3@m ABOVE CROWN LEVEL.
Poyun CeYLE ona UL
UI CUNEAL TL PERCE. HHL SLEURY CUAL OHALE UL Art cine
WITHIN THE TIME INTERVAL ie WHEN THE CONCRETE SURFACE IS
TOTALLY DRY (BETWEEN SUCCESSIVE COATING APPLICATION),
SPECIFIED BY Be EE Ren - OTe DRY HLM
THICKN,
5.ALL_ EXPOSED FOUNDATION (ABOVE GRAI ANCHOR BOLTS, & BAS!
PLATE SHALL BE COATED ATING. THE a pane
SHALL COVER THE GROUT, BASE PLATES AND EX ANCHOR:
BOLTS AND AT LEAST 306mm OF STEEL MONOPOLE. THE COATING
APPLICATION SHALL EXTEND CONTINUOUSLY 380 mm BELOW
GRADE AFTER CURING OF FIRST COAT OF COAL TAR EPOXY
COATING. THE MINIMUM DRY FILM THICKNESS OF COATING SHALL
BE Imm. THE PRIMER SHALL BE SUITABLY SELECTED FOR
CONCRETE SURFACES.
a
INCHOR BOLTS SHAI E THERMOWELDED TO REBARS AT MINIMUM
TWO POINTS. REBARS SHALL BE CONNECTED TO MAIN GROUNDING
GRID AT MINIMUM TWO POINTS. ALL THERMOWELD SHALL BE COATED
WITH TWO (2)COATS OF COAL TAR EPOXY AND MASTIC TAPED.
7. MINIMUM CLEAR COVER TO REINFORCEMENT SHALL BE 75+10mm,
THE CONCRETE COVER SHALL BE OBTAINED WITH THE HELP OF
PVC SPACERS AT NOT MORE THAN 1.5m SPACING.