Вы находитесь на странице: 1из 1

Sultanate of Oman

Ministry of Transport & Doc. Number: SA-905-P-11408 Sht 1 of 1


Communications Piping Class: ANSI 150

Development of Muscat & Salalah International Airports


LEVEL TRANSMITTER
REQ./P.O. NO.
Issued for Tender. Ref.
T02 17.06.2009 NGUT CVST LVHA NIER CONTRACT NO.
Addendum 3
T01 Not issued for Tender 17.06.2009 NGUT CVST LVHA NIER MANUFACT. & MODEL NO.*)
REV DESCRIPTION DATE PREP'D CHK'D APPR'D APPR'D COUNTRY OF ORIGIN *)
PLANT SPECIFIC DATA REV
DESCRIPTION SPECIFIED VENDOR DATA
1 AMBIENT TEMPERATURE °C 10 / +55
2 HUMIDITY % 95
3 ENVIRONMENT SALIFEROUS, DUSTY
4 AREA CLASSIFICATION EEx Zone 2
5 METROLOGICAL SEAL (yes/no) Yes, sun shade
EQUIPMENT SPECIFIC DATA
5 SERVICE (Located at) Underground tanks
6 TYPE Guided radar
7
8 DESIGN
9 FLUID (Type and phase) JET fuel A1, Liquid
10 PRESSURE RATING barg 15
11 TEMPERATURE RATING °C 85
12 TEMPERATURE COMPENSATION Automatic
13 CALIBRATED RANGE Metres 5
14 DEAD BAND Metres 0.1
15 ACCURACY +/- 3 mm
16 LOCAL DISPLAY Yes/No Yes
17 SENSOR LENGHT Metres See instrumentation list
18
19
20
21 MATERIAL
22 HOUSING 316L SS
23 TRANSDUCER 316L SS
24 SEALS EPDM
25 SOUR SERVICE NO
26
27 CONNECTION
28 ELECTRICAL M20
29 PROCESS CONNECTION Flange 150# Size vendor to advise
30
31
32 PROTECTION
33 ENCLOSURE IP55
34 ELECTRICAL EEx ia II C T3
35
36 TRANSMISSION
37 SUPPLY Through fieldbus
38 COMMUNICATION Fieldbus, (Profibus or Foundation)
39 LOCAL DISPLAY (INTEGRATED) Yes, if indicated in the instrumentation list
40
41 IDENTIFICATION
42 TAG NO SS Tag engraved or screwed on housing
43
44 CERTIFICATION
45 PRESSURE RETAINING PARTS EN 10204 2.1
46 Eex ATEX
47 TOTAL SUPPLY Statement of Compliance

*) ALL INCLUDING SHADED FIELDS TO BE COMPLETED BY SUPPLIER, REQUIREMENTS SPECIFIED NEXT TO SHADED FIELDS ARE COMPULSORY
P:\61400\4_TEC\R_O_P_Equip._&_Utilities\04_Utility_Fuel\SA-Fuel_Farm_&_PS\07_Specifications\Data Sheets\07 Instrumentation\[SA_980_P_11408_Level_transmitter Rev T02.xls]Level Transmitter