Вы находитесь на странице: 1из 6

BITZER Output data

Created on : 20/07/2017 23.59.36


BITZER Software v6.7.0 rev1837 20/07/2017 / All data subject to change. 2/6

Table of content

Project survey............................................................................................................................................................ 3
Selection: Water-cooled Condensers........................................................................................................................ 4
Technical Data: K073H.............................................................................................................................................. 5
Information: Water-cooled Condensers..................................................................................................................... 6
BITZER Software v6.7.0 rev1837 20/07/2017 / All data subject to change. 3/6

Project survey
Selected compressors
Water-cooled Condensers 1x K073H
BITZER Software v6.7.0 rev1837 20/07/2017 / All data subject to change. 4/6

Selection: Water-cooled Condensers


Input Values
Condenser type K073H
Passes no. 2
Series Standard
Refrigerant R22
Cooling agent Water
Condensing temperature 39,0 °C
Water inlet temp. 29,0 °C
Volume flow 1,38 m³/h
Liq. subc. (in condenser) 1,00 K
Fouling factor 0,000040 m²K/W

Result
Condenser type K073H
Passes no. 2
Condenser Capacity 7,92 kW
Allowed max. capacity 15,30 kW
Condensing SDT 39,0 °C
Water outlet temp. 34,0 °C
Volume flow 1,38 m³/h
Vol.flow min. 0,85 m³/h
Vol.flow max. 2,75 m³/h
Fluid velocity 0,80 m/s
Pressure drop 0,03 bar
Water speed < 1,0 m/s (Influence of fouling!).
BITZER Software v6.7.0 rev1837 20/07/2017 / All data subject to change. 5/6

Technical Data: K073H


Dimensions and Connections

Technical Data
Technical Data
Weight 11 kg
Total width 602 mm
Total height 184 mm
Jacket tube diameter 108 mm
Refrigerant inlet 12 mm - 1/2''
Refrigerant outlet 10 mm - 3/8''
Coolant inlet (2 passes) 2 x 1/2''
Coolant outlet (2 passes) 3/4''
Coolant inlet (4 passes) 1/2''
Coolant outlet (4 passes) 1/2''
Receiver volume refrigerant 3,4 dm3
Max. refrigerant charge 90% at 20°C
R22 3,7 kg
R134a 3,8 kg
R407C 3,5 kg
R404A/R507A 3,3 kg
Max. pressure 33 bar
Max. Operating Temperature 120°C
Max pressure coolant side 10 bar
Larger inlet connection 16 mm - 5/8''
Available Options
2 fixing rails (above) Option
2 fixing rails (below) Option
BITZER Software v6.7.0 rev1837 20/07/2017 / All data subject to change. 6/6
Water-cooled Condensers

Water-cooled Condensers
Legend of connection positions according to "Dimensions":
1 Refrigerant inlet
2 Refrigerant outlet
2a alternitive Refrigerant outlet
3 Coolant inlet
3a 4 passes
3b 2 passes
4 Coolant outlet
4a 4 passes
4b 2 passes
5 Coolant drain
6 Pressure gauge connection
7 Pressure relief valve connection
Dimensions can show tolerances according to EN ISO 13920-B.

Вам также может понравиться