Вы находитесь на странице: 1из 4

TUGAS KENDALI SISTEM TENAGA LISTRIK

NOMOR URUT : 2

Dik : G1 = 650 MW
650 MW 550 MW
G2 = 550 MW
~
R1 = 6 R1 6 %
Load
R2 = 4 1000 MW
R2 4 %
G1 output = 550 MW ~
Δ PL= 100 MW
G2 output = 450 MW 550 MW 450 MW

NVA base = 2000 MW

Δ PL = 100 MW

Dit: D=0

Gen1.........MW?

Gen2..............MW?

D = 0,8

Gen1................MW?

Gen2............MW?

Peny : 𝑼⁄
𝑫=𝟎
𝟐𝟎𝟎𝟎
𝑹𝟏 = 𝑿 𝟎, 𝟔 % = 𝟎, 𝟎𝟏𝟖 pu
𝟔𝟓𝟎

𝟐𝟎𝟎𝟎
𝑹𝟏 = 𝑿 𝟎, 𝟒 % = 𝟎, 𝟎𝟏𝟒𝟓 pu
𝟓𝟓𝟎

𝟏𝟎𝟎
∆ 𝑊𝑠𝑠 = lim𝑆→0 𝑆 ∆ 𝑊𝑠𝑠 ∆𝑷𝑳 = = 𝟎, 𝟎𝟓 𝒑𝒖
𝟐𝟎𝟎𝟎

1
= − ∆𝑃𝐿 ( )
𝐷+1⁄𝑅 + 1⁄𝑅
1 2

1
= −0,05 (1 )
⁄0,018+ 1⁄0,0145

= −𝟎, 𝟎𝟎𝟎𝟒 𝒑𝒖

MUH. ARFAN YAHYA/D032172001


TUGAS KENDALI SISTEM TENAGA LISTRIK
∆𝑓𝑠𝑠 = −0,0004 × 60 𝐻𝑧

= 0,024 𝐻𝑧

𝒇𝑴𝑾 = (𝟔𝟎 − 𝟎, 𝟎𝟐𝟒) = 𝟓𝟗, 𝟗𝟕𝟔 𝑯𝒛

Perubahan Suplai dari G1 dan G2 adalah


− (∆ 𝑊𝑠𝑠) − (− 0,0004)
∆ 𝑃1 = = = 0,0222 𝑝𝑢
𝑅1 0,018

= 0,0222 × 2000 = 44,4 𝑀𝑊

𝑮𝟏 𝒎𝒆𝒏𝒚𝒖𝒑𝒍𝒂𝒊 = 𝟓𝟓𝟎 + 𝟒𝟒, 𝟒 = 𝟓𝟗𝟒, 𝟒 𝑴𝑾


− (∆ 𝑊𝑠𝑠) − (− 0,0004)
∆ 𝑃2 = = = 0,0275 𝑝𝑢
𝑅2 0,0145

= 0,0275 × 2000 = 55 𝑀𝑊

𝑮𝟐 𝒎𝒆𝒏𝒚𝒖𝒑𝒍𝒂𝒊 = 𝟒𝟓𝟎 + 𝟓𝟓 = 𝟓𝟎𝟓 𝑴𝑾

𝑮𝟏 + 𝑮𝟐 = 𝟓𝟗𝟒, 𝟒 + 𝟓𝟎𝟓 = 𝟏𝟎𝟗𝟗, 𝟒 𝑴𝑾

𝑼⁄
𝑫 = 𝟎, 𝟖

∆ 𝑊𝑠𝑠 = lim𝑆→0 𝑆 ∆ 𝑊𝑠𝑠

1
= − ∆𝑃𝐿 (𝐷+1 )
⁄𝑅1 + 1⁄𝑅2

1
= −0,05 (0,8 + 1 )
⁄0,018+ 1⁄0,0145

= −𝟎, 𝟎𝟎𝟎𝟑𝟗𝟖 𝒑𝒖

∆𝑓𝑠𝑠 = −0,000398 × 60 𝐻𝑧

= 𝟎, 𝟎𝟐𝟑𝟖𝟖 𝑯𝒛

𝒇𝑴𝑾 = (𝟔𝟎 − 𝟎, 𝟎𝟐𝟑𝟖𝟖) = 𝟓𝟗, 𝟗𝟕𝟔 𝑯𝒛

Perubahan Suplai dari G1 dan G2 adalah


− (∆ 𝑊𝑠𝑠) − (− 0,000398)
∆ 𝑃1 = = = 0,0221 𝑝𝑢
𝑅1 0,018

= 𝟎, 𝟎𝟐𝟐𝟏 × 𝟐𝟎𝟎𝟎 = 𝟒𝟒, 𝟐 𝑴𝑾

𝑮𝟏 𝒎𝒆𝒏𝒚𝒖𝒑𝒍𝒂𝒊 = 𝟓𝟓𝟎 + 𝟒𝟒, 𝟐 = 𝟓𝟗𝟒, 𝟐 𝑴𝑾

MUH. ARFAN YAHYA/D032172001


TUGAS KENDALI SISTEM TENAGA LISTRIK
− (∆ 𝑊𝑠𝑠) − (− 0,000398)
∆ 𝑃2 = = = 0,0274 𝑝𝑢
𝑅2 0,0145

= 𝟎, 𝟎𝟐𝟕𝟒 × 𝟐𝟎𝟎𝟎 = 𝟓𝟒, 𝟖𝟗 𝑴𝑾

𝑮𝟐 𝒎𝒆𝒏𝒚𝒖𝒑𝒍𝒂𝒊 = 𝟒𝟓𝟎 + 𝟓𝟒, 𝟗𝟖 = 𝟓𝟎𝟒, 𝟖𝟗𝑴𝑾

𝑮𝟏 + 𝑮𝟐 = 𝟓𝟗𝟒, 𝟐 + 𝟓𝟎𝟒, 𝟖𝟗 = 𝟏𝟎𝟗𝟗, 𝟎𝟗 𝑴𝑾

Unit 1 mensuplai 594,2 MW dan unit 2 504,89 MW, pada frekuensi 59,976 Hz. Jadi ada
penambaahn daya 99,09 MW, yang mana ini lebih kecil/hampir sama dari penambahan daya
yang terjadi pada sistem yaitu 100 MW.

MUH. ARFAN YAHYA/D032172001


16/03/18 19:08 C:\Program Files\MATLAB\R2016a\bin\KSTL.m 1 of 1

SB=2000;
f0=60; p01=550/SB; p02=450/SB;
R1 = SB/650*0.05;
R2 = SB/550*0.05;
DPL=100/SB;
disp('(a) D = 0')
Dw=-DPL/(1/R1+1/R2);
Df=Dw*f0; f=f0+Df;
Dp1=-Dw/R1;
Dp2=-Dw/R2;
p1=(p01+Dp1)*SB;
p2=(p02+Dp2)*SB;
disp('Tugas II')
%p=0.2:0.01:0.7;
p=0:0.01:0.7;

f1=-0.071*p+1.0426;
f2=-0.083*p+1.0415;
f0g=ones(1, length(p));
fg=0.9996*ones(1, length(p));
y=0.98:.001:0.9996;
p1g=0.594*ones(1, length(y));
p2g=0.505*ones(1, length(y));
plot(p, f1, p, f2, p, f0g, p, fg, p1g, y,'--', p2g, y,'--'), grid
xlabel('Per-Unit Output'), ylabel('f,pu')
text(0.255, 1.024, 'Unit # 1')
text(0.185, 1.012, 'Unit # 2')
text(0.145, 0.993, '0.9996')
disp('(b) D=0.8')
D=0.8;
Dw=-DPL/(1/R1+1/R2+D);
Df=Dw*f0; f=f0+Df;
Dp1=-Dw/R1;
Dp2=-Dw/R2;
disp('New Generation')
p1=(p01+Dp1)*SB;
p=(p02+Dp2)*SB;
disp('Change in load due to frequency drop')
DPL=(Dp1+Dp2)*SB - 90;

Вам также может понравиться