Specification
Specification for:
Table of Content:
1. Scope......................................................................................................................................... 2
2. General ...................................................................................................................................... 2
3. Standards .................................................................................................................................. 2
4. Ratings....................................................................................................................................... 2
5. Technical features ..................................................................................................................... 3
5.1. Switching medium - Vacuum Interrupters and pole design ............................................... 3
5.2. Operating Mechanism ....................................................................................................... 3
5.3. Housing of switch unit ....................................................................................................... 3
5.4. Current transformer ........................................................................................................... 3
5.5. Voltage sensing................................................................................................................. 4
5.6. Interfaces .......................................................................................................................... 4
5.7. Installation ......................................................................................................................... 4
5.8. Controller cubicle .............................................................................................................. 4
5.9. Power supply..................................................................................................................... 4
5.10. Control Features................................................................................................................ 4
5.11. Controller features............................................................................................................. 5
5.12. Optional Accessories ........................................................................................................ 6
6. Test............................................................................................................................................ 6
6.1. Type Test .......................................................................................................................... 6
1. Scope
This specification applies to electronically controlled three-phase vacuum reclosers for use in
distribution and sub transmission networks with maximum system voltage of up to 38 kV.
Reclosers comprise both, the pole-top vacuum circuit breaker and the recloser control being
the protection and control unit.
2. General
This specification is for an automatic three-phase recloser, designed for outdoor application in
overhead systems. It must include the switch unit (or called recloser tank) and the controller,
which has the control and protection functions to sense over currents, time and interrupt fault
currents, and reenergize the distribution circuit by reclosing automatically. The controller can
be operated locally or by remote operation. It is housed in an outdoor cabinet separate from
the switch unit. This cabinet also includes the uninterruptible power supply, communication
unit and further accessories.
The recloser is operated by a magnetic actuator with a mechanical link between the three
phases to ensure correct fault interruption. It uses vacuum tubes for switching load and fault
currents. The vacuum interrupters are fully encapsulated in cycloaliphatic epoxy resin, proven
to be the most reliable insulation for outdoor applications. Oil and SF6 insulation are strictly
avoided ensuring the highest level of environmental compatibility.
3. Standards
ANSI C37.60: IEEE Standard requirements for Overhead, Pad mounted, Dry vault, and
Sumersible Automatic Circuit Reclosers and Fault Interrupters for AC Systems.
IEC 62271, IEC 60694, IEC 60255, IEC 60044
4. Ratings
1
GOST Standard
2
Without maintenance
5. Technical features
5.1. Switching medium - Vacuum Interrupters and pole design
• Load and fault current interruption and reclosing must use vacuum interrupters
• Vacuum interrupters from manufacturer with more then 3 decades of experience in
vacuum tubes and circuit breaker design
• Solid insulation made out of cycloaliphatic epoxy being the most reliable and long
term proven outdoor insulation
• Creepage distance of 810 mm (for up to 27 kV) suitable for application in very heavy
polluted environment
• Life time of more than 20 years
5.6. Interfaces
• Control cable to connect switch unit and Controller with 6m length as minimum
• Cable with special shielding for voltage measurement providing protection against
electromagnetic disturbances
• Weather proof connections on both switch unit and controller cubicle for easy
mounting
• NEMA type terminal connectors
5.7. Installation
• Recloser configurations for pole top or substation application
• Galvanized design
• Special design to support easy installation
• Autoreclose
• Lockout
• Negative phase sequence overcurrent
• Thermal overload
• Inrush restraint
• Cold load pickup
• Under/overfrequency
• Circuit breaker fail
• Circuit breaker close fail
• Voltage dependent overcurrent
• Neutral voltage displacement
• CT supervision
• VT supervision
• Trip circuit supervision
• Battery and capacitor test and monitoring
• Programmable logic
• Loop automation by loss of voltage; Fault Locator
• Metering of power quality
• Load profile recording
• TCC for IEC, ANSII and Legacy curves
• TC-Curve editor
• Programmable BI / BO logic (AND / OR / NOT / XOR)
• Surge arresters
• Transformator for auxiliary supply voltage
• Additional pushbutton on/off
6. Test