Академический Документы
Профессиональный Документы
Культура Документы
EXPERIMENT 1
a) The process plant consists of two air vessels T91 and T92 with the associated piping,
valves and fittings.
b) An external air supply from the compressor air system is connected to the Model plant at
the process inlet at the pressure regulator, AR91, into the vessel T91. This inlet pressure
(Barg, psig) is preset according to the pressure indicated at AR91, with its downstream
manual valve MV91 shut. The maximum inflow rate can be varied by regulating the
manual valve MV91 immediately downstream of AR91.
c) The process air inlet flows into T91 and then along pipeline PLI-T92-FI92-PCV91-
discharge via the process vent valve VP. The process air also flows from T92 along
pipeline PLII-PCV92-discharge via either manual globe valve MV92A/orifice OR
manual gate valve MV92B.
The pressure in T91 is also measured by a gauge pressure transmitter PT91 and
controlled by PID pressure controller PIC91, which throttles control valve PCV91 via the
Current (4-20mA) to Air (3-15 psig) converter, PCY91 and the pneumatic positioner
(PP). Control valve PCV91 is ATC (Air-to-Close) .The process air finally discharges to
atmosphere via the process vent VP through PCV91 and the variable area flowmeter
FI92.
d) The pressure measured by the gauge pressure transmitter PT92 is controlled ON/OFF by
the ON/OFF pressure controller PIC92. PIC92 will switch to close the normally-open
(NO) solenoid valve PSV92, when the preset high pressure limit is exceeded. The
ON/OFF control valve PCV92 is ATC (Air-to-Close). Thus when the pressure in T92 or
its discharge pipeline is above the preset high limit, PIC92 switches to close PSV92,
cutting off the instrument air supply to the actuator of PCV92. PCV92 then opens to vent
(V) air to the atmosphere. The rate of discharge can be manually set at the manual valves
(MV92A, MV92B) at the common vent line (V) downstream of PCV92.
e) Note that both the control valves PCV91 and PCV92 are Air-to-Close (ATC) so that
when there is instrument air failure, they stay open to vent out any pressure inside the
plant.
PAD91 : The pressure at T91, measured by PT91, exceeds its preset Deviation
from the setpoint, whether above or below. The Deviation alarm limit
is set at DL1 at the “PID1” page or panel.
PAL91 : The pressure at T91, measured by PT91, drops below its preset Low
alarm limit. The Low alarm limit is set at PL1 at the “PID1” page or
panel.
1. Make sure the Instrument Air Supply (IAS) or AR91 is set at 26-28 psig. Adjust the
manual valve MV91 till rotameter FI92 is at flowrate of 30Nm³/Hr max. DO NOT
exceed the stated flowrate.
2. Check the pressure with PCV91 fully shut. The parameter PV1 at controller PIC91
(i.e. PT91) should be 22-27 psig. Reset AR91 if the pressure is insufficient.
3. Check the flowrate with PCV91 fully open. The parameter PV1 at controller PIC91
(i.e. PT91) should be less than 5-6 psig and the flowrate at FI92 is not more than the
recommended flowrate. Readjust MV91 for maximum flowrate.
4. Make sure the valve Positioner (PP) at PC91 is ON and connected. With PIC91 in
Manual (M) mode, stroke the control valve PCV91 manually with MV = 100%, 50%
and 0% and note that the corresponding valve stem position at its stem indicator scale
is 0%, 50% and 100% opened.
5. With PIC91 in the Manual (M) mode, open the control valve PCV91 fully with
MV= -6.3%. For confirmation, check the control valve stem position at PCV91.
Take note of the minimum pressure PV1 (in PIC91). Concentrate on the Pressure PID
panel controller PIC91/PIC92 and the recorder PR91.
6. Check that vessels T91 and T92 are connected for air to flow in series from one vessel
to the next. Check their respective pressure at the pressure gauges PG91 and PG92.
The manual By-pass valve B92 around T92 should be fully shut. The final manual
discharge valve (VP) downstream of the pressure control valve PCV91 should be fully
opened.
7. Start the recorder PR91 by pressing the ‘RCD’ pushbutton at the front of the recorder
with its swing front cover opened. Note that PT91 response is shown by the Red pen
(Channel 1), Input Range: % of 0-25 psig. The recorder chart drive is preset for ‘fast
speed’ (500mm/Hr).
8. Access the PID values in the pressure PID controller PIC91, at the PID1 page or
panel. Set the following first (I) trial PID values.
PB1 = 70 %, TI1 = 40 secs, TD1 = 0
9. Adjust the setpoint SV to 18 psig (72%) at PIC91. Make sure the chart drive of the
recorder PR91 is running. Otherwise, press the “RCD” button at the front of the
recorder with its swing front cover opened.
10. Transfer PIC91 to Auto (A) mode and watch the response at the recorder PR91 till it
is steady at its setpoint SV to within ± 0.1 psig or continues to oscillate even after 3
cycles.
11. Continue the experiment for both 2-capacity and 1-capacity processes using the
following settings:
14. In order to check for process inlet load disturbance, carefully monitor the response. If
the response tends to oscillate outside the desired control band of ±0.1 psig (i.e. below
8.9 and above 9.1 psig for SV = 9 psig; OR below 17.9 and above 18.1 psig for SV = 18
psig); switch PIC91 to Manual (M) mode and observe if the pressure i.e. process air
inlet supply is still oscillating.
Note: Oscillation of process air inlet supply is a load disturbance at the process inlet.
15. If the load disturbance does occur, then the PID values (70% / 40 sec/ 0 sec) may have
slowed down the controller action, till it is slower than the process inlet disturbance.
Thus, try a faster TI i.e. set TI1 = 10 to 20 secs instead of 40 secs, for faster setpoint
recovery. Observe similarly for any improvement.
4.0 RESULTS/DISCUSSION
Relevant portions of the recorder chart responses should be submitted as results of the
experiment, with the following pertinent data marked on the corresponding chart recording:-
The Recorder chart speed is occasionally printed on the chart, for example at
500 mm or 0.139 mm or 7.2 secs
Hr sec mm
a) Study and compare the different pressure responses for different PID values.
Calculate the time constant and dead time for each response.
d) In your opinion, is PID a good controller for gas pressure control? State your
reason(s).