Instructions:
1 Kindly do not alter the contents of the cell which contain formulas
2 Click the appropriate TABS to select/go to the respective sheets.
3 Cells/Columns colour coding
Data Contain standard / Formulas / Results
Data to be Entered Manually
Select from Drop down
Resp. Dept. Prepared by Sheet
1
Doc No: PTC-BT-D-010-01, Rev. 0 Date Approved by Rev.
1.0 GENERAL
1.1 Ambient temperature 40
1.2 Altitude Mtrs ≤ 1000
1.3 Reference standard IEEE 946 / IEEE 485 / IEE 450 / IEEE
1115 / IEC 62040 / IEEE 446 / IEC
60146 / IEC 60529
1.4 Input voltage variation (positive Tolerance) % 10
1.5 Input voltage variation (Negative Tolerance) % 10
1.6 Noise level @ 1 Mtr dB(A) 90
1.7 Location Indoor
1.8 Material of construction CRCA
1.9 Paint shade RAL 7035
1.10 Busbar material Copper
1.11 Busbar size Supplier to furnish
1.12 Name plate Required
1.13 Danger plate Required
1.14 Live parts isolation Required
1.15 Cable entry Bottom
1.16 Cable gland plate 3mm thick CRCA sheet
1.17 Lifting hooks Required
1.18 Panel lamp with door limit switch and space Required
heater with thermostat
2.0 BATTERY
2.1 Type VRLA
2.2 Battery configuration 1x100% Battery
2.3 Type of mounting Floor
2.4 Access Front
2.5 Capacity Ah As per RFQ
2.6 Battery back-up 2 Hrs
2.7 Nominal voltage 110
2.8 Maximum voltage 121
2.9 Minimum voltage 99
2.10 End cell voltage 1.85
2.11 No. Of cells Vendor to specify
2.12 Minimum electrolyte temperature ºC 25
2.13 Ageing factor % 25
2.14 Design margin % 10
2.15 Battery fuse box Required
2.16 Battery interconnection flexible DC cable Required
2.17 Between battery, fuse box and charger flexible Required
DC cable
2.18 Cable length Mtrs 30
2.19 Battery sizing calculation As per the Attachment
2.20 Dimension Supplier to Furnish
2.21 Weight Supplier to Furnish
Page 2 of 4
Resp. Dept. Prepared by Sheet
1
Doc No: PTC-BT-D-010-01, Rev. 0 Date Approved by Rev.
3.0 DCDB
3.1 Location Indoor
3.2 Degree of protection IP 41
3.3 Type of mounting Floor
3.4 Form of construction Form-2
3.5 Incoming ammeter Required
3.6 Incoming voltmeter Required
3.7 Feeder list
3.7.1 Incomer
Incomer Qty Nos. 1
Incomer MCCB Rating A 125
3.7.2 Bustie
Bustie Rating A -
3.7.3 Outgoing Feeders (DP, MCB)
6A Nos. 6
16A Nos. 25
32A Nos. 5
63A Nos. 4
Page 3 of 4
Resp. Dept. Prepared by Sheet
1
Doc No: PTC-BT-D-010-01, Rev. 0 Date Approved by Rev.
Page 4 of 4