TEST REPORT

Standard as per : BDS 899-3, BS-6500 & IEC 60228 Date : 28.03.2018
Size of Cable : 3X2.5 rm (mm2) Color : White
Type of Cable : Flexible-FR Length : 5000 Meter
Voltage Grade : 300/500 Volts Client : Walton Hi-Tech. Industries Ltd.
M/C : Extruder 80 mm B
SL. Description of test Unit Required Value Observed Value
No.
Visual Check - Smooth OK
Nominal cross-sectional area of conductor mm² 2.5 2.5
Number of core’s no. 03 03
Color of core’s - Red, Yellow & Blue Red, Yellow & Blue
Conductor: (Class-5)
Material - Copper Copper
Physical Test
01 Shape of conductor - Stranded Stranded
circular circular
Number of wire no. 50 50
Diameter of Wire 0.250 0.250
Insulation:-
Material - PVC Flame Retardant PVC Flame Retardant
Nominal thickness of insulation mm 0.8 0.82
Minimum Thickness of Insulation mm 0.62 0.75
Sheath:-
Material - PVC Flame Retardant PVC Flame Retardant

Nominal thickness of Sheath mm 1.1 1.15


Minimum Thickness of Sheath mm 0.835 1.09
Approximate overall diameter of cable mm 10.5 10.5
Max. D.C resistance of conductor at 20⁰ C
m
Ω/Km 7.98 7.17

Electrical Test Min. Insulation resistance constant ki at 20⁰ C


m
MΩ.km 35 119
02
A.C Spark Test 6 kv No Break Down Withstood
A.C High Voltage Test for 05 minutes 1.5 kv No Break Down Withstood
Before ageing:
03 Mechanical Min. Tensile strength of PVC FR Insulation N/ mm² 12.5 15.85
Test Min. Elongation of PVC FR Insulation % 150 232
Min. Tensile strength of PVC FR Sheath N/ mm² 12.5 15.75
Min. Elongation of PVC FR Sheath % 150 235
04 Flame Test Unaffected portion from lower edge of the clamp mm 50 387
should be minimum 50 mm
05 Oxygen Index Minimum Oxygen Index % 29 30.87

Remarks: The above test results are found Passed.

Tested By Checked by
Approved by