Вы находитесь на странице: 1из 2

_____________________________________________________________________

Company Name :
Job Description : Assignment 3
Designed by : Edwin Leon (CF150032)
Date and Time : Tuesday, March 13, 2018 10:03:02 AM
(License Number: NetMaster-SN23-C0-1)
_____________________________________________________________________

MATERIAL AND DESIGN DATA


Load Allowance = 10.0 %
Minimum Steel Percentage Permitted = 0.13 %
Maximum Steel Percentage Permitted = 4.00 %
Minimum Rebar Spacing Allowed = 100 mm
Maximum Rebar Spacing Allowed = 250 mm
Enhanced Shear Multiplier = 1.5

Lean Concrete
Code of Practice fcu (N/mm²) Ec, (N/mm²) fy (N/mm²) γc γs
fcu (N/mm²)
BS8110 : 1997 30 10 24597 460 1.5 1.05

Cover (mm) Conc. Unit Weight (kN/m³) Steel Unit Weight (kg/m³)
50 24 7860

BRIEF CALCULATION REPORT FOR PILE CAP DESIGN AT FLOOR gb (3D)

PILE FOOTING DESIGN SUMMARY TABLE FOR FLOOR gb


Number of Pile Cap on Plan = 14
Number of Pile Cap Pass = 14

Dimension AsReq Rebar Pile


Grid D.L. L.L. W.L. Mx My
(B × L × H) XDir YDir XDir YDir No. Type
P1
Square
C11:(5, 123.8 3.9 0.0 0.0 0.0 600×600×300 234 234 3T12 3T12 1
150×150
A)
P1
Square
C14:(5, 118.8 3.2 0.0 0.0 0.0 600×600×300 234 234 3T12 3T12 1
150×150
F)
P1
Square
C4:(2,F 161.5 8.1 0.0 0.0 0.0 600×600×300 234 234 3T12 3T12 1
150×150
)
P2
Square
C12:(5, 334.7 20.9 0.0 0.0 0.0 900×600×400 312 468 3T12 5T12 2
150×150
B)
P2
Square
C13:(5, 332.3 20.3 0.0 0.0 0.0 900×600×400 312 468 3T12 5T12 2
150×150
E)
P2
Square
C8:(4,B 277.4 27.9 0.0 0.0 0.0 900×600×400 312 468 3T12 5T12 2
150×150
)
P2
Square
C7:(4, 313.9 22.8 0.0 0.0 0.0 900×600×400 312 468 3T12 5T12 2
150×150
A)
P2
Square
C1:(2, 211.1 16.2 0.0 0.0 0.0 900×600×400 312 468 3T12 5T12 2
150×150
A)
License Number: NetMaster-SN23-C0-1
1/2
P2
Square
C9:(4,E 280.3 29.0 0.0 0.0 0.0 900×600×400 312 468 3T12 5T12 2
150×150
)
P2
Square
C10:(4, 332.9 25.0 0.0 0.0 0.0 900×600×400 312 468 3T12 5T12 2
150×150
F)
P3
Square
C5:(3,B 357.0 33.0 0.0 0.0 0.0 900×840×450 491 527 5T12 5T12 3
150×150
)
P3
Square
C2:(2,B 466.3 30.6 0.0 0.0 0.0 900×840×450 491 527 5T12 5T12 3
150×150
)
P3
Square
C3:(2,E 423.2 24.2 0.0 0.0 0.0 900×840×450 491 527 5T12 5T12 3
150×150
)
P3
Square
C6:(3,E 382.3 38.6 0.0 0.0 0.0 900×840×450 491 527 5T12 5T12 3
150×150
)
Note
D.L./L.L./W.L. - Axial Force due to Dead Load, Live Load and Wind Load, kN(Including 10 % Load Allowance)
Mx/My - Moment About X-X/Y-Y Axis, kNm
Dimension - Dimension of the Pile Cap, mm
AsReq - Area of Reinforcement Required, mm²
Rebar - Steel Reinforcement Provided, mm²
XDir/YDir - Span Along X/Y Direction
Pile No. - Number of Pile Unit
Pile Type - Type of Pile and Pile Dimension, mm

FOOTING LOADING SUMMARY TABLE FOR FLOOR gb


∑ D.L. ∑ L.L.
Without Load Allowance 3741.3 276.0
With Load Allowance of 10% 4115.5 303.6
Note: ∑ D.L. - Sum of Dead Load, ∑ L.L. - Sum of Live Load

Summary of Column Loading without Load Allowance :


Total Footing SelfWeight = 70.5 kN
Total Column Dead Load Reaction = 3741.3 kN
Total Column Live Load Reaction = 276.0 kN
Total Column Dead Load Reaction with Footing Self-Weight = 3811.8 kN

Summary of Column Loading with Load Allowance of 10 Percent :


Total Dead Load (with Footing Self-Weight) = 4186.0 kN
Total Live Load = 303.6 kN

Summary of Total Loading Without Load Allowance :


Total Footing Self-Weight of whole Key Plan = 70.5 kN
Total Dead and Live Load of Whole Key Plan = 4087.8 kN

Total Dead Load Reaction from Stump and Wall = 3741.6 kN


Total Live Load Reaction from Stump and Wall = 276.0 kN

License Number: NetMaster-SN23-C0-1


2/2

Вам также может понравиться