
point: (GF)
Midspan Clearance: √(AG²+ GF²)
(AF)
MID SPAN CLEARANCE BETWEEN TOP PHASE CONDUCTOR AND OPGW
As per SEC Standard TES‐P‐122.09 Table 9‐13
Midspan clearance required for 244 m Span 7.30 m
Midspan clearance required for 305 m Span 9.70 m
By linear interpolation
Midspan clearance required at 275.00 m Ruling Span: ( 275 ‐ 244 ) / ( 305 ‐ 244 ) x ( 9.70 ‐ 7.30 )+ 7.30
(AF) = 8.52 m
Final Sag of AAAC Conductor at every day temperature 30 ºC, No wind &
275.00 m Ruling Span: 7200 mm (Sag without Conductor Lights)
Final Condition (AB)
Final Sag of OPGW at every day temperature 30ºC, No wind & Final
275.00 m Ruling Span: 5050 mm (Sag without Warning Spheres)
Condition (HF)
Length of V‐suspension string for top phase top conductor: (tower cleat+4720‐646.29)‐conductor radius:
4209.16 mm
(150+4720‐646.29)‐(29.1/2) (BC)
Vertical length of OPGW suspension assembly: 129+(16.2/2)+tower cleat(65) ‐ (DH) 202.85 mm
Horizontal distance from center of tower to top right conductor (top cross arm): (2085/2)+(12232/2) 6958.5 mm
Horizontal distance from center of tower to OPGW attachment point: (1900/2)+5200 6150 mm
Horizontal distance between OPGW attachment point and conductor attachment
(6958.5 ‐ 6150) 808.5 mm
point: (GF)
Midspan Clearance: √(AG²+ GF²)
(AF)
MID SPAN CLEARANCE BETWEEN TOP PHASE CONDUCTOR AND OPGW
As per SEC Standard TES‐P‐122.09 Table 9‐13
Midspan clearance required for 244 m Span 7.30 m
Midspan clearance required for 305 m Span 9.70 m
By linear interpolation
Midspan clearance required at 300.00 m Ruling Span: ( 300 ‐ 244 ) / ( 305 ‐ 244 ) x ( 9.70 ‐ 7.30 )+ 7.30
(AF) = 9.50 m
Final Sag of AAAC Conductor at every day temperature 30 ºC, No wind &
300.00 m Ruling Span: 8220 mm (Sag without Conductor Lights)
Final Condition (AB)
Final Sag of OPGW at every day temperature 30ºC, No wind & Final
300.00 m Ruling Span: 6010 mm (Sag without Warning Spheres)
Condition (HF)
Length of V‐suspension string for top phase top conductor: (tower cleat+4720‐646.29)‐conductor radius:
4209.16 mm
(150+4720‐646.29)‐(29.1/2) (BC)
Vertical length of OPGW suspension assembly: 129+(16.2/2)+tower cleat(65) ‐ (DH) 202.85 mm
Horizontal distance from center of tower to top right conductor (top cross arm): (2085/2)+(12232/2) 7158.5 mm
Horizontal distance from center of tower to OPGW attachment point: (1900/2)+5200 6150 mm
Horizontal distance between OPGW attachment point and conductor attachment
(6958.5 ‐ 6150) 1008.5 mm
point: (GF)
Midspan Clearance: √(AG²+ GF²)
(AF)
MID SPAN CLEARANCE BETWEEN TOP PHASE CONDUCTOR AND OPGW
As per SEC Standard TES‐P‐122.09 Table 9‐13
Midspan clearance required for 305 m Span 9.70 m
Midspan clearance required for 350 m Span 11.30 m
By linear interpolation
Midspan clearance required at 320.00 m Ruling Span: ( 320 ‐ 305 ) / ( 350 ‐ 305 ) x ( 11.30 ‐ 9.70 )+ 9.70
(AF) = 10.23 m
Final Sag of AAAC Conductor at every day temperature 30 ºC, No wind &
320.00 m Ruling Span: 9340 mm (Sag without Conductor Lights)
Final Condition (AB)
Final Sag of OPGW at every day temperature 30ºC, No wind & Final
320.00 m Ruling Span: 6840 mm (Sag without Warning Spheres)
Condition (HF)
Length of V‐suspension string for top phase top conductor: (tower cleat+4720‐646.29)‐conductor radius:
4209.16 mm
(150+4720‐646.29)‐(29.1/2) (BC)
Vertical length of OPGW suspension assembly: 129+(16.2/2)+tower cleat(65) ‐ (DH) 202.85 mm
Horizontal distance from center of tower to top right conductor (top cross arm): (2085/2)+(12232/2) 7158.5 mm
Horizontal distance from center of tower to OPGW attachment point: (1900/2)+5200 6150 mm
Horizontal distance between OPGW attachment point and conductor attachment
(6958.5 ‐ 6150) 1008.5 mm
point: (GF)
Midspan Clearance: √(AG²+ GF²)
(AF)
MID SPAN CLEARANCE BETWEEN TOP PHASE CONDUCTOR AND OPGW
As per SEC Standard TES‐P‐122.09 Table 9‐13
Midspan clearance required for 305 m Span 9.70 m
Midspan clearance required for 350 m Span 11.30 m
By linear interpolation
Midspan clearance required at 350.00 m Ruling Span: ( 350 ‐ 305 ) / ( 350 ‐ 305 ) x ( 11.30 ‐ 9.70 )+ 9.70
(AF) = 11.30 m
Final Sag of AAAC Conductor at every day temperature 30 ºC, No wind &
350.00 m Ruling Span: 11170 mm (Sag without Conductor Lights)
Final Condition (AB)
Final Sag of OPGW at every day temperature 30ºC, No wind & Final
350.00 m Ruling Span: 8200 mm (Sag without Warning Spheres)
Condition (HF)
Length of V‐suspension string for top phase top conductor: (tower cleat+4720‐646.29)‐conductor radius:
4209.16 mm
(150+4720‐646.29)‐(29.1/2) (BC)
Vertical length of OPGW suspension assembly: 129+(16.2/2)+tower cleat(65) ‐ (DH) 202.85 mm
Horizontal distance from center of tower to top right conductor (top cross arm): (2085/2)+(12232/2) 7158.5 mm
Horizontal distance from center of tower to OPGW attachment point: (1900/2)+5200 6150 mm
Horizontal distance between OPGW attachment point and conductor attachment
(6958.5 ‐ 6150) 1008.5 mm
point: (GF)
Midspan Clearance: √(AG²+ GF²)
(AF)
MID SPAN CLEARANCE BETWEEN TOP PHASE CONDUCTOR AND OPGW
As per SEC Standard TES‐P‐122.09 Table 9‐13
Midspan clearance required for 366 m Span 11.90 m
Midspan clearance required for 427 m Span 13.70 m
By linear interpolation
Midspan clearance required at 370.00 m Ruling Span: ( 370 ‐ 366 ) / ( 427 ‐ 366 ) x ( 13.70 ‐ 11.90 )+ 11.90
(AF) = 12.02 m
Final Sag of AAAC Conductor at every day temperature 30 ºC, No wind &
370.00 m Ruling Span: 12490 mm (Sag without Conductor Lights)
Final Condition (AB)
Final Sag of OPGW at every day temperature 30ºC, No wind & Final
370.00 m Ruling Span: 9160 mm (Sag without Warning Spheres)
Condition (HF)
Length of V‐suspension string for top phase top conductor: (tower cleat+4720‐646.29)‐conductor radius:
4209.16 mm
(150+4720‐646.29)‐(29.1/2) (BC)
Vertical length of OPGW suspension assembly: 129+(16.2/2)+tower cleat(65) ‐ (DH) 202.85 mm
Horizontal distance from center of tower to top right conductor (top cross arm): (2085/2)+(12232/2) 7158.5 mm
Horizontal distance from center of tower to OPGW attachment point: (1900/2)+5200 6150 mm
Horizontal distance between OPGW attachment point and conductor attachment
(6958.5 ‐ 6150) 1008.5 mm
point: (GF)
Midspan Clearance: √(AG²+ GF²)
(AF)
MID SPAN CLEARANCE BETWEEN TOP PHASE CONDUCTOR AND OPGW
As per SEC Standard TES‐P‐122.09 Table 9‐13
Midspan clearance required for 366 m Span 11.90 m
Midspan clearance required for 427 m Span 13.70 m
By linear interpolation
Midspan clearance required at 400.00 m Ruling Span: ( 400 ‐ 366 ) / ( 427 ‐ 366 ) x ( 13.70 ‐ 11.90 )+ 11.90
(AF) = 12.90 m
Final Sag of AAAC Conductor at every day temperature 30 ºC, No wind
400.00 m Ruling Span: 14600 mm (Sag without Conductor Lights)
& Final Condition (AB)
Final Sag of OPGW at every day temperature 30ºC, No wind & Final
400.00 m Ruling Span: 10720 mm (Sag without Warning Spheres)
Condition (HF)
Length of V‐suspension string for top phase top conductor: (tower cleat+4720‐646.29)‐conductor radius:
4209.16 mm
(150+4720‐646.29)‐(29.1/2) (BC)
Vertical length of OPGW suspension assembly: 129+(16.2/2)+tower cleat(65) ‐ (DH) 200.25 mm
Horizontal distance from center of tower to top right conductor (top cross arm): (2085/2)+(12232/2) 7158.5 mm
Horizontal distance from center of tower to OPGW attachment point: (1900/2)+5200 6150 mm
Horizontal distance between OPGW attachment point and conductor attachment
(6958.5 ‐ 6150) 1008.5 mm
point: (GF)
Midspan Clearance: √(AG²+ GF²)
(AF)