Air System Sizing Summary for Default System

Project Name: Untitled 04/23/2018


Prepared by: csec 07:32PM

Air System Information


Air System Name Default System Number of zones 1
Equipment Class PKG VERT Floor Area 4413.0 ft²
Air System Type SZCAV Location Colombo, Sri Lanka

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 26.1 Tons Load occurs at Aug 1400
Total coil load 313.6 MBH OA DB / WB 94.4 / 81.1 °F
Sensible coil load 271.1 MBH Entering DB / WB 76.8 / 63.8 °F
Coil CFM at Aug 1400 12278 CFM Leaving DB / WB 56.3 / 55.1 °F
Max block CFM 12278 CFM Coil ADP 54.0 °F
Sum of peak zone CFM 12278 CFM Bypass Factor 0.100
Sensible heat ratio 0.865 Resulting RH 48 %
ft²/Ton 168.9 Design supply temp. 55.0 °F
BTU/(hr-ft²) 71.1 Zone T-stat Check 1 of 1 OK
Water flow @ 10.0 °F rise N/A Max zone temperature deviation 0.0 °F

Supply Fan Sizing Data


Actual max CFM 12278 CFM Fan motor BHP 0.00 BHP
Standard CFM 12267 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 2.78 CFM/ft² Fan static 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM 490 CFM CFM/person 16.33 CFM/person
CFM/ft² 0.11 CFM/ft²

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for Default System
Project Name: Untitled 04/23/2018
Prepared by: csec 07:32PM

Air System Information


Air System Name Default System Number of zones 1
Equipment Class PKG VERT Floor Area 4413.0 ft²
Air System Type SZCAV Location Colombo, Sri Lanka

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 265.0 12278 12278 Aug 1500 1.4 4413.0 2.78

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
Default Space 1 265.0 Aug 1500 12278 1.4 4413.0 2.78

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for Default System
Project Name: Untitled 04/23/2018
Prepared by: csec 07:32PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.4 °F / 81.1 °F HEATING OA DB / WB 69.0 °F / 57.6 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 1970 ft² 135692 - 1970 ft² - -
Wall Transmission 4136 ft² 6775 - 4136 ft² 193 -
Roof Transmission 2323 ft² 3892 - 2323 ft² 96 -
Window Transmission 1280 ft² 13251 - 1280 ft² 730 -
Skylight Transmission 690 ft² 7143 - 690 ft² 393 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 4413 ft² 0 - 4413 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 6178 W 21080 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11474 W 39148 - 0 0 -
People 30 7350 6150 0 0 0
Infiltration - 4156 10009 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 23849 1616 0% 0 0
>> Total Zone Loads - 262336 17775 - 1412 0
Zone Conditioning - 261397 17775 - 47 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 12278 CFM 0 - 12278 CFM 0 -
Ventilation Load 490 CFM 9707 24685 490 CFM 164 24
Supply Fan Load 12278 CFM 0 - 12278 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 271104 42461 - 211 24
Central Cooling Coil - 271104 42487 - 0 0
>> Total Conditioning - 271104 42487 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


System Psychrometrics for Default System
Project Name: Untitled 04/23/2018
Prepared by: csec 07:32PM

August DESIGN COOLING DAY, 1400

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 94.4 0.01989 490 400 9707 24685
Vent - Return Mixing Outlet 76.8 0.00968 12278 806 - -
Central Cooling Coil Outlet 56.3 0.00895 12278 806 271104 42487
Supply Fan Outlet 56.3 0.00895 12278 806 0 -
Cold Supply Duct Outlet 56.3 0.00895 12278 806 - -
Zone Air - 76.0 0.00926 12278 822 261397 17775
Return Plenum Outlet 76.0 0.00926 12278 822 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4742.5 BTU/(hr-CFM)
Site Altitude = 24.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 262336 Cooling 261397 76.0 12278 822 0 0

Hourly Analysis Program v4.90 Page 4 of 6


System Psychrometrics for Default System
Project Name: Untitled 04/23/2018
Prepared by: csec 07:32PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 69.0 0.00751 490 400 -164 -24
Vent - Return Mixing Outlet 69.3 0.00752 12278 636 - -
Central Cooling Coil Outlet 69.3 0.00752 12278 636 0 0
Supply Fan Outlet 69.3 0.00752 12278 636 0 -
Cold Supply Duct Outlet 69.3 0.00752 12278 636 - -
Zone Air - 69.3 0.00752 12278 645 -47 0
Return Plenum Outlet 69.3 0.00752 12278 645 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4742.5 BTU/(hr-CFM)
Site Altitude = 24.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -1412 Deadband -47 69.3 12278 645 0 0

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for Default System
Project Name: Untitled 04/23/2018
Prepared by: csec 07:32PM

Location: Colombo, Sri Lanka


Altitude: 24.0 ft.
Data for: August DESIGN COOLING DAY, 1400
1
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0.018
5. Room Air

0.016

Specific Humidity ( lb/lb )


0.014

0.012
2
34 0.010
5
0.008

0.006

0.004

0.002

0.000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program v4.90 Page 6 of 6