Вы находитесь на странице: 1из 3

ICHALKARANJI POWERLOOM MEGA CLUSTER LTD.

,
ICHALKARANJI.
TAL- HATKANANGLE, DIST- KOLHAPUR.

Plot No. 1-7/B, Laxmi Co-op Industrial Estate, Hatkanangale – 416 109, Kolhapur
Dist.

Website: www. ichmegacluster.com

Email:ich.megacluster@gmail.com

Ref No: ICPM/CHILLER/2

TENDER NO D2

TENDER SPECIFICATIONS
CHILLER FOR ICHALKARANJI POWERLOOM MEGA CLUSTER
LTD., AT ICHALKARANJI, TALUKA HATKANANGLE, DIST.
KOLHAPUR, STATE- MAHARASHTRA, INDIA.
Technical Specifications of 1 No. Air Cooled Chilling Plant for Cold Pad Batch Machine
Having Scroll Chiller of 30 TR (7.5 TR x 4 Nos. OR 15TR * 2 nos.) Capacity with Scroll
Type Compressors.

A. CHILLER
1. System Industrial Process Chiller
2. Model No. TO BE SPECIFIED
3. Flow Rate 24000 LPH
4. Inlet Temperature to Chiller 15 Deg C.
5. Outlet Temperature from Chiller 10 Deg C.
6. Refrigeration Load 30TR (5.5 TR x Nos.)
7. Capacity of Chilled Water Tank Min. 300 Ltrs. SS 304 (Duly Insulated)
8. Chiller Type Brazed PHE
9. Evaporator SS Brazed Plate Heat Exchanger
10. Condenser Type Shell & Finned Tube Type
11. Pump 460 LPM @ 3 Bar Centrifugal Pump with
SS Impeller
12. Refrigerant R-22
13. Refrigeration Compressor Scroll Type
14. Refrigerant Parts 1. Drier.
2. Expansion Device : Expansion Valves
3. Pressure Gauge at Suction and
Discharge
4. Accumulator
15. Control Fully Automatic
16. Safety Interlocks 1. L.P. Switch & Gauge
2. H.P. Switch & Gauge
3. Digital Temperature Controller
4. Chilled Water Failure Trip (Pump
Electrical Interlock)
5. Compressor and Pump Overload Trip
17. Structure MS Frame with MS Sheets (with Primer
and PU Paints) All wetted Parts in SS 304.
B. COMPRESSOR
1. Make Danfoss / Emerson
2. Type Scroll
C. ELECTRICAL SPECIFICATION
1. Power Supply 400 +/- 10% / 3 Phase / 50 HZ +/- 5%
2. Connected Load TO BE SPECIFIED
3. Protection IP 54
4. Electrical Components 1. Contactors
2. MCB
3. Connectors
4. Transformer
5. Wiring
D. TEMPERATURE CONTROLLER Digital Type with Display
E. SAFETY COMPONENTS 1. Single Phase Preventer.
2. Pump Motor Overload Protection.
3. MPCB for Compressor.
4. Electronic Water Level Controller.
5. Flow Switch.
6. Anti Freeze Thermostat
F. LED INDICATION 1. Power ON.
2. Compressor ON “For each Circuit”
3. Pump ON.
4. Water Level Flow.
5. HP / LP “Trip” for each circuit.
G. GENERAL CONDITIONS
1. Design Temperature 45 Deg Ambient
2. Noise Level Less than 80 db at 1.0 m distance
3. Condensor Fan Control
4. Condensor Fan Type
H. MATERIAL OF CONSTRUCTION
1. Chilled Water Tank SS 304, Duly Insulated.
2. Structure MS Frame with MS Sheets (with Primer
and PU Paints) All wetted Parts in SS 304.
3. MOC of Shell Copper
4. Pressure Testing At 350 PSI