Вы находитесь на странице: 1из 10

YILDIZ TECHNICAL UNIVERSITY

FACULTY OF ELECRICAL AND ELECTRONICS ENGINEERING


DEPARTMENT OF ELECTRICAL ENGINEERING

FLEXIBLE AC TRANSMISSION LINE

TERM PROJECT

Static Var Compensator Power Control Circuit Implemented in PSIM

PREPARED BY
----------------------

HOMEWORK ADVISOR
-----------------------------------

İSTANBUL, 2017
SVC - Static VAr Compensation Systems

Static VAr Compensation (SVC) System is one kind of compensation systems consisting of static, or
semi-conductor, switching elements. The first technologies that come to mind when SVC is
considered are Thyristor Controlled Reactor (TCR) and Thyristor Switched Capacitor (TSC)
systems.
SVC systems are being used for voltage regulation, current/voltage harmonics filtering, power factor
improvement, load balancing and flicker compensation issues in such systems where reactive power
demand is varying very fast, and loads are unbalanced and rich in harmonics . Hence, SVC systems
are commonly preferred in industries having arc, ladle and induction furnaces, rolling mills,
hoist/cranes and welding machines. SVC systems are also used in transmission and distribution
systems for reactive power compensation, voltage regulation and improvement of system stability.

PRİMARY BENEFİTS
 Reduction in active energy losses as a fact of improving reactive power flow and filtering
harmonics
 Improvement in system stability with load balancing and flicker compensation
 Better utilization of the capacity in transmission and distribution systems
 Increasing the quality of supply
 Reduction of unit-costs in iron and steel industry
 In result, increase in energy efficiency

Our Homework SVC System


SVC CHARACTERİSTİC WAVEFORMS IN OPEN LOOPS MODE

Our Homework Open Loop SVC System


Isvc

100K

50K

0K

-50K

-100K

0 0.2 0.4 0.6 0.8 1


Time (s)

SVC Current (Isvc) Value When Open Loop Mode

Vload

20K

10K

0K

-10K

-20K

0 0.2 0.4 0.6 0.8 1


Time (s)

System Voltage ( Vload ) Value When Open Loop Mode


Vrms

0.8

0.6

0.4

0.2

0 0.2 0.4 0.6 0.8 1


Time (s)

Voltage RMS ( Vrms ) Value When Open LoopMode


VL

20K

10K

0K

-10K

-20K

0 0.2 0.4 0.6 0.8 1


Time (s)

IL

100K

50K

0K

-50K

-100K

0 0.2 0.4 0.6 0.8 1


Time (s)

VC

20K

10K

0K

-10K

-20K

0 0.2 0.4 0.6 0.8 1


Time (s)
IC

100K

50K

0K

-50K

-100K

0 0.2 0.4 0.6 0.8 1


Time (s)

VL IL Vc Ic Values When Open Loop Mode


PROCESS STEPS

 There are one fixed load group and one variable load group in our system.
 And we want the power factor to remain constant when a load group is added to the
system.
 Therefore, we are designing a control circuit to keep the power factor constant.
 Initially , we first plotted the svc circuit given to us.
 After this, we calculated the required values and wrote them.
 Then, we made a control circuit using the elements like comparator, logic gate, voltage
sensor, thyristor, rms block, PI controller etc.

CALCULATİONS

(13.8x1000)2
R1   3.174
60 x106

(13.8x1000)2
R2   11.174
162 x106

(13.8x1000)2
X L1   4.761
40 x106

(13.8x1000)2
X L2   0.238
800 x106

4.761  2 x50 xL1

L1  0.0151546H

0.238  2 x50 xL2

L2  0.000758H
SVC CHARACTERİSTİC WAVEFORMS IN CLOSED LOOP MODE

Our Homework Closed Loop SVC System


 First of all, we generated the Vrms signal needed to send to PI block.
 So, the effective value of the load voltage was divided by the constant of 13.8k.

Closed Loop RMS Block in SVC System

 Then, we generated the Piout signal needed to keep the power factor constant.
 Therefore, the coefficients of PI circuit used are 0.2 and 0.001

Closed Loop PI Block in SVC System

 Then, we produce square wave signal.


 It is produced by comparing the square wave signal voltage source with the comparator
 The profit value of the proportional block used was 12 .

Closed Loop PI Sawtooth Signal Block in SVC System


Isvc

200K

100K

0K

-100K

-200K

-300K

0 0.2 0.4 0.6 0.8 1


Time (s)

SVC Current (Isvc) Value When Closed Loop Mode

Vload

40K

20K

0K

-20K

-40K

0 0.2 0.4 0.6 0.8 1


Time (s)

System Voltage ( Vload ) Value When Closed Loop Mode


Vrms

1.4

1.2

0.8

0.6

0.4

0.2

0 0.2 0.4 0.6 0.8 1


Time (s)

Voltage RMS ( Vrms ) Value When Closed LoopMode


VL

40K

20K

0K

-20K

-40K

0 0.2 0.4 0.6 0.8 1


Time (s)

IL

300K

200K

100K

0K

-100K

-200K

0 0.2 0.4 0.6 0.8 1


Time (s)

Vc

40K

20K

0K

-20K

-40K

0 0.2 0.4 0.6 0.8 1


Time (s)

IC

300K

200K

100K

0K

-100K

-200K

-300K

0 0.2 0.4 0.6 0.8 1


Time (s)

VL IL Vc Ic Values When Closed Loop Mode