Вы находитесь на странице: 1из 2

C&D TECHNOLOGIES, INC.

1400 UNION MEETING ROAD


BLUE BELL, PA 19422-0858
(215) 619-2700
FAX: (215) 619-7840

COMPANY: DATE: 3/23/2014


SIZED BY: Sandeep Menon
REF: IEEE STD.: 485-2010

MINIMUM
SIZING BASIS
LOWEST DESIGN DESIGN msEndur
48.0 F 1.94 PLATE
TEMPERATURE CELL II AT-P
NOMENCLATURE
VOLTAGE
Duration Time to Capacity Required Section
Change in Load
Load Load of Load End of Amperes Cell Size Positive
(amperes)
Period (amperes) Period Section per Plates
+ Values - Values (minutes) (minutes) Pos. Plate + Values - Values
SECTION 1
1 151.32 151.32 1 1 50.49 2.997
SECTION 1
2.997
TOTAL:
SECTION 2
1 151.32 151.32 1 450 10.69 14.151
2 141.99 9.32 449 449 10.71 0.870
SECTION 2
13.281
TOTAL:
SECTION 3
1 151.32 151.32 1 479 10.18 14.865
2 141.99 9.32 449 478 10.20 0.914
3 182.95 40.96 29 29 43.80 0.935
SECTION 3
14.886
TOTAL:
SECTION 4
1 151.32 151.32 1 480 10.16 14.890
2 141.99 9.32 449 479 10.18 0.916
3 182.95 40.96 29 30 43.57 0.940
4 212.54 29.59 1 1 50.49 0.586
SECTION 4
15.500
TOTAL:

MAXIMUM + RANDOM
15.50 0.00 = Base Design Size 15.50
SELECTED SIZE LOAD SIZE
X Temperature Correction 1.214
BASE DESIGN
X Design Margin 1.20
MULTIPLIERS
X Aging Factor 1.25
= NUMBER OF POSITIVE
28.23
PLATE

POSITIVE PLATES 10 Strings per System 3 Cell Model AT-21P


CELLS PER JAR 1

FORM # BSP-A1 REV DATE 3/21/05


Sunday, March 23, 2014
© 2014 C&D Technologies, Inc.
All critical calculations must be verified with C&D applications.
Specifications are subject to change without notice.