Академический Документы
Профессиональный Документы
Культура Документы
Start-Up Procedures
Open fully the pipelines PLI and PLII at their various manual valves.
Close fully the manual by-pass valve around the control valve FCV91
and the ON/OFF control valve FCV90.
7. The pipeline PLI has two discharge manual valves, VF and MV901.
Open the vent VF and close the valve MV901.
8. Make sure the valves MV900A and MV900D are open and valves
MV900B and MV900C are shut.
9. Place the panel controller FIC91 in the Manual (M) mode. Make sure
the control valve positioner PP is connected (i.e. Not by-passed).
10. Open fully the control valve FCV91 by setting the MV of FIC91 to
-6.3%.
11. Shut fully the manual valve MV900A and set AR900 to the pressure
indicated at AR900.
12. Adjust the manual valve MV900A till the air flow rate is about 50
kg/hr (Read the flow rate from PV of FIC91).
13. Step (10), (11) and (12) have set the process air supply pressure and
flow rate. DO NOT re-adjust AR900 and MV900A hereafter.
14. Check that vent valve and bottom drain valve of vessel T90 are shut.
Set MV = 106.3% at FIC91 to fully shut the control valve FCV91.
15. Check control valve FCV91 (in the plant) is fully shut and FI911
reads the air volumetric flow rate as ZERO. Also check the mass flow
rate Fm at FIC91 is ZERO.
16. Now set the MV = 50% at FIC91 and check control valve FCV91 (in
the plant) is 50% opened. 17. Note the variables that are recorded in each
channel of the recorder FPTR91.
Red Pen - Mass flow rate (kg/hr)
Green Pen - Volumetric flow rate (m3/hr)
Blue Pen - Temperature (oC)
5. Examine the chart response for the uniform oscillation. New PID value
from tuning procedures can be obtained as follows:
PB = 2 x PB*, TI = Tn*/1.2
6. To test this new PI controller settings, set this value into FIC91 (in
Auto mode). Perform the test with a pulse disturbance. Increase PB value
to damp the oscillation and fine tune the PB and TI values to get as close
to Quarter Amplitude Damping response.
Shutdown Procedures