Вы находитесь на странице: 1из 2

FEATURES Series 1500 dc-to-dc converters provide a well-regulated dc output

.400-WATT and 200-WATT voltage from station batteries or other widely fluctuating dc sources. This
MODELS output is galvanically isolated from the source and chassis and, therefore,
may be connected either as a positive or a negative output. Applications
.HEIGHT 3.45" include powering radio transceivers, telecommunications equipment,
(2 RACK SPACES) supervisory control systems and other critical electronic loads.
Designed for relay rack mounting, these state-of-the-art converters
.REGULATED, ADJUSTABLE achieve superior electrical performance in a low profile enclosure.
OUTPUT VOLTAGE Conservatively rated and very efficient, Series 1500 converters will
operate continuously at any load within their rating over a wide ambient
.80%-85% EFFICIENCY temperature range with simple convection cooling. Exceptionally effec-
tive noise suppression and filtering allow these converters to be used in
.INPUT -OUTPUT ISOLATION
many applications considered too noise-sensitive for other transistor-
.-30°C TO 60°C switching power converters. Standard options let users adapt converters
to specific system requirements, including paralleling for redundancy
TEMPERATURERANGE
and for additional power.
.VERY LOW RIPPLE AND Six 48-volt input versions are available with different combinations
NOISE of dc output voltage and output power.
Table 1

Input Voltage Input Output Voltage Output


Range Current' Adjustment Range Current Model
(VDC) (ADC) (VDC) (ADC) Number'
5.2 0-15 15xx-48-13-15
12-14 (13 nominal)

10.3 0-30 15xx-48-13-30


4.8 0-8 15xx-48-24-8
22-26 (24 nominal)
9.5 0-16 15xx-48-24-16
40-58
4.7 0-4 15xx-48-48-4
44-52 (48 nominal)

9.4 0-8 15xx-48-48-8


4.6 0-1.5 15xx-48-130-1.5
1123.5-136.5 (130 nominal)
9.4 0-3 15xx-48-130-3
'Typical current at full load, nominal input and output voltages
2See reverse side for complete model numbering information

DESIGNERS AND MANUFACTURERS OF SOLID-STATE POWER CONVERSION EQUIPMENT


SPECIFICATIONS

Input Voltage
40 Vdc to 58 Vdc (48 Vdc nominal)

Output Voltage and Current


The nominal output voltage, the
adjustable output voltage range, and
output current for standard models
are shown in Table 1.

Output Voltage Regulation


Versus line: :!:0.1 %
Versus load: :!:0.5%

Output Voltage Ripple and Noise


3 millivolts rms (typical)
30 millivolts peak-to-peak (typical)

Isolation and Grounding


Mutual electrical isolation is
provided between the input circuit, 19 OR 23

the output circuit, and chassis 0


0
0 r lllllll HIIIIIIIJ 00000
r"iJl
ground. 11
3.45
~ O~
+- ++-
Protection 0 INPUT ~ OUTPUT LQ 1
Protection against overloads, short
circuits, and output overvoltages is
provided electronically. Recovery to Rear View
normal operating conditions is auto- (COVERPANELREMOVED)
Fig. 1 Converter shown with optional meters, auxiliary contacts, and
matic upon removal of the overload
paralleling diode with heatsink.
or short-circuit fault. Following an
overvoltage shutdown, input power
to the converter must be removed locking nut is provided to adjust the give the basic model number (1501
and reapplied to resume converter output voltage level. An optional for plain front panel, 1502 for output
operation. Protection against voltmeter and ammeter display the meter option), the nominal input
accidental reversal of the dc input- dc output. voltage, the nominal output voltage,
voltage polarity during installation is and the maximum load current.
Physical Characteristics Standard options other than meters
provided by a shunt diode working
Refer to Fig. 1 for overall dimensions. are specified by an additional suffix:
in conjunction with the front-panel
Weight is less than 15 pounds. M1 designates paralleling diode
circuit breaker.
Brackets are provided for 19-inch or plus auxiliary contacts, M2 desig-
Ambient Temperature Range 23-inch relay rack mounting. A nates load sharing, and M3 combines
Operating: -30°C to 60°C cover panel protects the recessed paralleling diode, auxiliary contacts
rear panel and wiring connections. and load sharing. For example,
(convection cooling)
Storage: -40°C to 95°C Model 1502-48-13-30-M3 is a 48-
STANDARD OPTIONS
volt to 13-volt converter with a 30-
Efficiency .Output voltmeter and output
ampere maximum load rating. It is
The efficiency reaches 80% at ammeter
provided with output meters, paral-
approximately 15% of full load and .Output series diode for parallel-
leling diode, auxiliary contacts and
remains above 80% for most of the redundant operation of multiple
load sharing capabili~
load range. The no-load input current converters
is approximately 100 milliamperes. .Auxiliary Form C contacts for OTHER WILMORE
Heat dissipation is approximately remote indication of improper PRODUCTS
340 BTU/hour for 400-watt models output (converter fail) For information about other Wilmore
and 170 BTU/hour for 200-watt .Balanced load sharing between dc-to-dc converters or for informa-
models. converters being paralleled for tion about other power-conditioning
additional power products such as switching power
Front-Panel Controls and
supplies, dc-to-ac inverters, and
Indicators MODEL NUMBERING
A combination circuit breaker and INFORMATION uninterruptible power systems, please
contact our sales department.
ON/OFF switch is provided for input Series 1500 converters are identified
power. A potentiometer shaft with by four numbers. In sequence, these

WILMORE ELECTRONICS CO. , INC.


P.o. Box 1329, Hillsborough, N.C. 27278 .Telephone (919) 732-9351 .FAX (919) 732-9359