Академический Документы
Профессиональный Документы
Культура Документы
TECHNICAL MANUAL
Components
Design
Installation
Maintenance
Recharge
Figure Figure
Description Page Rev Date Description Page Rev Date
No. No.
Cylinder and Valve Proper measurement
2-1 Assembly Dimensions 2-1 5 01/01/13 and nozzle placement
and Table 3-4 3-2 5 01/01/13
for smaller to larger
transition ducts.
Model BFR-VLV Valve
2-2 2-2 5 01/01/13
Assembly Upper / Lower Plenum
3-5 3-2 5 01/01/13
Protection
Model BFR-CAP Valve
2-3 2-2 5 01/01/13
Cap Assembly Electrostatic Precipitator
3-6 3-2 5 01/01/13
Protection.
Model BFR-DAK
2-4 2-2 5 01/01/13
Discharge Adaptor Kit Plenum Nozzle
3-7 3-3 2 4/20/10
Placement and Aiming
Model SRM Systems
2-5 2-3 5 01/01/13
Releasing Module Low Proximity 12” (30.5
3-8 3-4 5 01/01/13
cm) x 24” (61 cm) Range
Model BFR-AC-S and
2-6 BFR-AC-L Nitrogen 2-3 5 01/01/13 High Proximity 24” (61
Actuation Cartridges 3-9 3-4 5 01/01/13
cm) x 24” (61 cm) Range
Model MB-1 Shown Low Proximity 24” (61
2-7 2-3 5 01/01/13 3-10 3-4 5 01/01/13
With BFR-5 Cylinder cm) x 24” (61 cm) Range
Model MB-2 Shown 36” (91 cm) x 24” (61
2-8 2-4 5 01/01/13 3-11 3-5 5 01/01/13
With BFR-20 Cylinder cm) Range
30” (76 cm) x 24” (24
Model RPS-M Remote 3-12 cm) Combination 3-5 5 01/01/13
2-9 2-4 5 01/01/13
Mechanical Pull Station Range/Griddle
Model BFGV-Series 24” (61cm) x 24” (61 cm)
2-10 2-4 5 01/01/13 3-13 Four Burner Range with 3-5 5 01/01/13
Mechanical Gas Valve
Back-shelf
Model FLB-1, 10” (25
2-11 cm) Fusible Link Bracket 2-5 5 01/01/13 12” (30.5 cm) x 24” (61
Assembly 3-14 cm) Two Burner Range 3-5 5 01/01/13
with Back-shelf
Model FLH Fusible Link
2-12 2-5 5 01/01/13
Holder 24” (61cm) x 24” (61 cm)
3-14a Four Burner Range w/ 3-6 5 01/01/13
2-13 Globe ML Fusible Link 2-5 5 01/01/13 Back-shelf, High Prox.
Figure Figure
Description Page Rev Date Description Page Rev Date
No. No.
Sample Radiant Series Link
3-24 Charbroiler Module 3-11 5 01/01/13 4-19 4-12 5 01/01/13
Installation
Protection
Terminal Bracket
4-20 4-12 5 01/01/13
Connection
Proper Detector Fusible Link Holder
4-21 4-12 5 01/01/13
3-26 Placement Appliances 3-14 5 01/01/13 Connection
and Duct
Fusible Link Holder
Cylinder and Mounting 4-22 4-13 5 01/01/13
4-1 4-1 5 01/01/13 Connection
Bracket Installation
Fusible Link Line
4-23 4-13 5 01/01/13
SRM Mounted Directly Termination In Plenum
4-2 4-2 5 01/01/13
to Cylinder Valve
Fusible Link
4-24 4-13 5 01/01/13
Systems Releasing Connection
4-3 Module Shown Actuating 4-3 5 01/01/13
Typical Fusible Link
a Single Agent Cylinder 4-25 4-13 5 01/01/13
Installation
Multiple Cylinder
Actuation Using the Fusible Link Line
4-4 4-3 5 01/01/13 4-26 4-14 5 01/01/13
Systems Releasing Installation
Module
Remote Pull Station
Buckeye Shielded 4-27 4-14 5 01/01/13
Installation
4-5 Cable Installation 4-4 5 01/01/13
Guidelines Overview 4-28 Gas Valve Installation 4-15 5 01/01/13
Buckeye Shielded
4-6 4-5 5 01/01/13 Mechanical Pull
Cable
4-29 Station Cable 4-15 5 01/01/13
Cutting Buckeye Connection
4-7 4-5 5 01/01/13
Shielded Cable Two Methods of
Buckeye Shielded Connecting Fusible Link
4-30 4-16 5 01/01/13
Line to Fusible Link
4-8 Cable Minimum Bend 4-6 5 01/01/13
Ratchet
Radius
Connecting Fusible
Buckeye Shielded 4-31 4-16 5 01/01/13
Link Line to SRM
4-9 Cable Interface 4-6 5 01/01/13
Installation Detail Catch in “SET”
4-31a 4-16 5 01/01/13
Position
Buckeye Shielded
4-10 Cable Interface Typical 4-6 5 01/01/13 Tensioning Fusible
4-32 4-17 5 01/01/13
Connection Types Link Line
Figure
Description Page Rev Date
No.
Mechanical Gas
4-39 4-19 5 01/01/13
Valve in SET position
4-40 Setting Actuation Pin 4-20 5 01/01/13
Installing Nitrogen
4-41 4-21 5 01/01/13
Cartridge
Dating Nitrogen
4-42 4-21 5 01/01/13
Cartridge
Installing Systems
4-43 Releasing Module 4-21 5 01/01/13
Cover
Model BFR-VRK
6-1 6-1 5 01/01/13
Valve Rebuilding Kit
Model BFR-VRT,
6-2 6-1 5 01/01/13
Valve Rebuilding Tool
Chapter 1
General Information
Introduction System Temperature Limitations
The Buckeye Fire Equipment Kitchen Mister Fire The operating temperature range of the Kitchen Mister
o o o o
Suppression System is a pre-engineered wet chemical System is 32 F (0 C.) minimum to 120 F (49 C.)
restaurant fire suppression system as defined by the maximum.
NFPA-17A Standard for Wet Chemical Extinguishing
Systems. It is designed to protect commercial restaurant Listings and Approvals
cooking appliances, hoods, and ducts as described in
this manual. The Kitchen Mister Fire Suppression System is Listed
and Approved by the following agencies:
Installation and maintenance of the Kitchen Mister
System must be in compliance with the parameters set • Underwriters Laboratories, Inc. (Listed to the
forth in this manual and be performed by a factory requirements of UL-300/UL-1254) UL-EX 6885
trained, Authorized Buckeye Fire Equipment Distributor.
• Underwriters Laboratories of Canada, ULC-EX 6885
CAUTION • Approved by the New York City Fire Department
This technical manual can in no way be considered COA # 5550
sufficient to completely understand the proper
design, installation, and/or maintenance of the • ISO-9001 Registered
Kitchen Mister System. Buckeye Certified Training
is required to become Authorized to perform these Manufacturers Warranty
procedures. Buckeye Fire Equipment will not be
responsible for system(s) designed, installed, or
maintained by individuals or companies not trained Buckeye Fire Equipment warrants the Kitchen Mister
and Authorized by Buckeye Fire Equipment. System against defects in material and workmanship for
a period of one year from date of shipment to the
purchaser under normal use and service. Buckeye Fire
Equipment is not responsible for the installation and
How the Kitchen Mister Works maintenance of the system. All warranty claims must be
filed with Buckeye Fire Equipment within 30 days of the
The Kitchen Mister System utilizes a potassium based discovery of the defect to be valid.
liquid fire extinguishing agent specifically designed for
grease laden fires such as those associated with System Installation and Maintenance
restaurant cooking areas. The Kitchen Mister agent Requirements
works to suppress commercial kitchen fires in three
ways:
Any individual installing or performing maintenance on
1. The agent interrupts the chemical chain reaction the Kitchen Mister System MUST be; fully trained and
causing combustion, thus extinguishing the fire. Authorized by Buckeye Fire Equipment, have a complete
understanding of this manual in full, and have a complete
2. The agent is discharged in a very fine mist, cooling understanding of all local, state, and federal
the fire to below its auto-ignition temperature. requirements that may apply. The Buckeye Kitchen
Mister System must be installed and maintained in
3. The agent reacts with grease to form a foam-like accordance with the NFPA-17A Standard for Wet
layer commonly called saponification that starves Chemical Extinguishing Systems, NFPA-96 Standard for
the fire of oxygen, stopping combustion and Ventilation Control and Fire Protection of Commercial
preventing re-ignition. Cooking Operations, this manual, and all applicable
The system will automatically actuate upon detection of a local, state, and federal regulations.
fire or can be manually actuated by using a remote
manual pull station positioned at the point(s) of egress Buckeye Fire Equipment is not responsible for systems
from the hazard area. When the system is actuated, a installed or maintained by personnel that are not factory
pre-determined amount of fire extinguishing agent is trained and Authorized.
discharged through the piping network and fixed nozzles
to the duct, plenum, and cooking appliances. The agent
is discharged as a very fine mist that quickly acts to
suppress grease laden fires.
Chapter 2
System Components
Cylinder Sizes
The Buckeye Fire Equipment Kitchen Mister Fire Suppression System has available four (4) cylinder sizes; the Model
BFR-5 (5 flow points), Model BFR-10 (10 flow points), Model BFR-15 (15 flow points), and Model BFR-20 (20 flow
points). Cylinder sizes are based on the flow point capacity of the cylinder, for example, the BFR-5 is capable of
supporting a maximum of five (5) flow points. All cylinders are manufactured, marked, and tested in accordance with DOT
4BW240. Each cylinder is shipped pre-filled with extinguishing agent, and charged with dry nitrogen to a pressure of 195
o o
psig (1344 KPa) @ 70 F (21 C). Cylinder and valve assembly dimensions are shown in Figure 2-1.
SET
È REPLACE CARTRIDGE
WITHIN ONE YEAR OF
DATE SHOWN IN WINDOW
FIRED
Figure 2-1.
Cylinder and Valve Assembly Dimensions.
A B C D Max. Weight
Model inches inches inches inches Flow lbs. Mounting
Number (cm) (cm) (cm) (cm) Points (kg) Bracket
BFR-5 24.8 (63) 16.2 (41) 10 (25) 13.4 (34) 5 42 lbs. (19) MB-1
BFR-10 34.4 (87) 25.8 (66) 10 (25) 23 (58) 10 74 lbs. (33) MB-2
BFR-15 44.8 (114) 36.2 (92) 10 (25) 33.4 (85) 15 107 lbs. (48) MB-2
BFR-20 42.4 (108) 33.8 (86) 12 (31) 31 (79) 20 130 lbs. (60) MB-2
All Kitchen Mister System cylinders utilize the same The Model BFR-DAK Discharge Adaptor Kit is included
poppet style valve assembly, the Model BFR-VLV as with all Buckeye cylinders and is required to connect the
shown in Figure 2-2. cylinder valve assembly to the discharge piping. See
Figure 2-4.
1/4 (0.6 cm)-20 X
7/8 (2.2 cm) SOC
HD SCREW
1/4 (0.6 cm)-20 EXTERNAL THD:
HEX NUT, SS
SHIPPING CAP
1/4 (0.6 cm) LOCK
3/4" (1.9 cm) NPT/
DETENT PIN
WASHER, SS INTERNAL THD:
ASSY
1/2" (1.2 cm) NPT
VALVE BODY
DISCHARGE
195 PSI (1344
KPa) STAINLESS ADAPTER
STEEL GAUGE
1/4 (0.6 cm)-20
X 3/4 (1.9 cm)
BFR-DAK MOUNTING
HX HD SCREW
PLATE
O-RING, DISCHARGE
FUSEIBLE
PLUG ANTI-RECOIL ADAPTER
PLATE
Figure 2-2.
Model BFR-VLV, Extinguishing Agent
Valve Assembly
The Kitchen Mister System utilizes a potassium
The valve comes equipped with a detent pin that will, carbonate based extinguishing agent that is specifically
upon system actuation, lock the valve in the open designed to extinguish grease laden fires such as those
position assuring full discharge of the extinguishing found in commercial cooking areas. The recharge agent
agent. To re-set the valve after actuation, simply pull the is available in two different sized containers; the Model
ring on the detent pin and the valve stem will return to its BFR-5R (5 flow points of agent) and the Model BFR-10R
closed position. (10 flow points of agent). For information on the proper
procedure for refilling the cylinder after system discharge,
refer to Chapter 5 of this manual.
Valve Cap Assembly
Figure 2-3.
Model BFR-CAP,
Valve Cap Assembly
Mounting Brackets
Figure 2-5.
Model SRM,
Systems Releasing Module
IN CASE OF
FIRE
PULL HANDLE HARD
Figure 2-10.
Model BFGV-XXX,
Mechanical Gas Valve
Figure 2-9.
Model RPS-M,
Remote Mechanical Pull Station
Fusible Link Bracket Kit detection line and causing system actuation. Correct
fusible link selection is an essential element in the design
of any restaurant fire suppression system. After
The Model FLB-1 Fusible Link Bracket kit (see Figure 2-
performing a temperature study to determine the
11) includes the following:
maximum ambient temperature at the fusible link
location, the correct fusible link should be selected from
• Standard high profile 10” (25 cm) fusible link
the following chart:
bracket.
• Two (2) ½” (1.3 cm) EMT connectors.
• Two (2) cable crimps. Fusible Link Max. Ambient
• Two (2) “S” hooks. Model Number Temperature
o o
FL-280 225 F. (107 C.)
Note: Fusible links must be ordered separately. FL-360 o o
300 F. (149 C.)
o o
FUSIBLE LINK BRACKET FL-450 375 F. (191 C.)
o o
FL-500 430 F. (221 C.)
"S" HOOK
Figure 2-11.
Model FLB-1,
10” (25 cm) Fusible Link Bracket Assembly
Figure 2-13.
Fusible Link Holder Globe ML Fusible Link
Fusible Links
Figure 2-15.
Model BFR-SCI,
Shielded Cable Interface
TETHERED
BLOW-OFF CAP
Note: A 3/32” (0.2 cm) hex wrench is required to tighten
the set screw.
COLOR
ID BAND
necessary. The Model CPCT-1 corner pulley is equipped 3/8" (1.0 cm) NPT
with a compression type fitting that connects to standard
1/2” (1.3 cm) EMT conduit. See Figure 2-16. Figure 2-17.
Discharge Nozzle
Discharge Nozzles
3/8" (1.0 cm) NPT
Misting type discharge nozzles have been specifically MALE THREAD
developed for appliance, duct, and plenum applications.
30° ROTATION
Each nozzle has a predetermined flow point value and
comes equipped with a blow-off cap to protect the end
orifice from blockage. Each nozzle is identified by the Figure 2-18.
model number stamped on the nozzle body and has a Model N-SA,
unique color band for easy visual identification. See Swivel Adaptor
Figure 2-17.
Digital Thermometer
CAUTION
A temperature study is required before the
installation of any system in order to determine the
correct temperature fusible link at each fusible link
location.
COMPONENT LIST
Large Nitrogen Actuation FL-500 Fusible Links - 500o F (260o C). Globe - ML
BFR-AC-L BFRACL
Cartridge (2 per package) o o
Fusible Links - 500 F (260 C).
FL-500-10 FL50010
Small Nitrogen Actuation (10 per package)
BFR-AC-S BFRACS
Cartridge (5 per package) 10" (25.4 cm) Fusible Link
FLB-1 LBK3
Bracket Kit
BFR-CAP Valve Cap Assembly BFRCAP
10" (25.4 cm) Fusible Link
Replacement Discharge FLB-10 LBK3
BFR-DAK BFRDAK Bracket Kit (10 per package)
Adaptor Kit
FLH Fusible Link Holder PDE10038
BFR-OM Owners Manual BFROM
195 psi (1334 KPa) Pressure Fusible Link Holder (25 per
BFR-PG BFRPG FLH-25 FLH25
Gauge package)
Replacement Nozzle
N-STR-10 NSTR10 SH-100 "S" Hooks (100 per package) SH100
Strainers (10 per package)
Chapter 3
System Design
OVERVIEW OF SYSTEM DESIGN (127 cm) perimeter and a maximum one side length of
12-1/2” (32 cm) (square) and 16-3/4” (43 cm)
(rectangular) respectively. It can also protect a round
The following chapter will cover the proper design of the duct with a maximum circumference of 50” (127 cm)
Buckeye Fire Equipment Kitchen Mister Fire [16” (41 cm) maximum diameter]. See Figure 3-1 & 3-2.
Suppression System. It is divided into three sections:
rectangular ducts and 12-1/2” (32 cm) for HORIZONTAL DUCT NOZZLE PLACEMENT:
square ducts 1/2L 1"- 6" (2.5-15 cm)
[Per. 0 to 50" (0-127 cm), N-1LP]
or NOZZLE
0" - 6" (0-15 cm)
50” (127 cm) Maximum Circumference 1/2L [Per. 0 to 150" (0-381 cm), N-2W]
(maximum diameter of 16” (41 cm)) for L
1/2W W
INTO THE DUCT TRANSITION
round ducts.
HOOD
Placement: Centered in duct opening, from 1-6” (2.5-
15 cm) into the duct opening.
FOR DUCTS WITH A VERTICAL TO HORIZONTAL
Aim point: Center of duct. TRANSITION
The Model N-1LP nozzle is a one flow point nozzle that Figure 3-1.
can protect a square or rectangular duct of unlimited Proper Duct Nozzle Placement
length and changes of direction with a maximum 50”
1/2 W 1/2 W
Figure 3.3.
W W
Proper Measurement And Nozzle
Placement For Larger To Smaller Transition Ducts.
1/2 L 1/2 L
L=W
L Smaller to Larger Duct Transitions
FOR PERIMETERS 0 to 50" (0-127 cm): LONGEST SIDE
SHALL NOT EXCEED 16-3/4" (42.5 cm);
FOR PERIMETERS 0 to 150" (0-381 cm) USING THE
N-2W: LONGEST SIDE SHALL NOT EXCEED 50" (127 cm). To determine the proper coverage for ducts that have a
smaller opening into the plenum than the final exhaust
VIEW OF DUCT CROSS-SECTIONAL AREA
duct, measure the perimeter of the final exhaust duct.
Figure 3-2. The nozzle will be located as per standard duct
Proper Duct Nozzle Placement coverage at the duct/plenum interface and aimed at the
center of the duct opening. See Figure 3.4.
The Model N-2W nozzle is a two (2) flow point nozzle PERIMETER
that can protect a square or rectangular duct of MEASUREMENT
Transition Ducts
PLENUM
Figure 3.5.
Protection of any non-standard duct should be
Upper / Lower Plenum Protection
discussed and agreed upon with the local authority
having jurisdiction before proceeding with any system
installation. Typically, transition ducts are protected in Electrostatic Precipitators
the following manner.
Ventilation systems that utilize electrostatic precipitators
Larger to Smaller Duct Transitions require duct protection above and below the precipitator.
Standard duct nozzles are used for this application.
To determine the proper coverage for ducts that have a See Figure 3.6.
NOZZLE
larger opening into the plenum than the final exhaust
duct, measure the perimeter of the duct half way
between the largest and smallest cross sectional areas. PRECIPITATOR
The nozzle will be located as per standard duct
coverage at the duct/plenum interface, rather than at the NOZZLE PLENUM
point of measurement, and pointed into the duct, aimed
at the center of the final duct opening. See Figure 3.3.
Figure 3.6.
Electrostatic Precipitator Protection.
Aim point: See Figure 3.7. In order to properly understand this section, several key
terms need to be defined in advance.
The Model N-1HP nozzle is a one (1) flow point nozzle
that can protect a plenum (either single bank or V-bank) DESIGN TERMINOLOGY
of 12 feet (3.7 m) in length and 4 feet (1.2 m) in width
per nozzle. Larger plenums must be divided into 12 foot Nozzle Height: The distance from the tip of the
(3.7 m) sections, with each section protected with a discharge nozzle to the top surface of the appliance
separate nozzle. See Figure 3-7. (except for woks, in which case the bottom of the wok is
used).
Plenum: V-bank Nozzle Placement
Hazard Area: All nozzle coverages include the
The nozzle must be located at the center of the V-bank maximum size of the hazard area they can protect.
width and down 1/3 of the vertical height, within 6 inches Hazard area is NOT the overall size of the appliance
(15 cm) of the end of the plenum or plenum module and being protected, but rather the actual size of the
aimed down the length of the plenum. See Figure 3-7. portion of the appliance used for cooking.
Plenum: Single Filter Bank Nozzle Placement Appliances Requiring Multiple Nozzles
The nozzle must be located at a point that is 2” (5.1 cm) Some appliances may need to be protected by multiple
from the back edge of the filter and 1/3 of the vertical nozzles because of their size. If the size of an
height of the filter, within 6 inches (15 cm) off the end of appliance is larger than the approved coverage for that
the plenum or plenum module and aimed down the appliance, multiple nozzles must be used. This is
length of the plenum. See Figure 3-7. accomplished by dividing the hazard area into individual
1/2W
W
1/3H zones that comply with the parameters of the listing for
that appliance. In this case, each zone will be protected
H as an individual appliance with respect to nozzle
placement and aiming.
V BANK
MINIMUM HEIGHT
Nozzle Ht: 35” (89 cm) – 43” (109 cm)
30" (76 cm) 12" (30.5 cm)
6"
(15 cm) Placement: Centered over appliance.
RANGE
CENTER
3"
Aim point: Center of appliance.
BURNER TO BURNER
TO
BURNER
LENGTH: BURNER The Model N-2LP nozzle is a two (2) flow point nozzle
WIDTH:
24" (61 cm)
24" (61 cm) that can protect a range cooking area of 36” (91 cm)
wide by 24” (61 cm) deep. The nozzle must be located
35” (89 cm) to 43” (109 cm) above the cooking surface
Figure 3-9. and centered over the appliance. The nozzle must be
High Proximity, 24” (61 cm) x 24” (61 cm) Range aimed at the center of the cooking area. See Figure
Model N-1LP Nozzle 3-11.
MAXIMUM HEIGHT 43" (109 cm) Protection For Appliances With a Back-
NOZZLE
PLACEMENT
shelf
AREA
MINIMUM HEIGHT 35" (90 cm) The protection of an appliance (such as a range) that
RANGE CENTER has a shelf that can interfere with a nozzle discharge
can be accomplished by either using the low proximity
coverage for that appliance or placing the nozzle in a
position within its stated limitation where the discharge
pattern will not be affected. Sample coverages for a
BURNER TO BURNER
LENGTH: 36" (91 cm) range with a back-shelf are shown in Figures 3-13 and
BURNER TO BURNER
WIDTH: 24" (61 cm) 3-14.
SHELF WIDTH: NOT TO
EXCEED THE CENTERLINE OF
THE RANGE UNLESS NOZZLE
IS LOCATED UNDER SHELF
OR OBSTRUCTION.
Figure 3-14.
Figure 3-12. 12” (30.5 cm) x 24” (61 cm) Range with Back-shelf
30” (76 cm) x 24” (61 cm) Combination Model N-1LP Nozzle
Range / Griddle
NOZZLE
Shelf Height: Minimum of 16” (41 cm) from the top of PLACEMENT
the appliance. AREA
Figure 3-14b.
SHELF WIDTH: NOT TO
EXCEED 11" (28 cm)
Wok Protection
MAX. HEIGHT: 40" (102cm)
Model N-1HP Nozzle
NOZZLE PLACEMENT
AREA The Model N-1HP nozzle is a one (1) flow point nozzle
that can protect a wok with a minimum diameter of 12”
MIN. HEIGHT 30" (76 cm)
(30.5 cm) up to a maximum diameter of 30” (76 cm).
MINIMUM SHELF
The nozzle must be located 30” (76 cm) to 48” (122 cm)
AIM: 6" (15 cm) FROM BACK EDGE ON
CENTERLINE HEIGHT
16" (41 cm) .
above the bottom of the wok and positioned anywhere
over the cooking area. The nozzle must be aimed at the
center of the cooking area. See Figure 3-14b.
6"
MAX. (15 cm)
9" (22.5 cm)
BURNER EDGE TO BURNER EDGE:
24" (61 cm)
BURNER EDGE TO 6"
BURNER EDGE: (15 cm)
24" (61 cm)
Figure 3-14a.
24” (61 cm) x 24” (61cm) Range with Back-shelf
Model N-2LP Nozzle
Coverage: 20.25” (51 cm) x 24” (61 cm) Coverage: 20.25” (51 cm) x 24” (61 cm) per nozzle
Nozzle Ht: 24” (61 cm) – 45” (114 cm) Nozzle Ht: 24” (61 cm) – 45” (114 cm)
Placement: Anywhere over the surface of the Placement: Anywhere over the surface of the
appliance cooking area. appliance cooking area.
Aim point: Center of appliance. Aim Point: Center of the protected zone.
The Model N-2HP nozzle is a two (2) flow point nozzle The Model N-2HP nozzle is a two (2) flow point nozzle
that can protect a deep fat fryer with a maximum that can protect a tilting brazing pan / skillet with a
cooking area of 20.25” (51 cm) wide by 24” (61 cm) maximum cooking area of 20.25” (51 cm) wide by 24”
deep. The nozzle must be located 24” (61 cm) to 45” (61 cm) deep per nozzle. The nozzle must be located
(114 cm) above the cooking surface and located 24” (61 cm) to 45” (114 cm) above the cooking surface
anywhere over the appliance cooking area. The nozzle and located anywhere over the appliance cooking area.
must be aimed at the center of the cooking area. See The nozzle must be aimed at the center of the cooking
Figure 3-15. area. See Figure 3-16.
NOZZLE TO BE LOCATED
WITHIN THE PERIMETER MAXIMUM HEIGHT
OF THE HAZARD 45" (114 cm)
COVER MUST
NOZZLE
MAXIMUM HEIGHT 45" (114 cm) NOT INTEFERE PLACEMENT
WITH NOZZLE AREA
DISCHARGE
NOZZLE MINIMUM HEIGHT
PLACEMENT 24" (61 cm)
AREA
NOZZLE AIMED C
L
CENTER OF
HAZARD AREA
Figure 3-16.
Tilting Skillet / Brazing Pan
Model N-2HP Nozzle
MAXIMUM
WIDTH: 24" (61 cm) GRIDDLE PROTECTION
MAXIMUM
LENGTH: 20.25" (51 cm)
Standard Griddle: 42”(107 cm) x 30” (76 cm)
Figure 3-15.
Nozzle: N-1LP (1 Flow Point)
20.25” (cm) x 24” (cm) Deep Fat Fryer
Model N-2HP Nozzle
Coverage: 42” (107 cm) x 30” (76 cm) Maximum
Fryers Requiring Multiple Nozzles Nozzle Ht: 24” (61 cm) – 48” (122 cm)
Fryers that exceed the coverage of a single nozzle can Placement: Directly over the edge of the cooking area.
be protected with multiple nozzles. The fryer must be
divided into equal sized modules, so that each module Aim Point: 6” (15 cm) from center of appliance in-line
does not exceed the maximum coverage allowed for a with the nozzle.
single nozzle.
The Model N-1LP nozzle is a one (1) flow point nozzle
that can protect a griddle with a maximum cooking area
CAUTION of 42” (107 cm) wide by 30” (76 cm) deep. The nozzle
The maximum size fryer that can be modularized is must be located 24” (61 cm) to 48” (122 cm) above the
864 square inches (5,574 sq. cm). cooking surface and positioned directly above the edge
of the cooking area. The nozzle must be aimed 6” (15
cm) from the center of the cooking area in-line with the
nozzle. See Figure 3-17.
NOZZLE TO BE LOCATED
ON THE PERIMETER OF The Model N-1LP nozzle is a one (1) flow point nozzle
THE HAZARD
MAXIMUM HEIGHT
48" (122 cm)
that can protect a griddle with a maximum cooking area
of 48” (122 cm) wide by 30” (76 cm) deep. The nozzle
must be located 30” (76 cm) to 43” (109 cm) above the
NOZZLE
PLACEMENT cooking surface, on the centerline of the appliance and
AREA 6” (15 cm) off the either short edge. The nozzle must be
MINIMUM HEIGHT aimed 3” (7.6 cm) from the center of the cooking area
24"( 61 cm) in-line with the nozzle. See Figure 3-18.
Large Griddle - 48” (122 cm) x 30” (76 cm) The Model N-2LP nozzle is a two (2) flow point nozzle
that can protect a griddle with a maximum cooking area
Nozzle: N-1LP (1 Flow Point) of 60” (152 cm) wide by 30” (76 cm) deep. The nozzle
must be located 24” (61 cm) to 48” (122 cm) above the
Coverage: 48” (122 cm) x 30” (76 cm) Maximum cooking surface and positioned directly above the edge
of the cooking area. The nozzle must be aimed 8” (20
Nozzle Ht: 30” (76 cm) – 43” (109 cm) cm) from the center of the cooking area in-line with the
nozzle. See Figure 3-19.
Placement: On the centerline of the appliance, 6” (15
cm) off the short edge.
NOZZLE TO BE LOCATED ON
MAXIMUM HEIGHT
THE PERIMETER OF THE
Aim Point: 3” (7.6 cm) from center of appliance in-line 48" (122 cm) HAZARD
with the nozzle.
NOZZLE
PLACEMENT
MAXIMUM HEIGHT AREA
43" (109 cm)
MINIMUM HEIGHT
24" (61 cm)
NOZZLE
PLACEMENT
AREA
MINIMUM HEIGHT
30" (76 cm) 8" (20 cm)
NOZZLE AIMED 8"
3" FROM CENTER
OF HAZARD AREA
(7.6 cm) INLINE WITH NOZZLE
MAXIMUM MAXIMUM
LENGTH: 48" (122 cm) 6" (15 cm) LENGTH: 60" MAXIMUM
MAXIMUM (152 cm) WIDTH: 30" (76 cm)
WIDTH:
30" (76 cm)
Figure 3-19.
Figure 3-18. Extra Large Griddle: 60” (152 cm) x 30” (76 cm)
Large Griddle: 48” (122 cm) x 30” (76 cm) Model N-2LP Nozzle
Model N-1LP Nozzle
Extra Low Proximity Griddle of 60” (152 cm) wide by 30” (76 cm) deep. The nozzle
must be located 10” (61 cm) to 30” (122 cm) above the
Nozzle: N-2W (2 Flow Point) cooking surface and positioned 0” to 3” (7.6 cm) outside
the short side edge of the cooking area of the griddle.
Coverage: 42” (107 cm) x 30” (76 cm) Maximum This allows the nozzle to be placed anywhere over the
short edge and up to 3” (7.6 cm) outside of the short
Nozzle Ht: 2” (5 cm) – 10” (25 cm) edge of the appliance. The nozzle must be aimed at the
point one-quarter the longest side length (1/4L) from the
o griddle short edge, in-line with the nozzle. See Figure
Placement: Over any corner, at a 45 angle to the
surface. 3-19b.
MAXIMUM OF 3"
Aim Point: At cooking surface, equal distance from (7.6cm) FROM EDGE
both edges.
MAXIMUM HEIGHT
The Model N-2W nozzle is a two (2) flow point nozzle 30" (76 cm)
that can protect a griddle with a maximum cooking area
of 42” (107 cm) wide by 30” (76 cm) deep. The nozzle NOZZLE
PLACEMENT
must be located 2” (5 cm) to 10” (25 cm) above any AREA
corner of the cooking surface and positioned on the
edge of the cooking area of the griddle. The nozzle MINIMUM HEIGHT
10" (25 cm)
must be aimed at the point over the cooking surface
equal distance from both edges. See Figure 3-19a.
1/4 L
MAXIMUM HEIGHT
10" (25 cm)
MAXIMUM
LENGTH(L): 60" (152 cm) MAXIMUM
NOZZLE
WIDTH: 30" (76 cm)
PLACEMENT
AREA
45°
MINIMUM HEIGHT
2" (5 cm)
Figure 3-19b.
L W
60” (152 cm) x 30” (76 cm) Griddle
Model N-2W Nozzle
L=W
MAXIMUM
WIDTH: 30" (76 cm)
MAXIMUM
LENGTH(L): 42" (107 cm) CHARBROILER PROTECTION
Radiant Charbroiler
Figure 3-19a.
42” (107 cm) x 30” (76 cm) Griddle Nozzle: N-1HP (1 Flow Point)
Model N-2W Nozzle
Coverage: 36” (91 cm) x 24” (61 cm) Maximum
Low Proximity Griddle Nozzle Ht: 30” (76 cm) – 48” (122 cm)
Nozzle: N-2W (2 Flow Point) Placement: Anywhere over the surface of the
appliance.
Coverage: 60” (152 cm) x 30” (76 cm) Maximum
Aim Point: Center of appliance.
Nozzle Ht: 10” (25 cm) – 30” (76 cm)
The Model N-1HP nozzle is a one (1) flow point nozzle
Placement: From 0” to 3” (7.6 cm) outside the short that can protect a radiant charbroiler with a cooking area
side edge of the cooking area, of 36” (91 cm) wide by 24” (61 cm) deep. The nozzle
must be located 30” (76 cm) to 48” (122 cm) above the
Aim Point: One-quarter the length (1/4L) of the cooking surface and positioned anywhere over the
longest side, in-line with the nozzle. cooking area. The nozzle must be aimed at the center of
the cooking area. See Figure 3-20.
The Model N-2W nozzle is a two (2) flow point nozzle
that can protect a griddle with a maximum cooking area
MAXIMUM
WIDTH: 24" (61 cm)
NOZZLE AIMED
CENTER OF
HAZARD AREA
NOZZLE AIMED
CENTER OF
HAZARD AREA
MAXIMUM MAXIMUM
LENGTH: 36" (91 cm) WIDTH: 24" (61 cm)
MAXIMUM
LENGTH:
24" (61 cm)
Figure 3-20.
Radiant Charbroiler
Model N-1HP Nozzle
Figure 3-21.
Lava Rock Charbroiler Protection Lava Rock Charbroiler
Model N-2HP Nozzle
Nozzle: N-2HP (2 Flow Point)
Upright Broiler Protection
Coverage: 24” (61 cm) x 24” (61 cm) Maximum
Nozzle: N-1LP (1 Flow Point)
Nozzle Ht: 24” (61 cm) – 40” (102 cm)
Coverage: 36” (91 cm) x 24” (61 cm) Maximum
Placement: Anywhere over the surface of the
appliance. Nozzle Ht: Upper corner of broiling chamber.
Aim Point: Center of appliance. Placement: Positioned in the corner of the front
opening of the appliance.
The Model N-2HP nozzle is a two (2) flow point nozzle
that can protect a lava rock charbroiler with a cooking Aim Point: Center of cooking grate.
area of 24” (61 cm) wide by 24” (61 cm) deep. The
nozzle must be located 24” (61 cm) to 40” (102 cm) The Model N-1LP nozzle is a one (1) flow point nozzle
above the cooking surface and positioned anywhere that can protect an upright broiler (salamander broiler)
over the cooking area. The nozzle must be aimed at the with a cooking area of 36” (91 cm) wide by 24” (61 cm)
center of the cooking area. See Figure 3-21. deep. The nozzle must be located in the top front
corner of the broiler and aimed at the center of the
cooking grate. See Figure 3-22.
Intentionally Blank
center of the cooking area. See Figure 3-22a.
NOZZLE TO BE
LENGTH:
60" (152 cm)
30" (76 cm)
LOCATED WITHIN
THE PERIMETER OF
THE HAZARD
MAXIMUM HEIGHT
40" (101 cm)
NOZZLE
PLACEMENT
AREA Figure 3-24.
MINIMUM HEIGHT
Sample Radiant Charbroiler Module Protection
24" (61 cm)
MAXIMUM
WIDTH: 24" (61 cm)
NOZZLE AIMED
CENTER OF
HAZARD AREA
MAXIMUM
LENGTH:
24" (61 cm)
Figure 3-22a.
Class “A”(Solid Fuel) Charbroiler
Model N-2HP Nozzle
RANGE, FOUR
BURNER- LOW CENTER OF
24 (61)X 24 (61) N-2W WHITE 2 16 (41) - 30 (76) * CENTER OF APPLIANCE 3-4
PROXIMITY APPLIANCE
(Back-shelf)*
CENTER OF
RANGE, SIX BURNER 36 (91) X 24 (61) N-2LP YELLOW 2 35 (89) - 43 (109) CENTER OF APPLIANCE 3-4
APPLIANCE
RANGE/GRIDDLE WITHIN 3 (7.6) OF CENTER OF
30 (76)X 24 (61) N-1LP RED 1 30 (76)- 40 (102) 3-5
COMBINATION CENTER APPLIANCE
RANGE, FOUR
6 (15) OFF FRONT 6 (15) from BACK
BURNER w/B SHELF - 24 (61)X 24 (61) N-2LP YELLOW 2 30 (76) - 40 (102) 3-6
EDGE EDGE
HIGH PROXIMITY
ANYWHERE OVER
WOK 12 (30.5) TO 30 (76) DIA. N-1HP BLUE 1 30 (76)- 48 (122) BOTTOM CENTER 3-6
HAZARD AREA
DEEP FAT FRYER, ANYWHERE OVER CENTER OF
20.25 (51) X 24 (61) N-2HP GREEN 2 24 (61)- 45 (114) 3-7
SINGLE VAT HAZARD AREA APPLIANCE
TILTING SKILLET, ANYWHERE OVER CENTER OF
20.25 (51) X 24 (61) N-2HP GREEN 2 24 (61)- 45 (114) 3-7
BRAISING PAN HAZARD AREA** APPLIANCE
6 (15) FROM
GRIDDLE, DIRECTLY OVER EDGE
42 (107) X 30 (76) N-1LP RED 1 24 (61)- 48 (122) CENTER, IN-LINE 3-7
STANDARD OF HAZARD AREA
WITH NOZZLE
6 (15) OUTSIDE OF
3 (7.6) FROM
SHORTER EDGE OF
GRIDDLE, LARGE 48 (122) X 30 (76) N-1LP RED 1 30 (76)- 43 (109) CENTER, IN-LINE 3-8
HAZARD AREA ON
WITH NOZZLE
C'LINE
8 (20) FROM
GRIDDLE, EXTRA DIRECTLY OVER EDGE
60 (152) X 30 (76) N-2LP YELLOW 2 24 (61)- 48 (122) CENTER, IN-LINE 3-8
LARGE OF HAZARD AREA
WITH NOZZLE
AT COOKING
GRIDDLE, OVER ANY CORNER AT
O SURFACE, EQUAL
STANDARD, EXTRA 42 (107) X 30 (76) N-2W WHITE 2 2 (5) – 10 (25) A 45 ANGLE TO 3-9
DISTANCE FROM
LOW PROXIMITY COOKING SURFACE
EDGES
1/4 Length of the
GRIDDLE, LOW 0” to 3” (7.6 cm) outside
60 (152) X 30 (76) N-2W WHITE 2 10 (25) – 30 (76) longest side, in-line 3-9
PROXIMITY the short side edge
with the nozzle
CHARBROILER, ANYWHERE OVER CENTER OF
36 (91) X 24 (61) N-1HP BLUE 1 30 (76)- 48 (122) 3-9
RADIANT HAZARD AREA APPLIANCE
CHARBROILER, LAVA ANYWHERE OVER CENTER OF
24 (61)X 24 (61) N-2HP GREEN 2 24 (61)- 40 (102) 3-10
ROCK HAZARD AREA APPLIANCE
The maximum and minimum pipe length for each size 4. A system shall have a minimum of three (3) flow
agent cylinder is based on total internal pipe volume, points.
regardless of the diameter of the pipe used. All piping
parameters are based on total system piping and do not General Piping Requirements
make a distinction between branches and supply line
piping. 1. All piping must be either 3/8” (17.1 mm OD) or 1/2”
(21.3 mm OD).
Note: Pipe and fittings must be furnished by the
installer. Pipe shall be Schedule 40 black, chrome 2. The maximum number of elbows allowed per
plated, or stainless steel pipe. Fittings shall be rated system are:
150 lb (68 kg).
BFR-5: 20 elbows maximum
BFR-10/15/20: 25 elbows maximum
PIPING VOLUME CHART
3. The maximum number of elbows between any two
Allowable Volume nozzles is five (5).
Pipe Sizes Per foot
4. The maximum vertical rise of the supply line is 10
3/8 in. (17.1 mm OD) pipe 37.5 mL./ft. (123mL/m) feet (3 m), this is either the maximum elevation
1/2 in. (21.3 mm OD) pipe 59.8 mL./ft. (196mL/m) difference between tank outlet and the highest
nozzle or tank outlet and the highest or lowest point
Example: 20 feet (6.1 m) of 3/8” (17.1 mm OD) pipe is in the piping system.
equal to 750 mL. of pipe volume [20 ft. (6.1 m) X 37.5
mL./ft. (123mL/m) = 750 mL.). 5. The maximum vertical rise of any nozzle above the
supply line is 2 feet (0.6 m).
MAXIMUM PIPING PER CYLINDER SIZE
6. No traps are allowed in the piping system.
Max. Pipe
Max. Max. Pipe Note: A “trap” is defined as a section of pipe that
Cylinder Vol. Between
Flow Volume would allow liquid to accumulate, such as, either a
Size any two (2)
Points (mL.) low point in the piping layout or piping that extends
Nozzles. (mL.)
past the last discharge point.
BFR-5 5 1500 1000
BFR-10 10 2500 2000
7. When different sized piping is used in the same
system, the largest diameter pipe must be closest
BFR-15 15 2800* 2500 to the cylinder and sizes are to decrease as they
BFR-20 20 2800* 2500 reach the nozzle. So piping always runs from
larger to smaller diameter.
* Total volume of 3/8” (17.1 mm OD) piping allowed
on the BFR-15 or BFR-20 is 2500 mL. 8. Elbow(s) or swivel adaptors used at the nozzle for
aiming DO NOT count toward the total elbows
allowed per system or the number of elbows
between two (2) nozzles.
Minimum Piping Requirements
9. For the BFR-15 and BFR-20 only, the maximum
Note: Minimum piping requirements ONLY apply when volume of piping between the nozzle nearest the
protecting a wok, deep fat fryer, or range. supply line from one branch to the closest nozzle
from the next branch shall not exceed 500 mL.
DETECTOR PLACEMENT
Detectors (fusible links) are required to be placed in the
air stream of each appliance (one detector per
appliance) and in the opening of the exhaust duct(s) of
protected ventilation hoods. Detectors shall be located
in the plenum area of the ventilation hood behind the
filters, which provide protection for the detection system.
A B C
Figure 3-26.
Proper Detector Placement
Appliances and Duct
Chapter 4
System Installation
GENERAL The cylinder must be vertically mounted. See Figure
4-1.
The following chapter will cover the proper installation of
1. The wall used to mount the cylinder must be
the Buckeye Fire Equipment Kitchen Mister Fire
sufficiently strong to support the cylinder weight.
Suppression System.
2. Mount the bracket using lag bolts, making sure it is
This chapter will only cover the various aspects of level.
installation associated specifically with the Kitchen
Mister System. Additional training in both mechanical 3. Loop the cylinder strap loosely over the top of the
and electrical systems is required for proper system cylinder as shown below.
installation and training in these areas is solely the 4. Hook the bottom rim of the cylinder into the bracket.
responsibility of the distributor.
5. Allow the mounting strap provided to slide into the
Various components required for system installation two top grooves of the bracket and around the
such as pipe, pipe hangers, conduit (EMT), conduit cylinder.
straps, wiring, mounting hardware, and the like are not 6. Tighten the strap securely around the cylinder.
furnished by Buckeye Fire Equipment and must be
provided by the installing distributor. The bracket can not be fastened to dry wall or other
such material, if this type of wall is encountered a stud
must be located and the bracket fastened to it.
CAUTION
This technical manual can in no way be considered
sufficient to completely understand the proper
design, installation, or maintenance of the Kitchen
Mister System. Buckeye Certified Training is
required to become Authorized to perform these
procedures. Buckeye Fire Equipment will not be
responsible for system(s) designed, installed, or
maintained by individuals or companies not trained
and Authorized by Buckeye Fire Equipment.
4. DO NOT over-tighten piping, using a pipe wrench After mounting the cylinder, align the mounting holes in
make sure all piping is snug. the control head base with the holes in the interface
gasket and cylinder valve. With the interface gasket in
5. If a section of pipe is over-tightened, it must be place and using all four mounting screws provided,
completely removed, the Teflon tape must be mount the Systems Releasing Module firmly onto the
removed and re-applied, and the section be cylinder valve using a 3/16” (0.5 cm) Allen wrench. See
reinstalled. Figure 4-2.
6. Make sure all piping is secure by using the
appropriate pipe hangers and/or straps. Wall Mounting of Systems Releasing Module
7. Before installing nozzles, blow all piping out with The Systems Releasing Module, Model SRM (or Model
dry air or nitrogen to assure no foreign material is SRM-D) can be wall mounted and used to pneumatically
left in the piping system. actuate a maximum of five (5) agent cylinders.
8. Install all nozzles in accordance with Chapter 3 of
this manual. For remote cylinder actuation, the Systems Releasing
Module must be mounted directly to a wall using four
9. Be sure that the blow off cap provided with each screws. The four knockouts in the back wall of the
nozzle is in place. Systems Releasing Module must be removed and the
Note: Make sure to explain to the owner of the system resulting holes used to secure the unit to the desired
the importance of nozzle caps (i.e., to keep debris out of wall. No bracket is required for mounting the Systems
the nozzle and prevent clogging) and that they should Releasing Module in this manner.
be checked daily to assure they are in place
After firmly mounting the Systems Releasing Module to
a wall, a Model BFR-CAP Valve Cap Assembly
(ordered separately) must be installed on all agent
SYSTEMS RELEASING MODULE cylinders being remotely actuated. Four mounting
INSTALLATION screws are provided with the Valve Cap Assembly for
fastening the Valve Cap Assembly to the top of the
Mounting Systems Releasing Module Directly cylinder valve. A 3/16” (0.5 cm) Allen wrench is required
for tightening the mounting screws. The Systems
to Cylinder Valve
Releasing Module is then connected to each agent
cylinder using 1/4” (0.6 cm) OD copper tubing.
The Systems Releasing Module, Model SRM (or Model
SRM-D) can be installed directly onto the cylinder valve
if desired. Four mounting screws are required for Option #1: Single Cylinder Activation
fastening the Systems Releasing Module to the top of
the cylinder valve; these screws are provided with the 1. The (4) mounting screw holes in the bottom of the
cylinder assembly. Systems Releasing Module must be filled. The
Systems Releasing Module Connection Kit includes
four (4) 1/4 (0.6 cm)-20 x 7/8” (2.2 cm) socket head
FOR AN AUTHORIZED DEALER CALL (800) 438-1028
screws to accomplish this. See Figure 4.3.
2. Mount the Systems Releasing Module to a wall as
described above.
3. Mount the agent cylinder making sure not to exceed
the maximum length of tubing allowed.
4. Install a Model BFR-CAP Valve Cap Assembly on
the agent cylinder valve.
È
SET
REPLACE CARTRIDGE
WITHIN ONE YEAR OF
DATE SHOWN IN WINDOW
5. Connect the Systems Releasing Module to the
agent cylinders using 1/4” (0.6 cm) OD copper
VALVE/SRM INTERFACE
SYSTEMS RELEASING GASKET tubing.
MODULE
1/4 (0.6 cm)-20 X 7/8" (2.2 cm)
SOCKET HEAD SCREW (4)
Figure 4-2.
Systems Releasing Module Mounted
Directly to Cylinder Valve
Limitations For Remote Cylinder Actuation Note: Refrigeration type copper tubing is used for
remote cylinder actuation. This tubing shall have an
Maximum Length Actuation outside diameter or 1/4” (0.6 cm) and a minimum wall
Number Of thickness of 1/32” (0.08 cm).
Of 1/4” (0.6 cm) Cartridge
Cylinders
Copper Tubing Required
Option #2: Multiple Cylinder Activation
1–3 15 feet (4.6 m) BFR-AC-S*
1–5 25 feet (7.6 m) BFR-AC-L** 1. The (4) mounting screw holes in the bottom of the
Systems Releasing Module must be filled. The
Systems Releasing Module Connection Kit includes
* Included with Systems Releasing Module four (4) 1/4 (0.6 cm)-20 x 7/8” (2.2 cm) socket head
** Sold separately screws to accomplish this. See Figure 4.4.
Note: The maximum length of tubing allowed between 2. Mount the Systems Releasing Module to a wall as
agent cylinders is 3 feet (0.9 m). described above.
SET
È REPLACE CARTRIDGE
WITHIN ONE YEAR OF
DATE SHOWN IN WINDOW
FIRED
SYSTEM
RELEASE
LOOP NOT
MODULE
È
SET
REQUIRED. È REPLACE CARTRIDGE
WITHIN ONE YEAR OF
DATE SHOWN IN WINDOW
FIRED
ADAPTER
ADAPTER FITTING, 1/8" (0.3 FITTING, 1/8"
cm) NPT - 1/4" (0.6 cm) OD .25" (0.6 cm) OD (0.3 cm) NPT -
TUBING COPPER TUBING 1/4" (0.6 cm)
OD TUBING
PLUG VALVE CAP
ADAPTER
FITTING, 1/8" (0.3
VALVE cm) NPT - 1/4" (0.6
ASSEMBLY cm) TUBING
Figure 4-4.
Multiple Cylinder Actuation Using the
Systems Releasing Module
Buckeye Shielded Cable (Patent Pending) is flexible conduit with a 1/16” (0.16 cm) stainless steel cable core that can
be used for all system inputs and outputs (fusible link line, gas valve line, and remote pull station line) instead of using
conduit and corner pulleys.
Note: If Buckeye Shielded Cable is not used for system controls, a combination of Buckeye Shielded Cable and 1/2” (1.3
cm) EMT conduit with corner pulleys or just 1/2” (1.3 cm) EMT conduit and corner pulleys are also approved.
In general, Buckeye Shielded Cable is attached at one end to the System Releasing Module with a Buckeye Shielded
Cable Interface, run to where it needs to be terminated (hood, gas valve, or pull station), and connected at the other
end with another Buckeye Shielded Cable Interface. See Figure 4-5.
The Shielded Cable Interface holds the outer flexible conduit and allows the 1/16” (0.16 cm) stainless steel cable to
pass through. It connects to any standard 1/2” (1.3 cm) conduit type connection fitting, such as a corner pulley or
conduit connector.
DROP CEILING
SEAL
WINDOW
CONNECTOR
· T est Pressure: 450 psi (31 bar). Cylinder meets
ylinder must be relieved of all pressure
efore removing cyli nd er valve.
mpty cyli nd er compl etely before
BFR-5 requirements.
· If cylinder sho ws signs of mechanical damag e it
be hydrostatically tested in accordance with NF
or replaced.
efilling.
NL Y refill with one complete container HMIS:
odel BFR-5 R) o f Buckeye Re charge Meets the Requirements of UL-300 Liquid Fire Suppression Agent - HMIS 2-0-0
gent. Potassium Carbonate
ressuri ze with nitrogen to 195 psi (1344 Intended for Indoor Use Only Alkaline Irritant.
Pa) at 70°F (21 °C) in accordance with
chnical manual . Nitrogen Expe l en t Ga s - HMIS 0-0-0
UL-6885
E OF MANUFACTURE IS ON
Buckeye Fire Equipment Company VERY COLD DISCHARGE
Wet Chemica l Solution
CYLINDER. 110 Kings Road
Extingu ish ing System Unit CONTENTS UNDER HIGHPRESSURE
Kings Mountain, NC 28086
S WGT. OF UNIT: Pre Engineere d Type
704-739-7415
41 ± 2 LBS (18.6 ± 0 .9 Kgs.) MSDS av ailable at www .buckeyef.com
IN CASE OF
FIRE
PULL HANDLE HARD
HOOD
REMOTE MANUAL
PULL STATION
BSC INTERFACE
WITH CONDUIT
CONNECTOR
CAUTION
AUTOMATIC GAS
SHUT-OFF VALVE
MECHANICAL GAS
VALVE
Figure 4-5.
Buckeye Shielded Cable Installation
Typical Installation
Buckeye Shielded Cable Installation Releasing Module. Then, pull enough of the 1/16” (0.16
Guidelines cm) stainless steel cable through the gas valve side of
the cable to allow for connection of BOTH the gas valve
(at one end) and the Systems Releasing Module (at the
Buckeye Shielded Cable (Patent Pending) can be used
other end).
for all system mechanical interfaces:
5. The Buckeye Shielded Cable can now be cut at the
• Fusible Link Detection Line
end opposite of where the excess 1/16” (0.16 cm)
• Gas Valve Line
stainless steel cable has been pulled through. To
• Remote Mechanical Pull Station Line cut the cable, use a sharp, heavy duty, cable cutter
and cut through the entire piece of Buckeye
The Model BFR-SC-100 comes with 105 feet (32 m) of Shielded Cable, both the outer flexible conduit and
flexible conduit with 210 feet (64 m) of 1/16” (0.16 cm) the inner cable, at the location desired. See Figure
stainless steel cable inside it. See Figure 4-6. 4-7.
REMAINING BUCKEYE
SHIELDED CABLE
BUCKEYE SHIELD
1/16" (0.16 cm) STAINLESS
CABLE (DETECTION,
STEEL CABLE
9" GAS, OR REMOTE
(23 cm) PULL LINE)
CONTROL
MINIMUM 1' (30.5 cm)
9" (23 cm) MINIMUM HEAD ANY 1/2" (1.3 cm) EMT TYPE
OF STRAIGHT CABLE
BEND RADIUS (SHOWN) CONDUIT CONNECTOR
Figure 4-9.
Buckeye Shielded Cable Interface
Installation Detail
The following methods are approved for the installation of the fusible link detection line:
Method #1:
• Buckeye Shielded Cable used to connect the Systems Releasing Module to the plenum.
• No fusible link brackets or conduit used in the plenum area.
• Approved with or without the use of Fusible Link Holders.
BFR-5
y linder must be relieved of all press ure requirements.
efore remov ing cy linder valv e. · If cy linder s hows signs of mechanical damage it
mpty cy linder c ompl etely before be hy drost atic al ly t es ted in ac cordance with NF
efi lling. or replac ed.
NLY refi ll with one complete c ontainer H MIS :
odel BFR-5R) of Buck eye Recharge Meets the Requirements of UL-300 Liquid Fire Suppres s ion A gent - HMIS 2-0-0
gent. Potas sium Carbonate
res s urize with nitrogen t o 195 ps i (1344 Intended for Indoor Use Only A lkaline I rritant .
P a) at 70°F (21°C) in ac cordance with
c hnic al manual . Nitrogen E xpellent Gas - HMIS 0-0-0
UL-6885
E OF MANUFA CTURE IS ON Buckeye Fire Equi pment Company V ERY COLD DISCHA RGE
CONNECTED IN SERIES
Figure 4-11.
Fusible Link Line Installation Method #1
Method #2:
• Buckeye Shielded Cable used to connect the Systems Releasing Module to the plenum.
• Fusible link brackets and conduit used in plenum area.
• Approved with or without the use of Fusible Link Holders.
CONNECTED IN SERIES
Figure 4-12.
Fusible Link Line Installation Method #2
Method #3:
• 1/2” (1.3 cm) EMT conduit and Buckeye Corner Pulleys used to connect the Systems Releasing Module to
the plenum.
• No fusible link brackets or conduit used in the plenum area.
• Approved with or without the use of Fusible Link Holders (only shown with holders used).
ML STYLE FUSIBLE
CONDUIT CORNER PULLEY LINK WITH FLH FUSIBLE LINK BRACKET
LIQUID TIGHT
(USED FOR CABLE ALIGNMENT)
COMPRESSION
HOOD SEAL
SHOWN USING CONTINUOUS DETECTION LINE WITH FUSIBLE
LINK HOLDERS
Figure 4-13.
Fusible Link Line Installation Method #3
Method #4:
• 1/2” (1.3 cm) EMT conduit and Buckeye Corner Pulleys used to connect the Systems Releasing Module to
the plenum.
• Fusible link brackets and conduit used in plenum area.
• Approved with or without the use of Fusible Link Holders (only shown with holders used).
ML STYLE FUSIBLE
CONDUIT CORNER PULLEY LINK WITH FLH
LIQUID TIGHT FUSIBLE LINK BRACKET
COMPRESSION
HOOD SEAL
SHOWN USING CONTINUOUS DETECTION LINE WITH FUSIBLE
LINK HOLDERS
BFR-5
ylinder must be relieved of all pre ssure requirement s.
efore removing cylinder valve. · If cylinder shows signs of mechanical damage it
mpt y cylin der completely before be hydrostatic ally tested in accordance wit h NF
ef li ilng. or replaced.
NLY ref lil wit h one complete container HMIS:
odel B FR-5R) of Buckeye Recharge Meets the Requirements of UL-300 Liquid Fire S uppression A gent - HM IS 2-0-0
gent . P otassium Carbonate
ressurize with nit rogen t o 195 psi (1344 Intended for Indoor Use Only Alkaline I rritant.
P a) at 70°F (21°C) in accordance with
chnical manual . Nitrogen Expelle nt Gas - HMIS 0-0-0
UL -6885
E O F MA NUFA CTURE IS ON Bu ckeye F ire Eq uipment Comp any VE RY COLD DIS CHARGE
Wet Chemical S olution
CY LINDER. 110 Kings Road
E xt n
i guishing Syst em Unit CONTE NTS UNDER HIGH PRE SSURE
Pre Engineered Type Kings Mou nt ai n, NC 28086
S WGT. OF UNI T:
704-739-7415
41 ± 2 LBS (18. 6 ± 0. 9 Kgs.) MS DS avai labl e at www .buckeyef. com
Figure 4-14.
Fusible Link Line Installation Method #4
Method #5:
• 1/2” (1.3 cm) EMT conduit and Buckeye Corner Pulleys used in combination with Buckeye Shielded Cable
to connect the Systems Releasing Module to the plenum.
• No fusible link brackets or conduit used in the plenum area.
• Approved with or without the use of Fusible Link Holders (only shown with holders used).
CLAMPS
Figure 4-15.
Fusible Link Line Installation Method #5
Method #6:
• 1/2” (1.3 cm) EMT conduit and Buckeye Corner Pulleys used in combination with Buckeye Shielded Cable
to connect the Systems Releasing Module to the plenum.
• Fusible link brackets and conduit used in plenum area.
• Approved with or without the use of Fusible Link Holders (only shown with holders used).
CLAMPS
Figure 4-16.
Fusible Link Line Installation Method #6
Fusible Link Line Installation 2. Without fusible link brackets and conduit in the
plenum area when filters are present, thus
providing mechanical protection for the fusible link
Fusible link line limitations are based on the method by
line.
which the Systems Releasing Module is connected to
the plenum. Limitations are as follows:
If fusible link brackets and conduit are used in
plenum area:
Fusible Link Line Limitations
Although fusible link brackets and conduit are only
1. Conduit and corner pulleys used with standard required for applications where no filters are present in
1/16” (0.16 cm) stainless steel cable to connect the ventilation hood, they can be used for all
System Releasing Module to plenum: applications if desired.
Max. No. of Detectors: 20 Once the decision has been made to use fusible link
Max. Length of Conduit: 150 feet (45.7 m) brackets and conduit in the plenum area, begin by
Max. No. of Corner Pulleys: 35 installing the detector brackets in the plenum area of the
ventilation hood over each appliance and in each duct
2. ONLY Buckeye Shielded Cable used to connect opening as described in Chapter 3 of this manual.
System Releasing Module to plenum: Connect the fusible link brackets using 1/2” (1.3 cm)
EMT conduit and conduit connectors.
Max. No. of Detectors: 10
Max. Length of BSC: 35 feet (10.7 m) A Buckeye corner pulley is required for each change in
Max. No. of Bends: 6 conduit direction. The conduit will exit the plenum area
through an approved liquid tight hood seal. The
3. Conduit and corner pulleys with standard 1/16” detection line can now be run back to the Systems
(0.16 cm) stainless steel cable in combination Releasing Module.
with Buckeye Shielded Cable used to connect
System Releasing Module to plenum: If fusible link brackets and conduit are not
used in plenum area:
Max. No. of Detectors: 10
Max. Length of Conduit: 25 feet (7.6 m) For installations where filters are present in the
Max. No. of Corner Pulleys: 8 ventilation hood, fusible link brackets and conduit ARE
Max. Length of Buckeye NOT required in the plenum area.
Shielded Cable: 35 feet (10.7 m)
Max. No. of Bends in BSC: 6 Install a single bracket at the top of the far end of the
plenum, approximately 3 inches (7.6 cm) in from the far
Note: The maximum number of transitions from wall and in line with the center of the duct opening.
BSC to conduit or conduit to BSC is 6.
This bracket is not used to center a fusible link, but
rather as a termination point for the fusible link line
cable.
Note: The use of Fusible Link Holders in the plenum
area does not affect fusible link line limitations. After mounting the terminal bracket, use another bracket
as a template, making sure it is also in line with the duct
Globe ML Style fusible links are used for automatic centerline, to determine the location of the hood
actuation of the Kitchen Mister System and must be penetration on the other end of the plenum. Install an
installed in the plenum area of the ventilation hood (for approved liquid tight hood seal in the hole in the far end
proper link placement see Chapter 3 of this manual). of the hood. See Figure 4-17.
Fusible Link Line Installation Step #1: The terminal bracket is the only bracket required for this
application. The fusible links will be attached directly to
the detection line in the plenum area in their appropriate
Determine if fusible link brackets and locations (see Chapter 3 for proper fusible link
conduit will be used in the plenum area: placement). No additional brackets are required. The
detection line can now be run back to the Systems
The Kitchen Mister System is approved: Releasing Module.
END VIEW OF
DETECTION LINE END OF BRACKET
ENTERING NEAR FUSIBLE LINK BRACKET HOOD
END OF HOOD (USED FOR CABLE
ALIGNMENT)
Figure 4-17.
Terminal Bracket Installation
For Systems without Brackets or
Conduit in Plenum Area
Fusible Link Line Installation Step #2: OPTION #2: Using only Buckeye Shielded Cable
1. Using standard 1/2” (1.3 cm) EMT conduit and a The Buckeye Shielded Cable is connected to the
corner pulley for each change in direction. Systems Releasing Module through a knockout in the
upper right-side corner. Install a standard conduit
2. Using ONLY Buckeye Shielded Cable. connector in the knockout hole. Then connect a
Buckeye Shielded Cable Interface to the end of the
3. Using a combination of Buckeye Shielded Cable section of Buckeye Shielded Cable to be used. Connect
and 1/2” (1.3 cm) EMT conduit / corner pulleys. the Buckeye Shielded Cable Interface to the conduit
connector installed in the knockout. The Buckeye
Note: Buckeye Shielded Cable CANNOT be attached Shielded Cable can then be run to the plenum area.
directly to the hood penetration device used to seal the
plenum area, a corner pulley and/or six (6) inches (15 Note: A corner pulley and/or six (6) inches (15 cm) of
cm) of standard 1/2” (1.3 cm) EMT conduit must be standard 1/2” (1.3 cm) EMT conduit is required between
placed in between the Buckeye Shielded Cable the Buckeye Shielded Cable and the liquid tight seal
Interface and the plenum. installed in the plenum.
For all portions of the detection line that use conduit FUSIBLE LINK BRACKET
instead of Buckeye Shielded Cable, a Buckeye Corner
Pulley is required whenever a change in conduit
direction is necessary. "S" HOOK
CAUTION TO SRM
1/2" (1.3 cm) EMT
A corner pulley and/or six (6) inches (15 cm) of MIN.
CONNECTOR
standard 1/2” (1.3 cm) EMT conduit is required 3"
between the Buckeye Shielded Cable and the liquid (7.6 cm) CABLE CRIMP
tight seal installed in the plenum.
Figure 4-19.
Series Link Installation
Fusible Link Line Installation Step #3: Fusible Link Installation Using Fusible Link Holders:
Installing the fusible links in the plenum If Buckeye Fusible Link Holders are used, make sure to
leave 4” (10 cm) of slack in the fusible link line cable per
area: fusible link. This method is recommended because it
requires fewer cuts and crimps in the fusible link line
Fusible links can be installed in the plenum area of the and allows fusible links to be easily moved to assure
ventilation hood either with or without the use of they are in the correct position.
Buckeye Model FLH-1 Fusible Link Holders.
Attach the fusible link line to the terminal bracket by
Note: A minimum of three inches of travel towards the making a tight loop in the fusible link cable and securing
SRM must be maintained between a conduit connector it with the crimp provided. This loop is then connected
and the cable crimp or fusible link holder. to the far end of the terminal bracket using an “S” Hook.
The “S” Hook should be crimped closed after
OPTION #1: Installing fusible links when installation. See Figure 4-20.
fusible link brackets and conduit ARE used:
FUSIBLE LINK
When fusible link brackets and conduit are used in the BRACKET
(TERMINAL
plenum area, attach the terminal link to the far end of BRACKET)
BUCKEYE
FUSIBLE LINK
"S" HOOK HOLDER
Figure 4-18
FUSIBLE LINK (ML
Terminal Link Installation STYLE)
Figure 4-21.
Fusible Link Connection
After the last link is connected, the control head can be
put in the set position as described in the next section of The hole in the fusible link can now be hooked onto the
this chapter. bottom of the holder as shown in Figure 4-22.
TO SRM BUCKEYE
END
FUSIBLE LINK 1/16" (0.16 cm) STAINLESS STEEL VIEW OF
CABLE CENTERED IN BRACKET BRACKET
HOLDER
Fusible links can be positioned by sliding the Fusible This cable is then used to connect the remaining series
Link Holder along the detection line before it is links. Repeat the above procedure until all the links are
completely tensioned to the desired position. in their desired locations. See Figure 4-25.
BUCKEYE SHIELDED
FUSIBLE LINK BRACKET
CABLE (REMOTE PULL
(USED FOR CABLE ALIGNMENT) LINE)
LIQUID TIGHT
COMPRESSION
SEAL
BUCKEYE SHIELDED CABLE
1/16" (0.16 cm) STAINLESS INTERFACE (SHOWN)
STEEL CABLE
OR 1/2" (1.3 cm) CONDUIT
DETECTION LINE
OPPOSITE END
ENTERING NEAR 1/16" (0.16 cm) STAINLESS STEEL COVER PLATE
OF HOOD STANDARD 1/2" (1.3 cm) EMT
END OF HOOD CABLE CENTERED IN BRACKET END
CONDUIT CONNECTOR MOUNTING SCREW
VIEW OF
BRACKET
BREAK GLASS HOLDER
Figure 4-26. STANDARD 1/16" (.16 cm) CRIMP
Fusible Link Line Installation
The hole in the fusible link can now be hooked onto the Figure 4-27.
bottom of the holder as shown in Figure 4-22. Remote Pull Station Installation
Fusible links can be positioned by sliding the Fusible After the cable is connected, the remote pull station can
Link Holder along the detection line before it is be connected to the Systems Releasing Module as
completely tensioned to the desired position. described in the next section of this chapter.
The Model RPS-M Remote Mechanical Pull Station Max. Length of BSC: 35 feet (10.7 m)
must be used for remote actuation of the Buckeye Max. No. of Bends: 6
Kitchen Mister System. It is to be located near and exit
in the path of egress from the hazard area and no more 3. Conduit and corner pulleys with standard 1/16”
than five feet above the floor. It can be connected to (0.16 cm) stainless steel cable in combination
the Systems Releasing Module as follows: with Buckeye Shielded Cable used to connect
System Releasing Module to Pull Station:
1. Using standard 1/2” (1.3 cm) EMT conduit and a
corner pulley for each change in direction. Max. Length of Conduit: 25 feet (7.6 m)
Max. No. of Corner Pulleys: 8
2. Using ONLY Buckeye Shielded Cable. Max. Length of Buckeye
3. Using a combination of Buckeye Shielded Cable Shielded Cable: 35 feet (10.7 m)
and 1/2” (1.3 cm) EMT conduit / corner pulleys. Max. No. of Bends in BSC: 6
After mounting the remote pull station in the desired Note: The maximum number of transitions from
location, the stainless steel cable can be connected as BSC to conduit or conduit to BSC is 6.
described above. The cable then enters the pull station
box through any convenient knockout and fed through
the bushing and attached to the pull handle with the
crimp provided. See Figure 4-27. (Shown with Buckeye
Shielded Cable.)
supply line that feeds the cooking appliances. 1/16" (0.16 cm) STAINLESS
GAS VALVE
STEEL CABLE
COVER PLATE
Note: An arrow on the valve body shows the direction MOUNTING NUT MECHANICAL
of gas flow through the valve. GAS VALVE
UNION UNION
1. Using standard 1/2” (1.3 cm) EMT conduit and a Figure 4-28.
corner pulley for each change in direction. Gas Valve Installation
2. Using ONLY Buckeye Shielded Cable. Setting the Systems Releasing Module
3. Using a combination of Buckeye Shielded Cable
and 1/2” (1.3 cm) EMT conduit / corner pulleys. After installing the fusible link line, pull station line, and
gas valve line, the Systems Releasing Module can be
To connect the cable to the gas valve itself, thread the connected and put into the “set position”.
cable through the top knockout in the gas valve box,
loop the cable through the gas valve stem, and secure it Step #1: Connecting the Remote Pull Station
with the crimp provided. See Figure 4-28. (Shown with Cable.
Buckeye Shielded Cable.)
1. After installing the Remote Mechanical Pull Station
Gas Valve Limitations cable, feed cable into the Systems Releasing
Module through the top right knockout as shown.
1. Conduit and corner pulleys used with standard 2. Feed cable through the hole in Manual Release
1/16” (0.16 cm) stainless steel cable to connect Lever and remove the excess cable.
System Releasing Module to Gas Valve: 3. Install a cable crimp and loop the cable back
through the crimp so that NO loop is exposed.
Max. Length of Conduit: 150 feet (45.7 m) There should be approximately 1” (2.5 cm) of cable
Max. No. of Corner Pulleys: 35 left between the crimp and the Manual Release
2. ONLY Buckeye Shielded Cable used to connect Lever. See Figure 4-29.
System Releasing Module to Gas Valve:
REMOTE PULL CABLE
4. The cable can now be connected to the fusible link Step #3: Applying Tension to the Fusible Link
ratchet wheel. This can be accomplished two Line.
different ways:
Option #1: Install a crimp at the end of the fusible 1. Once the fusible link line has been attached to the
link cable and insert the crimp in the center slot of Fusible Link Ratchet and all Fusible Links have
the fusible link ratchet wheel. It is not necessary to been correctly positioned in the detection line, the
use the hole provided in the fusible link ratchet cable is ready to be set.
wheel when this method is used. Make sure to 2. Make sure the Catch is in the “set” position. See
leave enough free cable to allow for two complete Figure 4-31a.
wraps around the ratchet wheel when the line is
tensioned. See Figure 4-30.
PUSH HERE TO
Option #2: Slide the detection cable through the PLACE CATCH IN
hole in the fusible link ratchet wheel and crimp the "SET" POSITION
end of the cable, making sure to leave enough free
cable to allow for two complete wraps around the
ratchet wheel when the line is tensioned. See
Figure 4-30.
CATCH SHOWN IN
"SET" POSITION
CATCH
OR
GAP
PUSH
CATCH DISENGAGED
(NEUTRAL POSITION) Figure 4-33a.
Figure 4-32. Removing Additional Slack
Applying Tension to the
Fusible Link Line
CAUTION
4. Continue to turn clockwise until all the slack has Do not over tighten the detection line once the
been removed and the Detection Arm just touches Detector Arm Assembly has come in contact with
the STOP located on the Detection Arm Block, fully the stop and has fully engaged the Catch.
engaging the Catch. See Figure 4-33.
Step #4: Before Setting the Systems
Releasing Module.
DETECTION
TRIGGER
CATCH ENGAGED
Figure 4-34.
Locate 3/16” (0.5 cm) Hex Head Socket Figure 4-36.
Systems Releasing Module
2. Using a ratchet with a 3/16” (0.5 cm) hex-bit socket Shown In SET Position
(Allen type), rotate the Detection Trigger to the right
until the Catch snaps into place, locking the Trigger Step #6: Setting the Mechanical Gas Valve.
in the SET position. See Figure 4-35 & Figure 4-
36. 1. After installing the gas valve cable as described
previously, feed cable into the Systems Releasing
3/8" (1.0 cm) RATCHET DRIVE Module through the top left-side knockout as
shown.
2. With the excess slack removed from the cable, cut
it so that about 3” (7.6 cm) of cable extends past
the Gas Valve Ratchet. See Figure 4-37.
3. The cable can now be attached to the Gas Valve
Ratchet in the same manner that the fusible link line
was connected to the fusible link line ratchet. See
Figure 4-30.
MANUAL GAS
VALVE LINE
CONNECTION
CAUTION
If the Gas Valve Ratchet spins freely after the SRM
is set, the SRM has NOT BEEN SET CORRECTLY.
GAS VALVE LINE
If this occurs, release the tension on the fusible RATCHET
link line and repeat the entire SRM setting process, Figure 4-37.
making sure to follow all steps carefully. Gas Valve Ratchet and Cable
v. If the Systems Releasing Module does not Valve or Wall Mounting of Systems Releasing
operate when the terminal link is cut, determine Module.
the cause of the problem and repeat this step.
After assuring that the Systems Releasing Module is
CAUTION functioning properly, has been attached to the cylinder
If any of these events do not occur when the valve assembly(s), and has been reset, the nitrogen
terminal link is cut, determine the cause of the cartridge can be installed and the system put into
problem and repeat this step. DO NOT put the service.
system into service until the cause of the problem is
determined, the appropriate steps are taken to solve Step #8: Installing the Nitrogen Actuation
the problem, and the system is successfully re- Cartridge.
tested.
1. Before installing the Nitrogen Cartridge it is
necessary to make sure that the Actuating Pin is
6. Remove the used Nitrogen Actuation Cartridge and moving freely. Insert the Model BFR-PRT,
discard immediately. Actuation Pin Resetting Tool into the threaded hole
7. After testing the fusible link line, repair the terminal of the Manifold Mounting Block where the Nitrogen
link and re-set the control head as described in this Cartridge is installed. See Figure 4-40.
chapter. 2. After screwing the resetting tool fully in, the
8. Once the Systems Releasing Module is reset, the Actuating Pin is now in the set position and an
mechanical pull station must be checked. To do so, Actuation Cartridge can now be installed.
pull the handle on the remote pull station and make
sure that the following occurs:
i. The Systems Releasing Module will operate,
causing the detection arm assembly to move
back to the left, disengaging the trigger, and
allowing the actuation lever to operate.
ii. The gas valve will close, stopping gas flow to any
gas fueled appliances.
ACTUATION PIN
iii. All auxiliary devices connected to the miniature RESETTING TOOL
electrical switch(s) provided in the Systems
Releasing Module will have operated.
CAUTION
ACTUATION PIN GASKET
If any of these events do not occur when the (FIRED POSITION)
manual pull station is operated, determine the
cause of the problem and repeat this step. DO NOT
put the system into service until the cause of the Figure 4-40.
problem is determined, the appropriate steps are Setting Actuation Pin
taken to solve the problem, and the system is
successfully re-tested. CAUTION
Before installing the Nitrogen Actuation Cartridge
the installer shall inspect the sealing cap for
9. Reconnect the Systems Releasing Module or Valve punctures or other damage and verify that the
Cap Assembly(s) to the appropriate cylinder cartridge weighs more then the stated minimum
valve(s) and secure each with the four provided gross weight stamped on the cartridge. If any
screws. evidence of damage, puncture or if the cartridge
weighs less then minimum gross weight, discard
and replace.
CAUTION
The Interface Gasket must be properly installed
between the SRM and top of the cylinder valve
3. ONLY a Buckeye Nitrogen Actuation Cartridge may
assembly. Failure to do so may result in system
be used in the Systems Releasing Module.
failure.
Carefully hand-tighten the Nitrogen Cartridge
completely into the threaded hole of the Manifold
Refer to page 4-1 or 4-2 of this manual, Mounting Mounting Block. This should take approximately ten
Systems Releasing Module Directly to the Cylinder (10) full turns of the cartridge. See Figure 4-41.
NITROGEN CARTRIDGE
ACTUATION PIN
(BFR-AC-S SHOWN, OPTIONAL
(SET POSITION)
BFR-AC-L MAY ALSO BE USED)
Figure 4-41.
Installing Nitrogen Cartridge
È
SET
È REPLACE CARTRIDGE
WITHIN ONE YEAR OF
DATE SHOWN IN WINDOW
FIRED
4. In the grey area provided, write the “date of
installation” on the Nitrogen Cartridge. The ACTUATION LEVER IN ACTUATION PIN IN NITROGEN CARTRIDGE AND
THE SET POSITION THE SET POSITION
cartridge must be replaced within one (1) year VISIBLE IN WINDOW VISIBLE IN WINDOW
DATE OF INSTALLATION
VISIBLE IN WINDOW
of installation. See Figure 4-42.
Figure 4-43.
WARNING Installing Systems Releasing Module Cover
After installing the nitrogen cartridge, the system is in
the SET position and is ready to actuate. The Buckeye Fire Equipment Kitchen Mister Fire
Suppression System is now fully functional. The
system’s operation and what is required of the End User
should be reviewed with the End User or their
designated representative. Refer to Owner Manual and
Maintenance Section of this manual for additional
details.
Figure 4-42.
Dating Nitrogen Cartridge
Chapter 5
System Inspection and Maintenance
Maintenance Overview
1. Check that the hazard area has not changed.
This chapter will detail the basic procedures for proper 2. Check the cylinder pressure gauge, making sure it is
maintenance of the Buckeye Fire Equipment Kitchen in the operable range.
Mister Fire Suppression System. 3. Check all nozzle orifices to assure that they are
unobstructed and that all nozzle caps are in place.
Maintenance of the Kitchen Mister System must be in
compliance with the parameters set forth in this manual
and be performed by a factory trained, Authorized CAUTION
Buckeye Fire Equipment Dealer. Buckeye Fire Nozzles must be completely unobstructed and show
Equipment is not responsible for systems installed or no signs of internal blockage. If nozzle(s) show any
maintained by personnel that are not factory trained and signs of internal damage or blockage, remove
Authorized. nozzle from service and replace with a new nozzle.
Owners Inspection - Monthly 4. If any BFR-UBC stainless steel metal caps are used,
they must be removed, cleaned and checked to
Monthly inspections shall be performed as per NFPA-17A assure that they slide easily on and off the nozzle
and are required by Buckeye Fire Equipment. body. If the cap does not slide easily off the nozzle
tip, the o-ring and cap must be replaced.
On a monthly basis the owner of the Kitchen Mister Fire
5. Remove the face plate from the control head.
Suppression System must perform the following “quick
check” to verify the following: 6. Remove the actuation nitrogen cartridge from
the systems releasing module.
1. The extinguishing system is in its proper location.
2. The manual actuators are unobstructed. CAUTION
3. The tamper indicators and seals are intact. Buckeye Fire Equipment recommends the testing of
all Systems Releasing Module functions during
4. The maintenance tag or certificate is up to date and
semi-annual maintenance as required by NFPA
in place.
17A.
5. No obvious physical damage or condition exists that
might prevent operation. If the use of the Keeper pin is desired to prevent the
6. The pressure gauge is in the operable range. operation of the gas valve and miniature electric
7. The nozzle blow off caps are intact and undamaged. switches refer to the Keeper Pin section of Appendix
B.
8. The hood, duct, and cooking appliances have not
been replaced, modified, or relocated. 7. Check entire system for mechanical damage.
If any deficiencies are found the owner is to contact an 8. Inspect fusible link detection line for grease build-up
Authorized Buckeye Fire Equipment Distributor or mechanical damage. Replace corner pulleys, or
immediately. conduit if necessary.
Note: A record of monthly inspections is to be kept by the 9. Activate the Systems Releasing Module by releasing
owner of the system that includes the date of inspection, tension from the end of the fusible link line by cutting
the person performing the inspection, and any corrective or melting the last link. Make certain that the
action required. Systems Releasing Module fires, the gas valve
closes, and all auxiliary devices connected to the
micro-switch operate or stop.
Semi-Annual Maintenance 10. Replace all fusible link detectors.
Semi-annual maintenance of the Kitchen Mister System 11. Reset the Systems Releasing Module and then
is required by NFPA-17A and Buckeye Fire Equipment activate the system by using the remote pull station.
and must be performed by a factory trained, Authorized Make certain that the Systems Releasing Module
Buckeye Fire Equipment Dealer. Semi-annual fires, the gas valve closes, and all auxiliary devices
maintenance shall include the following: connected to the micro-switch operate or stop.
After the SRM has been tested and is functioning 4. To check the satisfactory operation of the fusible link
properly, the system can be put back into service. system, cut the terminal link or the “S” Hook
attached to the terminal link. This will release tension
12. If a Keeper Pin was used, remove it from the on the fusible link line causing the following to occur:
Systems Releasing Module. Refer to the Keeper Pin
section of the appendix. i. The Systems Releasing Module will operate,
causing the detection arm assembly to move back
13. Before installing the Nitrogen Cartridge it is to the left, disengaging the trigger, and allowing
necessary to make sure that the Actuating Pin is the actuation lever to operate. The actuation pin
moving freely. Insert the Actuation Pin Resetting will puncture the nitrogen cartridge and allow the
Tool into the threaded hole of the Manifold Mounting nitrogen gas to discharge through the bottom of
Block where the Nitrogen Cartridge is installed and the SRM or BFR-CAP(s).
then remove the BFR-PRT.
ii. The pressurization indicator of each Test Valve
CAUTION Assembly (when used) will be fully extended and
Before installing the Nitrogen Actuation Cartridge the there are no leaks in the copper tubing.
installer shall inspect the sealing cap for punctures or iii. The gas valve will close, stopping gas flow to any
other damage and verify that the cartridge weighs gas fueled appliances.
more then the stated minimum gross weight stamped
on the cartridge. If any evidence of damage, puncture iv. All auxiliary devices connected to the miniature
or if the cartridge weighs less then minimum gross electrical switch(s) provided in the Systems
weight, discard and replace. Releasing Module will have operated.
Annual maintenance of the Kitchen Mister System is 5. Remove the used nitrogen cartridge and discard
required by NFPA-17A and Buckeye Fire Equipment and immediately.
must be performed by a factory trained, Authorized
Buckeye Fire Equipment Dealer. Annual maintenance 6. Replace all fusible link detectors.
shall include the following:
7. After testing the fusible link line, repair the terminal
1. Check and inspect the system in accordance with link and re-set the control head as described in
steps 1 – 7 of semi-annual maintenance instructions. Chapter 4.
8. Once the Systems Releasing Module is reset, the
mechanical pull station must be checked. To do so,
CAUTION pull the handle on the remote pull station and make
Failure to disconnect the Systems Releasing sure that the following occurs:
Module or Valve Cap(s) from the cylinder valve(s)
prior to the test firing of the nitrogen cartridge will i. The Systems Releasing Module will operate,
cause system discharge (see below). causing the detection arm assembly to move
back to the left, disengaging the trigger, and
allowing the actuation lever to operate.
2. Disconnect the Systems Releasing Module from the
cylinder valve by removing the four screws securing ii. The gas valve will close, stopping gas flow to
the SRM to the top of the valve and separate. DO any gas fueled appliances.
NOT lose or damage the Interface Gasket because it iii. All auxiliary devices connected to the miniature
will be required to reconnect the SRM. If the SRM is electrical switch(s) provided in the Systems
mounted remotely, remove all Model BFR-CAP(s), Releasing Module will have operated.
Valve Cap Assembly from each of the cylinder
valve(s) by unscrewing the four mounting screws
and remove them from the cylinder valve(s).
3. Reinstall the Nitrogen Activation Cartridge.
CAUTION
Before installing the Nitrogen Actuation Cartridge
the installer shall inspect the sealing cap for
punctures or other damage and verify that the
cartridge weighs more then the stated minimum
gross weight stamped on the cartridge. If any
evidence of damage, puncture or if the cartridge
weighs less then minimum gross weight, discard
and replace.
Chapter 6
System Recharge
Overview Valve Rebuild Tool
This chapter will detail the basic procedure for recharging The Model BFR-VRT Valve Rebuilding Tool is required
the system after it has been activated. to properly rebuild the cylinder valve. It is used to hold
the piston in place while the valve stem is unscrewed. If
Recharging the Kitchen Mister System must be in it is not used, valve damage may occur. See Figure 6-2.
compliance with the parameters set forth in this manual
and be performed by a factory trained, Authorized
Buckeye Fire Equipment Dealer. Buckeye Fire
Equipment is not responsible for systems installed or
maintained by personnel that are not factory trained and
Authorized.
Figure 6-2.
Model BFR-VRT,
VALVE REBUILDING COMPONENTS Valve Rebuilding Tool
5. Disconnect the Discharge Adapter from the cylinder 17. Discard any agent that may still be in the cylinder.
valve by unscrewing the two (2) 1/4(0.6 cm)-20 hex
head screws holding the Discharge Adapter Plate to 18. Fill the tank with the required amount of Kitchen
the valve. Slide the Discharge Adapter out of the Mister agent, see chart below.
discharge port of the cylinder. Recharge Agent Quantities Required
6. Remove the cylinder from its mounting bracket by
loosening the mounting strap and lifting off the Cylinder Recharge Required
cylinder. BFR-5 1 x BFR-5R
BFR-10 1 x BFR-10R or
WARNING 2 x BFR-5R
Cylinder assembly is heavy and should be handled
with care. To prevent damage to discharge port and BFR-15 1 x BFR-5R and
piston chamber, an anti-recoil and shipping plate must 1 x BFR-10R
be installed on the cylinder valve whenever the
cylinder is being transported. BFR-20 2 x BFR-10R’s
19. Reinstall the valve and siphon tube into the filled
7. Before proceeding, the entire piping system must be cylinder. The valve must be screwed all the way into
flushed with hot water for a minimum of 10 minutes. the cylinder so that it sit flush with the cylinder neck.
Leaving the nozzles in place will facilitate the The valve must be hand tight when screwed
flushing process. Remove the Discharge Adapter completely into the cylinder neck.
from the piping system and attach the appropriate
20. Install the recharge adaptor and pressurize the
hose adapter needed to flush the piping.
cylinder to 195 psi. (1344 KPa) with dry nitrogen.
8. To assure that no water or chemical is left in the
21. Wait 15 minutes to assure the pressure in the tank is
piping, the piping must be blown out with
still 195 psi (1344 KPa).
compressed air or nitrogen, until the pipe is dry.
22. Pull the detent pin out, to release the valve stem,
9. Make note of each nozzles’ position, then remove all
allowing the valve to close.
system nozzles. Remove the internal strainer from
each, wash all parts in hot soapy water, and rinse. 23. The yellow pointer in the cylinder gauge should be in
the green section of the gauge.
10. Re-install the internal strainer and retaining ring in
each nozzle and inspect the orifice for any damage
or obstruction. Replace the nozzle cap on each CAUTION
nozzle. Never use the cylinder pressure gauge to determine
11. Once all nozzles and piping are dry and clean, the cylinder pressure. A properly calibrated external
nozzles can be re-installed on the system. gauge is required.
2. Composition/Information on Ingredients
3. Hazards Identification
FOR HUMANS:
Product:
E U Classification: Irritant
R 36/37/38 Irritating to eyes, respiratory system, and skin.
Buckeye Fire Equipment Company’s Liquid Fire Suppression Agent (continued) Page 2
Neither this preparation nor the substances contained in it have been listed as carcinogenic by National
Toxicology Program, I.A.R.C., or OSHA.
FOR ENVIRONMENT:
No data available.
Eye Contact: Wash with water for a minimum of 15 minutes. If irritation persists seek medical attention.
Skin Contact: Wash affected area with soap and water. If irritation persists seek medical attention.
Inhalation: Remove from exposure. If irritation persists seek medical attention.
Ingestion: Dilute by drinking large quantities of water.
5. Fire-Fighting Measures
Buckeye Fire Equipment Company’s Liquid Fire Suppression Agent (continued) Page 3
7.1 Handling
Keep Separate from acids. See incompatibility information in Heading 10.
7.2 Storage
NO special conditions are needed for safe storage. See Heading 10 for incompatibilities. Store in original
container. Keep tightly closed until used. There is minimal danger to the environment from a storage release.
Buckeye Fire Equipment Company’s Liquid Fire Suppression Agent (continued) Page 4
12.1 Ecotoxicity
Not determined
12.2 Mobility
Not determined
Buckeye Fire Equipment Company’s Liquid Fire Suppression Agent (continued) Page 5
EU Classification: Irritant
Exposure Limit Values: None
EINECS Status: All components are included in EINECS Inventory or
are exempt from listing
EPA TSCA Status: All components are included in the TSCA Inventory
or are exempt from listing.
Canadian DSL (Domestic Substances List): All components are included in the DSL or are
exempt from listing.
Environmental restrictions: None are known
Restrictions on Marketing and Use: None are known
Refer to any other national measures that may be relevant
EU Classification: Irritant
R 36/37/38 Irritating to eyes, respiratory system, and skin.
S 26 In case of contact with eyes, rinse immediately with
plenty of water and seek medical advice
Buckeye Fire Equipment Company’s Liquid Fire Suppression Agent (continued) Page 6
This product is rated: D2B – Product may irritate skin, eyes, or mucous
membrane.
17. Disclaimer
THE ABOVE INFORMATION IS BELIEVED TO BE CORRECT, BUT DOES NOT PURPORT TO BE ALL
INCLUSIVE AND SHALL BE USED ONLY AS A GUIDE. BUCKEYE FIRE EQUIPMENT COMPANY SHALL
NOT BE HELD LIABLE FOR ANY DAMAGE RESULTING FROM HANDLING OR FROM CONTACT WITH
THE ABOVE PRODUCT.
Appendix B
System Accessories and Supplemental Information
Model MS-DPDT Miniature Switches
RED
Figure B-3.
N.C.
BLACK N.O.
Model MS-AIS,
COM Alarm Initiating Micro Switch
WHITE
WHITE
COM for pipe and conduit are available in either threaded or
compression styles. See chart below for more details.
Buckeye Drill Hole
Model Hood Quickseal Description Size
Number inches (cm )
QS-38P Threaded for 3/8” (17.1 mm OD) PIPE 1-1/8 (2.9)
ALL ELECTRICAL CONNECTIONS
SHALL BE MADE OUTSIDE THE SRM
IN AN APPROVED JUNCTION BOX.
OPTIONAL DPDT
MIRCOSWITCH
4-40 X 1" RD HD SCREW
AND LOCK WASHER QS-50P Threaded for 1/2” (21.3 mm OD) PIPE 1-1/8 (2.9)
Figure B-2. Compression Type for 3/8” (17.1 mm
CQS-38P
OD) PIPE
1-1/8 (2.9)
Model MS-DPDT,
Compression Type for 1/2” (21.3 mm
Installation of MS-DPDT CQS-50P
OD) PIPE
1-1/8 (2.9)
CQS-50C Compression Type for 1/2” (1.3 cm) EMT 1-1/8 (2.9)
NOTE QS-CPA Corner Pulley Adapter 1-1/8 (2.9)
All electrical connections shall be made outside of
the Systems Releasing Module in approved junction
box. Model BFR-PG 195 psi Pressure Gauge
BPN: BFR-TM
January 1, 2013
Appendix B – Accessories
Page B - 2
Revision 5
A Kitchen Mister Owner’s Manual (Model BFR–OM) is WC-116-100, Wire Crimps for 1/16”
supplied with every cylinder or can be purchased (0.16 cm) Cable (100 per package)
separately. The Owners Manual must be given to
restaurant owner or the restaurant owner’s designated The Model WC-116-100 is a tin-plated copper sleeves
representative after system installation is complete (as specifically designed to be used with 1/16” (0.16 cm)
per NFPA 17A Standard for Wet Chemical Extinguishing stainless steel cable.
Systems and NFPA 96 Standard For Ventilation Control
and Fire Protection of Commercial Cooking Operations.)
and thoroughly reviewed with them. Flexible Hex Driver
Tee Pulley Installation The Model BFR-FHD is a flexible 3/16” (0.5 cm) hex
wrench that is used to facilitate the tightening of the hex
screws used to connect the Systems Releasing Module
The Model BFR-TP1 Tee Pulley is used to connect two
to the cylinder valve.
CAUTION
The Model BFR-TP1 Tee Pulley must never be used NOTE: The flexible end of the hex wrench should only
to connect two fusible link lines to the System be used to start the screw, final tightening must be done
Releasing Module. with the rigid part of the hex wrench to insure a tight
seal between the SRM and cylinder valve. See Figure
(2) remote pull stations and/or two (2) mechanical gas B-7.
valves to a single Systems Releasing Module.
CAUTION
When a tee pulley is used to connect two (2) gas valves
Failure to properly tighten hex screws may cause
or mechanical pull stations to a single Systems
system failure.
BPN: BFR-TM
January 1, 2013
Appendix B – Accessories
Page B - 3
Revision 5
SYSTEM
RELEASE REPLACE
CARTRIDGE
prevent the full actuation of the SRM and SRM-D. See
Figure B-9.
BEFORE DATE
SHOWN IN
MODULE WINDOW
VALVE/SRM
1/4 (0.6 cm)-20 X 7/8 (2.2 cm) INTERFACE GASKET
SOCKET HEAD SCREW (4)
USE RIGID END TO
USE FLEXIBLE END TO TIGHTEN SECURELY
START SCREW
Figure B-9.
Model BFR-KPIN
Keeper Pin
COLOR
ID BAND
BFR-FHD
O-RING
[3/16" (0.45 cm)
GROOVE
HEX WRENCH]
Figure B-8. 3. Insert the Keeper Pin into the keeper pin hole and
Model BFR-UBC slide the hook of the Keeper Pin over the Detection
Nozzle Cap Installation Arm. The Keeper Pin hook must engage the
Detection Arm completely. See Figure B-11.
BPN: BFR-TM
January 1, 2013
Appendix B – Accessories
Page B - 4
Revision 5
4. Remove hex wrench. Note gap between Catch and 3. Remove BFR-FHD and check that control head is
Detection Arm. The detection line can now be now in the SET position.
released without actuating the gas valve or micro
switches. See Figure B-12 4. Replace nitrogen Cartridge and put SRM back into
CAUTION
Before installing the Nitrogen Actuation Cartridge
the installer shall inspect the sealing cap for
punctures or other damage and verify that the
cartridge weighs more then the stated minimum
gross weight stamped on the cartridge. If any
evidence of damage, puncture or if the cartridge
weighs less then minimum gross weight, discard
and replace.
GAP service.
Figure B-12.
Keeper Pin Installed
The SRM-D follows the same procedure as the SRM.
Once the primary detection line is secured, the
To remove the Keeper Pin: secondary line can be secured following the same
procedure given for the SRM primary line. Refer to
1. Reset the Fusible Link Line by rotating the Detection figures B-15 and B-16 for location of secondary keeper
Arm Assembly until all the slack has been removed pin.
from the fusible link line and the Detection Arm hits
the stop and the Catch is engaged. See Figure B- SECOND
13. FUSIBLE
LINK LINE
SECONDARY
KEEPER
PIN HOLE
CATCH ENGAGED
Figure B-13.
Locating 3/16” (0.45 cm) Hex Head Figure B-15.
Locating Secondary Keeper Pin Hole
2. Locate the 3/16” Hex Head Socket and insert the
BFR-FHD into it. Rotate the BFR-FHD clockwise
and disengage the Keeper Pin hook from the DETECTION
TRIGGERS
Detection Trigger. Remove the Keeper Pin
SECONDARY
assembly slowly rotate the BFR-FHD counter- KEEPER
PIN
clockwise until the Detection Trigger engages the
Catch. See Figure B-14.
ACTUATION
LEVER (SET
POSITION)
GAS VALVE
RATCHET
ENGAGED
Figure B-14.
Keeper Pin Installed
BPN: BFR-TM
January 1, 2013